background image

 

1.  Loose S8600 connections.

  2.  Improper gas pressure.

  3.  Is spark in pilot gas stream?
  4.  No pilot gas — do not use match to  
 

  test - presence of gas is easily 

 

  detected by the odor.

  1.  Loose S8600 connections.

  2.  Cracked or broken sensor ceramic.
  3.  Check sensor/spark lead for continuity.
  4.  Measure 24 volts from term. MV to  
  

term. 

MV/PV.

  1.  Vertical run of fl ue is too short.

  2.  Unit is overfi ring.

  3.  Air fl ow too low

 4. Defective 

switch.

  1.  Power venter wheel loose.
  2.  Power venter wheel dirty.
  3.  Power venter wheel rubbing housing.
  4.  Bearings are dry.

 1. Loose 

wiring. 

 

 

 

 

  2.  Defective motor overload protector or  
  

defective 

motor.

  3.  Defective power venter relay.

  1.  Fan relay heater element improperly  
  

wired. 

  2.  Defective venter relay switch.
  3.  Motor overload protector cycling on  
  

and 

off.

  4.  Motor not properly oiled.

  1.  Improperly wired venter relay.
  2.  Main burners not lighting while   
 

  thermostat calls for heat.

  3.  Defective venter relay.
 

  1.  Check all connections, term.     
 

  PV feeds 24V to pilot valve.

  2.  Check pressure — pressure that is  
 

  either too high or too low may cause   

  

problem.

  3.  Spark should arc from electrode.
  4.  Check pilot line for kinks. Ensure   
 

  there are no drafts.

  1.  Check connections-term. MV feeds  
  

main 

valve.

  2.  Replace pilot assembly.
  3.  Replace if needed.
  4.  If present, replace main valve; if not,  
 

  replace S8600 Igniter.

  1.  Lengthen vertical run of fl ue pipe   
  

(see 

venting).

  2.  Burner orifi ce may be too large:         
 

  verify/replace if req'd.

  3.  Increase air fl ow; check fan size.  
 

  Check for proper voltage.

 4. Replace.

  1.  Replace or tighten.
  2.  Clean power venter wheel.
  3.  Realign power venter wheel.
  4.  Oil bearings on power venter motor.  
 

  (Refer to label on motor).

  1.  Check and tighten all wiring connec- 
 

  tions per diagrams. Thermostat wires  

 

  tagged "W" and "G" must be     

 

  connected together (unless special  

 

  thermostats are used; if so, see  

 

  thermostat wiring diagram). See  

  

electrical 

connections.

 2. Replace 

motor.

  3.  Check for 24V across 1 and 3   
 

  terminals on fan relay. If 24V is  

 

  present, jumper terminals numbered     

 

  2 and 4. If motor runs, the relay  

 

  is defective and must be replaced.If  

 

  24V is not present, check wiring per  

  

diagrams.

  1.  Be sure venter relay heater terminals  
 

  are connected per diagrams.

  2.  Replace venter relay.
  3.  Check motor amps against motor  
 

  name plate rating, check voltage,  

 

  replace power venter motor if   

  

defective.

  4.  Refer to label on motor.

  1.  Check all wiring.
  2.  Refer to H & N symptoms.

  3.  Replace venter relay. 

Power Vented Propellers Troubleshooting Guide 

SYMPTOMS

POSSIBLE CAUSE(S)

CORRECTIVE ACTION

  W.  Spark present but pilot does     
   not 

light. 

  X.  Pilot lights — Main valve  

   

   

does not energize.

   

  Y.  Hi-Limit switch tripping.

  Z.  Noisy power venter.

  AA.  Power venter will not run.

  BB.  Power venter motor turns      
      

on and off while burner is      

      

operating.

  CC.  Power Ventor motor will not     
  

stop.

21

Summary of Contents for QVEF 100 M

Page 1: ...instructions to avoid exposure to fuel substances or substances from incomplete combustion which can cause death or serious illness The state of California has determined that these substances may ca...

Page 2: ...have any questions after reading this manual contact the manufacturer See Identification of Parts Section for unit components Front View Rear View Indicates an imminently hazardous situation which if...

Page 3: ...ied individual per instructions in this manual Also follow procedures listed on the Gas Equipment Start Up Sheet located in this manual 3 GENERAL SAFETY INFORMATION 1 foot 0 305 m 1 inch 25 4 mm 1 psi...

Page 4: ...9 0 186 0 249 0 249 Motor Type SP SP PSC PSC PSC PSC PSC PSC PSC PSC R P M 1 050 1 050 1 140 1 140 1 140 1 140 1 140 1 140 1 140 1 140 Amps 115V 2 6 4 2 4 7 5 8 5 8 5 8 5 8 9 4 11 6 11 6 DIMENSIONAL D...

Page 5: ...must not be installed in locations where air for combustion would contain chlorinated halogenated or acidic vapors If located in such an environment premature failure of the unit will occur Since the...

Page 6: ...e between walls and the vertical sides of the Unit Heater shall be no less than 18 inches 457mm A minimum clearance of 6 inches 152mm must be maintained between the top of the Unit Heater and the ceil...

Page 7: ...tiply the Cu Ft Hr Cubic Meters per Hour value by 0 633 then use the table 4 Refer to the metric conversion factors listed in General Safety section for more SI unit measurements conversions To avoid...

Page 8: ...ing should be sized in accordance with the latest edition of ANSI Standard Z223 1 National Fuel Gas Code in Canada according to CSA B149 See Tables 1 and 3 for correct gas supply piping size If gas pr...

Page 9: ...ersonal injury or death Standard units are shipped for use on 115 volt 60 hertz single phase electric power The motor nameplate and electrical rating on the transformer should be checked before energi...

Page 10: ...regarding these venting conditions CARBON MONOXIDE Your venting system must not be blocked by any snow snow drifts or any foreign matter Inspect your venting system to ensure adequate ventilation exi...

Page 11: ...llow this procedure 1 Hold power venter motor in position 2 Remove the three Phillips head screws from the motor adaptor plate 3 Remove the three screws which connect the power venter stack to the pow...

Page 12: ...12 Figure 10A VENTING continued Figure 10B...

Page 13: ...13 Figure 10C VENTING continued Figure 10D...

Page 14: ...isting of a power venter motor and blower pressure switch and sealed flue collector in place of the conventional draft diverter The addition of external draft hoods or power ventors is not permitted A...

Page 15: ...ywell Pilot Burner 13 High Limit This safety device is located on the rear header plate of the heat exchanger air inlet side 15 13 Figure 11 Burner Components Intermittent Pilot Ignition Also refer to...

Page 16: ...C 0 9 kPa Adjustment of the pressure regulator is not normally necessary since it is preset at the factory However field adjustment may be made as follows a Attach manometer at pressure tap plug adja...

Page 17: ...e minimum clearance requirements listed in this manual Under no circumstances should combustible material be located within the clearances specified in this manual Failure to provide proper clearance...

Page 18: ...efer to Installation 7 Refer to Installation 1 Open all manual gas valves 2 Replace fuse or turn on power supply 3 Turn up thermostat 4 Check limit switch with continuity tester If open replace limit...

Page 19: ...Do not ream 6 Refer to Operation 7 Check thermocouple connection and replace if defective 8 Eliminate drafts Refer to Installation 9 Inspect and correct all wiring 10 Inspect and correct ignition sys...

Page 20: ...or short such as staples piercing thermostat wiring and correct Replace gas valve Refer to Operation 1 Be sure fan switch heater terminals are connected per diagrams 1 Refer to Operation 2 Check motor...

Page 21: ...valve if not replace S8600 Igniter 1 Lengthen vertical run of flue pipe see venting 2 Burner orifice may be too large verify replace if req d 3 Increase air flow check fan size Check for proper voltag...

Page 22: ...ROPELLER UNIT HEATERS Figure 13 Propeller Parts 1 HEAT EXCHANGER 2 FLUE COLLECTOR 3 BURNER DRAWER Figure 15 Internal Furnace Components Figure 16 Burner Assy Parts 115 1 60 MOTOR FAN GUARD FAN BLADE H...

Page 23: ...400 units 6 dia flue outlet Increaser required To be supplied by manufacturer 23 REF NO DESCRIPTION 1 Blower Housing Assembly 2 Speed Nut 3 Motor 4 Washer Plain 5 Plate Adapter 6 Blower Wheel 7 Mounti...

Page 24: ...rews Item 12 Do not loose these parts Using caution the motor will disengage from the Mounting Adapter Plate along with the Relay Junction Box and Pressure Switch Mounting Brackets will also disengage...

Page 25: ...instructions or has been altered or modified in any way by any unauthorized person b to any expenses including labor or material incurred during removal or reinstallation of the Product c to any damag...

Page 26: ...NOTES 26...

Page 27: ...een installed Do you understand all the controls on this equipment If not contact your wholesaler or rep DO NOT START this equipment unless you fully understand the controls GAS EQUIPMENT START UP GEN...

Page 28: ......

Reviews: