background image

 

1.  Reset manifold pressure. Refer to  

  

“Operation”.

  2.  Replace regulator section of combin- 
 

  ation gas valve or complete valve.

  3.  Check with local gas supplier for  
 

  proper orifi ce size and replace. Refer  

  

to 

“Operation”.

 1. Close air shutter. Refer to “Operation”.
  2.  Check with local gas supplier for  
   

proper orifi ce size and replace. Refer  

   to 

“Operation”.

 

1.  Close air shutter.

 2. Reduce pilot gas. Refer to “Operation”.
 3. Replace 

orifi 

ce.

  4.  Reset manifold pressure. Refer to  
 

  “Operation”; Replace regulator section  

 

  of combination gas valve or complete  

 

  valve; or Check with local gas supplier  

 

  for proper orifi ce size and replace.  

  

Refer 

to 

“Operation”.

 

1.  Open air shutters. Refer to      

  

“Operation”.

  2.  Clean main burner ports.
  3.  Replace manifold assembly.
  4.  Clean fl ue collector.
  5.  Check for dust or lint at air mixer  
 

  opening and around the air shutter.

  6.  Clean combustion air inlet openings in  
 

  bottom panel, see “Installation”.

 

1.  Clean fl ue. Refer to “Installation”.

  2.  Clean combustion air inlet openings in  
 

  bottom panel, see “Installation”.

  3.  Clean heat exchanger.
  4.  Determine cause and repair 
  

accordingly.

 

1.  Inspect all gas piping and repair.

  2.  Clean heat exchanger/fl ue.
  3.  Eliminate drafts. Refer to “Installation”.
 4. See 

“Installation”.

  5.  Clean fl ue collector.

 

1.  Close air shutter. Refer to “Operation".

  2.  Clean main burner ports.
  3.  Reset manifold pressure. Refer to  
  

“Operation”.

  4.  Supply piping is inadequately sized.   
  

Refer 

to 

“Installation”.

  5.  Clean pilot orifi ce. Refer to      
  

“Operation”.

  6.  Eliminate drafts. Refer to “Installation”.
 7. Refer 

to 

“Installation”.

 

1.  Open all manual gas valves.

  2.  Replace fuse or turn on power supply.
  3.  Turn up thermostat.
  4.  Check limit switch with continuity  
 

  tester. If open, replace limit switch.

  5.  Check wiring per diagrams.

  6.  Replace gas valve.

18

 

SYMPTOMS

POSSIBLE CAUSE(S)

CORRECTIVE ACTION

 

Table 6 - Power Vented Propellers Troubleshooting Guide

  1.  Pressure regulator set too high.

 2. Defective 

Regulator.

  3.  Burner orifi ce too large.

  1.  Excessive primary air.
  2.  Burner orifi ce too small.

 

1.  Too much primary air.

 2. Noisy 

pilot.

  3.  Irregular orifi ce causing whistle or  
  

resonance.

  4.  Excessive gas input.

 

1.  Insuffi cient primary air.

  2.  Clogged main burner ports.
 3. Misaligned 

orifi 

ces.

  4.  Clogged fl ue collector.
  5.  Air shutter linted.

  6.  Insuffi cient combustion air.

 

1. Blocked 

venting.

  2.  Insuffi cient combustion air.

  3.  Blocked heat exchanger.
  4.  Air leak into combustion chamber or  
  

fl 

ue 

collector.

 

1.  Shut off gas supply immediately!

  2.  Blocked heat exchanger/venting.
  3.  Drafts around heater.
  4.  Negative pressure in building.
  5.  Blocked fl ue collector.

 

1.  Excessive primary air.

  2.  Main burner ports clogged near pilot.
  3.  Pressure regulator set too low.

  4.  Pilot decreases in size when main  
 

  burners come on.

  5.  Pilot fl ame too small.

  6.  Drafts around heater.
 7. Improper 

venting.

 

1.  Main gas off.

  2.  Lack of power at unit.
  3.  Thermostat not calling for heat.
  4.  Defective limit switch.

  5.  Improper thermostat or transformer 
 

  wiring at gas valve.

  6.  Defective gas valve.

 

A.  Flame lifting from burner  

   

   ports.

 

B.  Flame pops back.

 

C. Noisy fl ame.

 

D.  Yellow tip fl ame (some yellow   

   

tipping on propane gas is  

   

   permissible).

 

E. Floating fl ame.

 

F. Gas 

Odor.

 

G.  Delayed ignition.

 

H.  Failure to ignite.

Summary of Contents for QVEF 100 M

Page 1: ...instructions to avoid exposure to fuel substances or substances from incomplete combustion which can cause death or serious illness The state of California has determined that these substances may ca...

Page 2: ...have any questions after reading this manual contact the manufacturer See Identification of Parts Section for unit components Front View Rear View Indicates an imminently hazardous situation which if...

Page 3: ...ied individual per instructions in this manual Also follow procedures listed on the Gas Equipment Start Up Sheet located in this manual 3 GENERAL SAFETY INFORMATION 1 foot 0 305 m 1 inch 25 4 mm 1 psi...

Page 4: ...9 0 186 0 249 0 249 Motor Type SP SP PSC PSC PSC PSC PSC PSC PSC PSC R P M 1 050 1 050 1 140 1 140 1 140 1 140 1 140 1 140 1 140 1 140 Amps 115V 2 6 4 2 4 7 5 8 5 8 5 8 5 8 9 4 11 6 11 6 DIMENSIONAL D...

Page 5: ...must not be installed in locations where air for combustion would contain chlorinated halogenated or acidic vapors If located in such an environment premature failure of the unit will occur Since the...

Page 6: ...e between walls and the vertical sides of the Unit Heater shall be no less than 18 inches 457mm A minimum clearance of 6 inches 152mm must be maintained between the top of the Unit Heater and the ceil...

Page 7: ...tiply the Cu Ft Hr Cubic Meters per Hour value by 0 633 then use the table 4 Refer to the metric conversion factors listed in General Safety section for more SI unit measurements conversions To avoid...

Page 8: ...ing should be sized in accordance with the latest edition of ANSI Standard Z223 1 National Fuel Gas Code in Canada according to CSA B149 See Tables 1 and 3 for correct gas supply piping size If gas pr...

Page 9: ...ersonal injury or death Standard units are shipped for use on 115 volt 60 hertz single phase electric power The motor nameplate and electrical rating on the transformer should be checked before energi...

Page 10: ...regarding these venting conditions CARBON MONOXIDE Your venting system must not be blocked by any snow snow drifts or any foreign matter Inspect your venting system to ensure adequate ventilation exi...

Page 11: ...llow this procedure 1 Hold power venter motor in position 2 Remove the three Phillips head screws from the motor adaptor plate 3 Remove the three screws which connect the power venter stack to the pow...

Page 12: ...12 Figure 10A VENTING continued Figure 10B...

Page 13: ...13 Figure 10C VENTING continued Figure 10D...

Page 14: ...isting of a power venter motor and blower pressure switch and sealed flue collector in place of the conventional draft diverter The addition of external draft hoods or power ventors is not permitted A...

Page 15: ...ywell Pilot Burner 13 High Limit This safety device is located on the rear header plate of the heat exchanger air inlet side 15 13 Figure 11 Burner Components Intermittent Pilot Ignition Also refer to...

Page 16: ...C 0 9 kPa Adjustment of the pressure regulator is not normally necessary since it is preset at the factory However field adjustment may be made as follows a Attach manometer at pressure tap plug adja...

Page 17: ...e minimum clearance requirements listed in this manual Under no circumstances should combustible material be located within the clearances specified in this manual Failure to provide proper clearance...

Page 18: ...efer to Installation 7 Refer to Installation 1 Open all manual gas valves 2 Replace fuse or turn on power supply 3 Turn up thermostat 4 Check limit switch with continuity tester If open replace limit...

Page 19: ...Do not ream 6 Refer to Operation 7 Check thermocouple connection and replace if defective 8 Eliminate drafts Refer to Installation 9 Inspect and correct all wiring 10 Inspect and correct ignition sys...

Page 20: ...or short such as staples piercing thermostat wiring and correct Replace gas valve Refer to Operation 1 Be sure fan switch heater terminals are connected per diagrams 1 Refer to Operation 2 Check motor...

Page 21: ...valve if not replace S8600 Igniter 1 Lengthen vertical run of flue pipe see venting 2 Burner orifice may be too large verify replace if req d 3 Increase air flow check fan size Check for proper voltag...

Page 22: ...ROPELLER UNIT HEATERS Figure 13 Propeller Parts 1 HEAT EXCHANGER 2 FLUE COLLECTOR 3 BURNER DRAWER Figure 15 Internal Furnace Components Figure 16 Burner Assy Parts 115 1 60 MOTOR FAN GUARD FAN BLADE H...

Page 23: ...400 units 6 dia flue outlet Increaser required To be supplied by manufacturer 23 REF NO DESCRIPTION 1 Blower Housing Assembly 2 Speed Nut 3 Motor 4 Washer Plain 5 Plate Adapter 6 Blower Wheel 7 Mounti...

Page 24: ...rews Item 12 Do not loose these parts Using caution the motor will disengage from the Mounting Adapter Plate along with the Relay Junction Box and Pressure Switch Mounting Brackets will also disengage...

Page 25: ...instructions or has been altered or modified in any way by any unauthorized person b to any expenses including labor or material incurred during removal or reinstallation of the Product c to any damag...

Page 26: ...NOTES 26...

Page 27: ...een installed Do you understand all the controls on this equipment If not contact your wholesaler or rep DO NOT START this equipment unless you fully understand the controls GAS EQUIPMENT START UP GEN...

Page 28: ......

Reviews: