43
04/24999499
SHE control panel TRZ Plus DG
Technical datas
The power supplies and electrical control equipment are to be operated exclusively with the components authorised by
the manufacturer.
Electrical properties
Primary energy supply
Operating voltage supply:
230 V AC / 50 Hz, (±10 %), separately fused
System voltage:
27 V DC (nominal) (-25 % / +10 %)
Power consumption:
max. 75 W
Monitoring:
yes,
Software
monitoring
Terminal:
screw terminals max. 2.5 mm²
Fuse:
F1 fuse: Print-fuse 1.25 A/T TE5 250 V
Secondary energy supply
Batteries:
2 x 12 V, 1,2 Ah, VdS
Battery type:
lead gel battery
Emergency power:
72 h
Charging time:
20 h for emergency power
Terminal:
max 1.5 mm², 4.8 blade terminal with insulating bush 200 mm long
Monitoring:
yes, cyclical, total discharge prot.
Fuse:
F3
battery,
FKS
5A
Output
Voltage:
27 V DC (nominal), (-25 % / +10 %) smooth
Ripple:
<1
%
Power (nominal):
2 A, 30 % ED
Power (temporary):
2.6 A (
≤
600 ms)
Cable monitoring function:
current monitoring
Terminal:
max. 2.5 mm², screw terminal
Fuse:
FKS
5A
Call point output
Voltage:
24
V
nominal
Power:
max. 60 mA, 100% ED
Terminal:
max. 1 mm², spring terminal
Max.
pieces:
10
Emergency power:
yes
Automatic alarm unit output
Voltage:
24
V
nominal
Power:
max. 150 mA, 100% ED
Terminal:
max. 1 mm², spring terminal
Cable monitoring function:
end resisted 10k or active end module
Max.
pieces:
10
Emergency power:
yes
Buzzer/Signal lamp output
Voltage:
27
V
nominal
Power:
max. 100 mA, 100% ED
Terminal:
max. 1 mm², spring terminal
Cable monitoring function:
no
Max.
pieces:
1
Emergency power supply:
no
Fuse:
no