Installation, operation and maintenance manual - FMA 2000
Ref: 2000/CPF01/230/VH
19
9. – STARTING INSTRUCTIONS.
Check previous section instructions.
Check the hydraulic circuit (see section 15) that provides the backwashing valve with
water, making sure that:
o
¾” filter is clean.
o
The ball valve is open.
o
The 3 way valve value is in AUTO position.
o
Start with the following shut-off valves configuration:
o
Inlet valve: OPEN
o
Outlet valve: CLOSE.
o
By – pass (If it exists): CLOSE
Switch on the filter, put the circuit breaker ON
Make sure that the programmable relay is on the selected option RUN
Manual backwash by pressing the limp button.
The backwashing cycle evolution is detailed in section 12.2.
Open outlet valve.
A drop in pressure and water flow increase is produced when the water mains is filled in.
That is why it is advisable to install an outlet pressure valve, making sure that the water
mains filling is controlled.
NOTE
IN CASE A SUPPORTING PRESSURE IS NOT INSTALLED, DURING THE
WATER MAINS FILLING, CLOSE THE OUTLET VALVE UNTIL GETTING 2
BAR IN THE CLEAN WATER PRESSURE GAUGE.
ONCE THE WATER MAINS IS PRESSURIZED, OPEN THE OUTLET
VALVE TO GET A CORRECT OPERATION.
Make sure that water flow and pressure installation correspond with the maximum values
defined for this manual model. See section 6
Check the equipment operation and the head loss when the starting up is finished.
Summary of Contents for FMA-2000 series
Page 5: ...Installation operation and maintenance manual FMA 2000 Ref 2000 CPF01 230 VH 5 ...
Page 7: ...Installation operation and maintenance manual FMA 2000 Ref 2000 CPF01 230 VH 7 2 WARRANTY ...
Page 15: ...Installation operation and maintenance manual FMA 2000 Ref 2000 CPF01 230 VH 15 ...
Page 16: ...Installation operation and maintenance manual FMA 2000 Ref 2000 CPF01 230 VH 16 ...
Page 24: ...Installation operation and maintenance manual FMA 2000 Ref 2000 CPF01 230 VH 24 LG FA IC DIF ...
Page 34: ...Installation operation and maintenance manual FMA 2000 Ref 2000 CPF01 230 VH 34 Layout 2 of 2 ...
Page 41: ...Installation operation and maintenance manual FMA 2000 Ref 2000 CPF01 230 VH 41 ...
Page 42: ...Installation operation and maintenance manual FMA 2000 Ref 2000 CPF01 230 VH 42 ...
Page 43: ...Installation operation and maintenance manual FMA 2000 Ref 2000 CPF01 230 VH 43 ...
Page 44: ...Installation operation and maintenance manual FMA 2000 Ref 2000 CPF01 230 VH 44 ...