background image

Figure 4 - Pipe Installation, Standard Controls

 Never use an open fl ame to detect 

gas leaks. Explosive conditions may exist which 
would result in personal injury or death.

The appliance and its individual shutoff valve must 
be disconnected from the gas supply piping system         
during any pressure testing of that system at test 
pressures in excess of 1/2 psig (3.5 kPa).

The appliance must be isolated from the gas supply 
piping system by closing its individual manual shutoff 
valve during any pressure testing of the gas supply 
piping system at test pressures equal to or less than 
1/2 psig (3.5 kPa).  

Table 4 - Gas Piping Requirements

SINGLE STAGE GAS PIPING REQUIREMENTS*

GasType  

 

Natural Gas  

Propane (LP) Gas

Manifold

 

 

3.5 in. W.C. 

10.0 in. W.C.

Pressure

 

 

(0.9 kPa) 

(2.5 kPa)

 

 

14.0 in. W.C. Max. 

14.0 in. W.C. Max.

Supply Inlet

   

(3.5 kPa) 

(3.5 kPa)

Pressure

 

 

5.0 in. W.C. Min. 

11.0 in W.C. Min.

 

(1.2 kPa) 

(2.7 kPa)

*

For single stage application only at normal altitudes.

TWO STAGE GAS PIPING REQUIREMENTS**

Gas Type

 

Natural Gas 

Propane (LP) Gas

Supply Inlet

 

6.5 in. W.C. Min. 

11.5 in. W.C. Min.

Pressure

 

(1.6 kPa) 

(2.9 kPa)

**For two stage applications only at normal altitudes. 

8

PIPE INSTALLATION

1.  Install the gas piping in accordance with 

               

applicable local codes.

2.  Check gas supply pressure. Each unit heater must 

be connected to a manifold pressure and a gas 
supply capable of supplying its full rated capacity 
(refer to Table 4). A field LP tank regulator must 
be used to limit the supply pressure to maximum 
of 14 in. W.C. (3.5 kPa). All piping should be sized 
in accordance with the latest edition of ANSI 
Standard Z223.1, National Fuel Gas Code; in 
Canada, according to CSA-B149. See Tables 1 and 
3 for correct gas supply piping size. If gas pressure 
is excessive on natural gas applications, install a 
pressure regulating valve in the line upstream from 
the main shutoff valve.

3.  Adequately support the piping to prevent strain on 

the gas manifold and controls.

4.  To prevent the mixing of moisture with gas, run        

the take-off piping from the top, or side, of the             
main.

5.  Standard gas duct furnaces, optional two-stage     

units, and hydraulic modulating units are supplied 
with a combination valve which includes:

 

(a) Manual “A” valve (b) Manual “B” valve 

                

(c) Solenoid valve (d) Pilot safety (e) Pressure        
regulator

 

Pipe directly in to combination valve (see Figure 4).

6.  A 1/8 in. N.P.T. plugged tapping, accessible for test 

gauge connection, must be installed immediately 
upstream of the gas supply connection to the 
appliance.

7.  Provide a drip leg in the gas piping near the gas      

unit heater. A ground joint union and a manual 
gas shutoff valve should be installed ahead of 
the unit heater controls to permit servicing. The             
manual main shutoff valve must be located external 
to the jacket. See Figure 4.

8.  Make cer tain that all connections have been             

adequately doped and tightened. 

 

 Do not overtighten the inlet gas 

piping into the valve. This may cause stresses 
that would crack the valve!

NOTICE: Use pipe joint sealant resistant to the 
action of liquefied petroleum gases regardless of 
gas conducted.

 Check all pipe joints for leakage    

using a soap solution or other approved method. 
Never use an open flame or severe personal 
injury or death may occur.

D3631C

Summary of Contents for QVEF 100 M

Page 1: ...instructions to avoid exposure to fuel substances or substances from incomplete combustion which can cause death or serious illness The state of California has determined that these substances may ca...

Page 2: ...have any questions after reading this manual contact the manufacturer See Identification of Parts Section for unit components Front View Rear View Indicates an imminently hazardous situation which if...

Page 3: ...ied individual per instructions in this manual Also follow procedures listed on the Gas Equipment Start Up Sheet located in this manual 3 GENERAL SAFETY INFORMATION 1 foot 0 305 m 1 inch 25 4 mm 1 psi...

Page 4: ...9 0 186 0 249 0 249 Motor Type SP SP PSC PSC PSC PSC PSC PSC PSC PSC R P M 1 050 1 050 1 140 1 140 1 140 1 140 1 140 1 140 1 140 1 140 Amps 115V 2 6 4 2 4 7 5 8 5 8 5 8 5 8 9 4 11 6 11 6 DIMENSIONAL D...

Page 5: ...must not be installed in locations where air for combustion would contain chlorinated halogenated or acidic vapors If located in such an environment premature failure of the unit will occur Since the...

Page 6: ...e between walls and the vertical sides of the Unit Heater shall be no less than 18 inches 457mm A minimum clearance of 6 inches 152mm must be maintained between the top of the Unit Heater and the ceil...

Page 7: ...tiply the Cu Ft Hr Cubic Meters per Hour value by 0 633 then use the table 4 Refer to the metric conversion factors listed in General Safety section for more SI unit measurements conversions To avoid...

Page 8: ...ing should be sized in accordance with the latest edition of ANSI Standard Z223 1 National Fuel Gas Code in Canada according to CSA B149 See Tables 1 and 3 for correct gas supply piping size If gas pr...

Page 9: ...ersonal injury or death Standard units are shipped for use on 115 volt 60 hertz single phase electric power The motor nameplate and electrical rating on the transformer should be checked before energi...

Page 10: ...regarding these venting conditions CARBON MONOXIDE Your venting system must not be blocked by any snow snow drifts or any foreign matter Inspect your venting system to ensure adequate ventilation exi...

Page 11: ...llow this procedure 1 Hold power venter motor in position 2 Remove the three Phillips head screws from the motor adaptor plate 3 Remove the three screws which connect the power venter stack to the pow...

Page 12: ...12 Figure 10A VENTING continued Figure 10B...

Page 13: ...13 Figure 10C VENTING continued Figure 10D...

Page 14: ...isting of a power venter motor and blower pressure switch and sealed flue collector in place of the conventional draft diverter The addition of external draft hoods or power ventors is not permitted A...

Page 15: ...ywell Pilot Burner 13 High Limit This safety device is located on the rear header plate of the heat exchanger air inlet side 15 13 Figure 11 Burner Components Intermittent Pilot Ignition Also refer to...

Page 16: ...C 0 9 kPa Adjustment of the pressure regulator is not normally necessary since it is preset at the factory However field adjustment may be made as follows a Attach manometer at pressure tap plug adja...

Page 17: ...e minimum clearance requirements listed in this manual Under no circumstances should combustible material be located within the clearances specified in this manual Failure to provide proper clearance...

Page 18: ...efer to Installation 7 Refer to Installation 1 Open all manual gas valves 2 Replace fuse or turn on power supply 3 Turn up thermostat 4 Check limit switch with continuity tester If open replace limit...

Page 19: ...Do not ream 6 Refer to Operation 7 Check thermocouple connection and replace if defective 8 Eliminate drafts Refer to Installation 9 Inspect and correct all wiring 10 Inspect and correct ignition sys...

Page 20: ...or short such as staples piercing thermostat wiring and correct Replace gas valve Refer to Operation 1 Be sure fan switch heater terminals are connected per diagrams 1 Refer to Operation 2 Check motor...

Page 21: ...valve if not replace S8600 Igniter 1 Lengthen vertical run of flue pipe see venting 2 Burner orifice may be too large verify replace if req d 3 Increase air flow check fan size Check for proper voltag...

Page 22: ...ROPELLER UNIT HEATERS Figure 13 Propeller Parts 1 HEAT EXCHANGER 2 FLUE COLLECTOR 3 BURNER DRAWER Figure 15 Internal Furnace Components Figure 16 Burner Assy Parts 115 1 60 MOTOR FAN GUARD FAN BLADE H...

Page 23: ...400 units 6 dia flue outlet Increaser required To be supplied by manufacturer 23 REF NO DESCRIPTION 1 Blower Housing Assembly 2 Speed Nut 3 Motor 4 Washer Plain 5 Plate Adapter 6 Blower Wheel 7 Mounti...

Page 24: ...rews Item 12 Do not loose these parts Using caution the motor will disengage from the Mounting Adapter Plate along with the Relay Junction Box and Pressure Switch Mounting Brackets will also disengage...

Page 25: ...instructions or has been altered or modified in any way by any unauthorized person b to any expenses including labor or material incurred during removal or reinstallation of the Product c to any damag...

Page 26: ...NOTES 26...

Page 27: ...een installed Do you understand all the controls on this equipment If not contact your wholesaler or rep DO NOT START this equipment unless you fully understand the controls GAS EQUIPMENT START UP GEN...

Page 28: ......

Reviews: