41
04/24999499
Troubleshooting
Display - operating OK - is not shining
in the SHE manual call points and the control panel:
• a malfunction has occurred (see malfunction - beep code - chart).
• mains power connection out of order:
- check mains supply lead / voltage.
- check mains fuse.
• batteries out of order:
- check battery fuse.
- check battery connection.
- defective batteries, to be replaced.
• Sliding switch are in position “secured“
The electromagnetic clamps open without pressing a switch
• SHE manual call point incorrectly connected or defective a check and correct.
• autom. detector soiled. Detector replace.
Capacitance of storage batteries is inadequately for 72 h network compensational operation
The measurement of the current draw for testing the capacitance of the storage batteries has to be done in standby
mode. It may not happen directly after a pressurized gas activation. The standby mode is initiate automatically
3 minutes after a reset.
All LED displays are dark (without mains 230 V / 50 Hz)
• discharge totally battery, take off fuse (battery) disconnect emergency batteries and wait at least 2 minutes. Replace by
new emergency batteries and connect them, replace fuse.
Malfunction - beep code - chart
The pulse sequence gives information regarding the source of the malfunction. The continuous acoustical signal rings
out only by SHE man. call point with buzzer and if the door contact switch is pressed.
Maintenance
(steady
fl
ash)
The green LED
OK
- Operation OK -
fl
ashes steadily:
Reset or setting of maintenance timer by con
fi
guration-software of TRZ Plus DG.
For more information please see technical information of PC Software Service Port of TRZ Plus DG.
all OK
mains failure
battery failure
malfunction SHE man. call point
malfunction autom. detector
malfunction psg-monitoring circuit
memory error
maintenance
SHE control panel TRZ Plus DG
0 x
1 x
2 x
5 x
4 x
3 x
8 x