3-1
122990-608
Uncrating/Installation Instructions
Installation Instructions
INSTALLATION INSTRUCTIONS
Before Operating
Equipment
1.
Review installation requirements:
a. Clearance — Clearance space shown on Equipment Draw-
ing is necessary for easy installation and proper operation and
maintenance of dryer.
b. Utility service lines:
• If unit is equipped with steam option, shutoff valve (not
by STERIS) should be installed on steam line near dryer
(see Figure 3-1). Shutoff valve must be capable of being
locked in OFF position.
• Disconnect switch (not by STERIS) should be installed in
electric supply line near dryer (see Figure 3-2). Discon-
nect switch must be capable of being locked in the OFF
position only.
• If this machine is installed next to other equipment,
disconnect switch should be located so that service can
be shut off to one piece of equipment at a time.
• Utility service requirements are shown on Equipment
Drawing. This machine requires either 208 volts, 60 Hz,
3-phase, 4-wire or 480 volts, 60 Hz, 3-phase, 3-wire.
Check Equipment Drawing or Identification Plate (lo-
cated inside dryer service compartment, see Figure 2-
2) for proper voltage.
2.
Place dryer, as shown on Equipment Drawing, in correct
relation to building supply line. If unit is not at installation site,
refer to Uncrating Instructions (Section 2) for proper moving
instructions.
NOTE: Floor under unit should be level. If necessary, add shims (not
by STERIS) to level unit.
1.
ELECTRIC — Connect building electrical supply to dryer.
Verify tight electrical connections.
2.
STEAM — Blow out the building steam supply line to remove
chips, scale, etc. Connect line to dryer. Steam line is required
for steam heater option only.
3.
VENTILATION — Connect dryer ventilation to a dedicated
building exhaust.
4.
If unit is equipped with steam option, open building supply
valve and check for leaks. Correct if necessary.
3
123456789012345678901234567890121234567
123456789012345678901234567890121234567
12345678901234567890123456789012123456
12345678901234567890123456789012123456
123456789012345678901234567890121234567
123456789012345678901234567890121234567
123456789012345678901234567890121234567
123456789012345678901234567890121234567
Connect Utilities
Figure 3-1. Shutoff Valves
Figure 3-2. Disconnect Switch