background image

24

TABLE 7 - MAIN BURNER ORIFICE SCHEDULE*

PRIMARY AIR SHUTTER ADJUSTMENT

After the unit has been operating for at least 15 minutes,
adjust the primary air  flow to the burners. Turn the
friction-locked, manually-rotated air shutters clockwise
to close, or counterclockwise to open.

For correct air adjustment, close the air shutter until yellow
tips in the flame appear. Then open the air shutter to the
point just beyond the position where yellow tipping
disappears. Refer to Figure 20.

NOTICE: There may be momentary and spasmodic
orange flashes in the flame. This is caused by the
burning of airborne dust particles, and not to be
confused with the yellow tipping, which is a stable or
permanent situation when there is insufficient
primary air.

Figure 20 - Main Burner Flames

GAS INPUT RATE

  Never overfire the duct furnace, as

this may cause unsatisfactory operation or shorten
the life of the heater.

Check the gas input rate as follows (Refer to general
safety section for metric conversions/SI units):
1.

Turn off all gas appliances that use gas through the
same meter as the heater.

2.

Turn gas on to the heater.

3.

Clock the time in seconds required to burn one cubic
foot of gas by checking the gas meter.

4.

Insert the time required to burn one cubic foot of
gas into the following formula and compute the
input rate.

3600 (Sec. Per Hr.) x Btu/Cu. Ft

                                                             = Input Rate
                       Time (Sec.)

For example, assume the Btu content of one cubic foot of
gas equalled 1000 and that it takes 18 seconds to burn
one cubic foot of gas.

3600 x 1000

   = 200,000

        18

NOTICE: If the computation exceeds or is less than
95 percent of the gas Btu/hr. input rating (see
“Specifications”), adjust the gas pressure.

Adjust the gas pressure as follows:
1.

NATURAL GAS:  Best results are obtained when the
heater is operating at its full input rating with the
manifold pressure of 3.5 inches W.C. (0.9 kPa).
Adjustment of the pressure regulator is not normally
necessary since it is preset at the factory.

However, field adjustment may be made as follows:

a.

Attach manometer at pressure tap plug
adjacent to control outlet.

b.

Remove regulator adjustment screw cap,
located on combination gas valve.

c.   With a small screwdriver, rotate the adjustment

screw counterclockwise to decrease or clock-
wise to increase pressure. Do not force beyond
stop limits.

d.   Replace regulator adjustment screw cap.

2.

PROPANE GAS:  An exact manifold pressure of
10.0 inches WC (2.5 kPa) must be maintained for
proper operation of the heater. If the unit is equipped
with a pressure regulator on the combination gas
valve, follow steps “a” through “d”  above. If the unit
is not so equipped, the propane gas supply system
pressure must be regulated to attain this manifold
operating pressure.

FT 

3

/HR

ORIFICE DRILL

FT 

3

/HR

ORIFICE DRILL

FT 

3

/HR

ORIFICE DRILL

*

INPUT

IN

1000

BTU

NO. OF

BURNER

ORIFICES

3.5" W.C.

(0.9 kPa)

1

0.0" W.C.

(2.5 kPa)

MANIFOLD

PRESSURE

PROPANE

TYPE OF GAS

NATURAL

2500 BTU/Ft

3

(93.1 MJ/m

3

)

1075 BTU/Ft

3

(40.1 MJ/m

3

)

HEATING

VALUE

100

125

150

175

200

225

250

300

350

400

4

5

6

7

8

9

10

12

14

16

96
42

120

42

140

42

163

42

186

42

210

42

233

42

280

42

326

42

372

42

40
54
50
54
60
54
70
54
80
54
90
54

100

54

120

54

140

54

160

54

FT 

3

/HR

ORIFICE DRILL

FT 

3

/HR

ORIFICE DRILL

FT 

3

/HR

ORIFICE DRILL

FT 

3

/HR

ORIFICE DRILL

FT 

3

/HR

ORIFICE DRILL

FT 

3

/HR

ORIFICE DRILL

FT 

3

/HR

ORIFICE DRILL

* This schedule is for units operating at normal altitudes of 2000 ft. (610m) or
less. SPECIAL ORIFICES ARE REQUIRED FOR INSTALLATIONS ABOVE
2000 FEET (610M).

When installed in Canada, any references to deration at altitudes in excess of
2000 feet (610m) are to be ignored.  At altitudes of 2000 to 4500 feet (610 to
1372m), the unit heaters must be orificed to 90% of the normal altitude rating,
and be so marked in accordance with the CSA certification.

LIFTING

(TOO MUCH AIR)

YELLOW TIPPING

(MARGINAL)

NORMAL

(HARD FLAME)

YELLOW FLAME

(TOO LITTLE AIR)

Summary of Contents for NATURAL INDOOR GAS-FIRED DUCT FURNACE

Page 1: ...th defects or other reproductive harm INSTALLER S RESPONSIBILITY Installer Please Note This equipment has been test fired and inspected It has been shipped free from defects from our factory However s...

Page 2: ...to in this manual are the ones that were applicable at the time the design was certified In addition the duct furnace may be installed on the downstream side of a cooling unit without need of a bypas...

Page 3: ...k tested by a suitably qualified individual per instructions in this manual Also follow procedures listed on the Gas Equipment Start up sheet located in this manual Use only the fuel for which the hea...

Page 4: ...RH 1 2 1 2 221 664 603 645 816 203 RH 100 225 28 7 8 26 1 2 28 1 8 34 7 8 8 RH 3 4 1 2 OR 3 4 243 733 673 714 886 203 RH 110 250 31 5 8 29 1 4 30 7 8 37 5 8 8 RH 3 4 1 2 OR 3 4 252 803 743 784 956 203...

Page 5: ...5 8 18 1 4 19 7 8 4 26 5 8 1 2 1 2 197 524 464 505 102 676 89 175 23 3 8 21 22 5 8 4 29 3 8 1 2 1 2 216 594 533 575 102 746 98 200 26 1 8 23 3 4 25 3 8 5 32 1 8 1 2 1 2 232 664 603 645 127 816 105 225...

Page 6: ...ater SIZE kW kW kW cu m s Deg C kPa cu m s Deg C Pascals 100 100 50 80 929 80 0 12 2469 30 0 90 29 3 14 6 23 4 0 438 44 0 03 1 165 17 0 22 125 125 62 5 100 1157 80 0 13 3086 30 0 80 36 6 18 3 29 3 0 5...

Page 7: ...allow a minimum of 21 inches 533mm at the bottom of the unit to facilitate servicing the burners and pilot or six inches 152mm if the unit has a side access burner drawer Provision should also be made...

Page 8: ...of mechanical vibration AIR FLOW The installation is to be adjusted to obtain an air throughput within the range specified on the appliance rating plate INSTALLATION COMBUSTION INLET AIR VENTILATION I...

Page 9: ...EOFSAFELYSUPPORTINGITS WEIGHT UNDER NO CIRCUMSTANCES MUST THE GAS LINES VENTING SYSTEM OR THE ELECTRICAL CONDUIT BE USED TO SUPPORT THE HEATER OR ANY OTHER OBJECTS I E LADDER PERSON LEAN AGAINST THE H...

Page 10: ...where drafts may affect the operation of the control 2 Hot areas Areas where the sun s rays radiation or warm air currents may affect control operation 3 Dead areas Areas where air cannot circulate fr...

Page 11: ...mon flue the cross sectional area of the common flue must be equal to the largest vent connection plus 50 of the area of each additional vent connection 3 Provide as long a vertical run of flue at the...

Page 12: ...ired from the venter outlet before installing an elbow in the vent system An elbow should never be attached directly to the venter Use single wall pipe constructed of 26 gauge galvanized steel or mate...

Page 13: ...sfor Structure Termination Locations 4 feet below Door window or any gravity air inlet 4 feet horizontally 1 foot above Forced air inlet within 10 ft 3 feet above Adjoining building or parapet 6 feet...

Page 14: ...14 Figure 12A Figure 12B...

Page 15: ...15 Figure 13A Figure 13B...

Page 16: ...Cap At Lowest Point Of Vent System Typ D4072 To Horizontal Flue Vent Termination Reducer Increaser Where Applicable Power Venter Power Venter Tee With Drip Leg Cleanout Cap At Lowest Point Of Vent Sy...

Page 17: ...10 6 9 06 8 07 7 36 6 80 6 23 5 80 5 52 4 96 4 53 4 11 3 82 1 1 4 1 380 1400 950 770 660 580 530 490 460 430 400 360 325 300 280 35 39 6 26 9 21 8 18 7 16 4 15 0 13 9 13 0 12 2 11 3 10 2 9 20 8 50 7...

Page 18: ...ng its full rated capacity as specified in Table 6 A field LP tank regulator must be used to limit the supply pressure to maximum of 14 W C 3 5 kPa All piping should be sized in accordance with the la...

Page 19: ...t Not standard equipment Also refer to Electrical Section Never use an open flame to detect gas leaks Explosive conditions may exist which would result in personal injury or death START UP Open the ma...

Page 20: ...ion Box 7 Pilot Tubing 9 High Limit Switch 10 Pilot Burner Assembly 11 Blocked Vent Spill Switch These safety devices are located on the rear header plate of heat exchanger inlet air side This safety...

Page 21: ...exceed 90 seconds from a cold start Make sure your fan is functioning properly 4 The wall thermostat is a temperature sensitive switch which turns the main gas valve ON or OFF to control the temperat...

Page 22: ...ressure to the main burners f Manual shutoff valve for service and long term shut down Separate from the automatic valve on some models 2 The high limit switch interrupts the flow of electric current...

Page 23: ...of the Heat Exchanger Air Inlet Side 14 Blocked Vent Spill Switch Located in the Upper Right Corner of the Unit Access Side Figure 19 Burner Components IntermIttent Pilot Ignition Also refer to Figure...

Page 24: ...3 5 inches W C 0 9 kPa Adjustment of the pressure regulator is not normally necessary since it is preset at the factory However field adjustment may be made as follows a Attach manometer at pressure t...

Page 25: ...e operation of the gas duct furnace The gas valve should close tightly completely extinguishing the flame on the main burners 11 Check the operation of the pilot safety device by closing the pilot lin...

Page 26: ...Figure 23 Burner Assembly Parts Figure 21 Duct Furnace Components Figure 22 Burners Controls FLAME CARRYOVER MAIN BURNER PACKAGED GAS VALVE BURNER DRAWER PILOT BURNER ASSEMBLY PARTS PILOT OBSERVATION...

Page 27: ...BRACKET JUNCTION BOX 9 SCREW S T 10 SCREW MACHINE L 3 4 11 NUT KEPS EXT LOCKWASHER 12 AIR PRESSURE SWITCH 13 DRILL SCREW 14 JUNCTION BOX ASSEMBLY REF NO DESCRIPTION 15 SNAP BUSHING 16 RELAY 17 STRAIG...

Page 28: ...from the Power Venter Blower Housing Item 8 6 Remove the Blower Wheel Item 9 from the motor shaft by removing the set screw Item 14 using a 1 8 Allen Wrench 7 Remove the three Motor Mounting Nuts Item...

Page 29: ...piping is inadequately sized Refer to Installation 5 Clean pilot orifice Refer to Oper ation 6 Eliminate drafts Refer to Installation 7 Refer to Installation 1 Open all manual gas valves 2 Replace fus...

Page 30: ...s valves 2 Increase size of pilot flame Refer to Operation 3 Purge air from gas supply 4 Follow lighting instruction label adjacent to gas valve 5 Remove pilot orifice Clean with compressed air or sol...

Page 31: ...2 Replace motor 3 Check for 24V across 1 and 3 terminals on fan relay If 24V is present jumper terminals numbered 2 and 4 If motor runs the relay is defective and must be replaced If 24V is not prese...

Page 32: ...tor voltage with fan running Should be 115 volts AC 3 Refer to Operation 1 Close thermostat contacts 2 Check for 24V across 24V terminals of S8600 3 Set gap to 0 1 4 Replace pilot assembly 1 Check all...

Page 33: ...ing removal or reinstallation of the defective Product or parts thereof c to any damage due to corrosion by chemicals including halogenated hydrocarbons precipitated in the air d to any workmanship of...

Page 34: ...34 NOTES...

Page 35: ...e controls GAS EQUIPMENT START UP GENERAL With power and gas off Make certain all packing has been removed Tighten all electrical terminals and connections Check damper linkages for tightness Check al...

Page 36: ......

Reviews: