Stephill SSDP30 Handbook Download Page 19

 

 

Issue 4                                                                                                                      

17 

 

Press and hold either of the 

Menu Navigation 

 

buttons to cycle to the section which is 

required to be edited. 

 

Press the 

Menu Navigation 

 

buttons to cycle to the parameter within the section chosen to 

be edited. 

 

Press the 

Tick 

 button to edit the parameter. The parameter begins to flash to indicate that the 

parameter is being edited. 

 

Press the 

Previous ─ & Next + 

buttons to adjust the parameter to the required value. 

 

Press the 

Tick 

 button to stop editing the parameter. The parameter ceases flashing to indicate 

that it the parameter is no longer being edited. 

 
9.1.4 EXITING THE FRONT PANEL CONFIGURATION EDITOR 

 

 

Press and hold the 

Stop/Reset Mode 

 

button to exit the editor without saving changes. 

 

Press and hold the 

Tick 

button to exit the editor and save the changes. 

 
10 Fault finding 6110 
Sympton 

Possible Remedy 

Unit is inoperative 
Read/Write configuration 
does not operate

 

Check the battery and wiring to the unit. Check the DC supply. 
Check the DC fuse.

 

Unit shuts down

 

Check DC supply voltage is not above 35 Volts or below 9 Volts 
Check the operating temperature is not above 70°C. Check the DC fuse.

 

Fail to Start is activated 
after pre-set number of 
attempts to start

 

Check wiring of fuel solenoid. Check fuel. Check battery supply. 
Check battery supply is present on the Fuel output of the module. 
Check the speed-

sensing signal is present on the module’s inputs. 

Refer to engine manual.

 

Continuous starting of 
generator when in the  

Auto Mode 

 

Check that there is no signal present on the “Remote Start” input. 
Check configured polarity is correct. 
Check the mains supply is available and within configured limits

 

Generator fails to start on 
receipt of Remote Start 
signal. 

 

Check Start Delay timer has timed out. 
Check signal is on “Remote Start” input.  
Confirm correct 

configuration of input is configured to be used as “Remote Start”. 

Check that the oil pressure switch or sensor is indicating low oil pressure to the 
controller.  
Depending upon configuration, the set does not start if oil pressure is not low.

 

Pre-heat inoperative

 

Check wiring to engine heater plugs.  
Check battery supply.  
Check battery supply is present on the Pre-heat output of module. Check pre-
heat configuration is correct.

 

Starter motor inoperative

 

Check wiring to starter solenoid. Check battery supply.  
Check battery supply is present on the Starter output of module. Ensure oil 
pressure switch or sensor is indicating the “low oil pressure” state to the 
controller.

 

 
10.1 ALARMS 

Low oil Pressure fault 
operates after engine has fired

 

Check engine oil pressure. Check oil pressure switch/sensor and wiring.  
Check switch is Normally Closed at rest and opens when running.

 

High engine temperature fault 
operates after engine has fired.

 

Check engine temperature. Check switch/sensor and wiring.  
Check switch is Normally Open and closes to fault.

 

Shutdown fault operates

 

Check relevant switch and wiring of fault indicated on LCD display.

 

Electrical Trip fault operates

 

Check relevant switch and wiring of fault indicated on LCD display.

 

Warning fault operates

 

Check relevant switch and wiring of fault indicated on LCD display. 

Incorrect reading on Engine 
gauges

 

Check engine is operating correctly. Check sensor and wiring paying 
particular attention to the wiring to terminal 10 (refer to appendix).

 

Fail to stop alarm when engine 
is at rest 

Check that Oil sender wiring is correct and correctly earthed. 

Summary of Contents for SSDP30

Page 1: ...stephill generators co uk Web Web www stephill generators co uk Northants NN8 6AG DO NOT OPERATE THE GENERATOR BEFORE READING THIS MANUAL AND ENGINE MANUFACTURER S OWNER S MANUAL AND WARNINGS THIS ST...

Page 2: ...PERATION 10 7 1 Starting the engine 10 7 2 Stopping the engine 10 7 3 Stop Reset mode 10 11 7 4 Manual mode 11 7 4 1 Starting sequence 11 7 4 2 Stopping sequence 11 7 5 Automatic mode 11 7 5 1 Waiting...

Page 3: ...run are based on these figures 2 GENERAL SAFETY 2 1 Warning signs Warnings shown on the machine should be observed at all times The warning signs should be checked for legibility and any that have be...

Page 4: ...orms of contact are irritant and therefore should also be avoided If skin contact is made wash with soap and water 4 3 Bunded tank This generator is fitted with a secondary containment system Bunded t...

Page 5: ...generator unless all guards are in place There is a risk of burns or serious mechanical injury 5 OPERATING INSTRUCTIONS 5 1 Pre start checks Before starting the generator please read the engine owners...

Page 6: ...e possibility of an automatic or manual reset selectable by a microswitch and to protect the settings by its sealable transparent front cover 1 Current tripping setting potentiometer 2 Tripping time s...

Page 7: ...es and hoses should be checked to ensure that they are un perished following extended periods of storage The generator should be stored in a clean dry area ideally having a reasonable constant ambient...

Page 8: ...e responds to the Start button to start the generator and run it off load Auto Mode This button places the module into its Auto Mode This mode allows the module to control the function of the generato...

Page 9: ...strumentation page the instruments displayed are automatically subject to the setting of the LCD Scroll Timer The screenshot below shows the factory settings for the timers taken from the DSE Configur...

Page 10: ...Alarm on the module Press and hold either of the Menu Navigation buttons to scroll to the alarms page to investigate Press the Stop Reset Mode button to clear the alarm if the alarm does not clear the...

Page 11: ...the Alarm Page The LCD displays multiple alarms such as Coolant Temperature High Emergency Stop and Low Coolant Warning These automatically scroll in the order that they occurred In the event of an a...

Page 12: ...Reset Mode is activated by pressing the Stop Reset Mode button In Stop Reset Mode the module removes the generator from load if necessary before stopping the engine if it is already running If the en...

Page 13: ...either The Stop Reset Mode button is pressed The delayed load outputs are de activated immediately and the set immediately stops The Auto Mode button is pressed The set observes all Auto Mode start re...

Page 14: ...The Cooling Down timer allows the set to run off load and cool sufficiently before being stopped This is particularly important where turbo chargers are fitted to the engine After the Cooling Down tim...

Page 15: ...the expansion module has failed or communications to the expansion module has been lost Fail To Stop The module has detected a condition that indicates that the engine is running when it has been ins...

Page 16: ...load from the generator Once this has occurred the module shuts the generator set down immediately to prevent further damage The alarm must be accepted and cleared and the fault removed to reset the m...

Page 17: ...below the under speed trip alarm setting 8 5 HIGH CURRENT SHUTDOWN The overcurrent alarm combines a simple warning trip level with a fully functioning IDMT curve for thermal protection Alarm is set at...

Page 18: ...ervice engineer after performing the required maintenance The method of reset is by breaking the connection between wires 43 1 which are located at the side of the MCCB Panel must be powered up for re...

Page 19: ...ilable and within configured limits Generator fails to start on receipt of Remote Start signal Check Start Delay timer has timed out Check signal is on Remote Start input Confirm correct configuration...

Page 20: ...n the DC connector plug and socket Check continuity on VE and VE wires to battery Battery not Note you may experience low charge if fan belt is loose charging Check for loose wires on the DC connector...

Page 21: ...59 018 0059 018 0059 Reactive silencer MK1 1 st Silencer 016 0133 016 0133 016 0175 016 0175 016 0175 Absorption Silencer MK1 With tail pipe 016 0135 016 0135 016 0176 016 0176 016 0176 U Pipe with ab...

Page 22: ...nning Ensure battery isolator switch is in the off position when working on generator this will prevent generator from starting 13 1 Engine service Service the engine strictly in accordance with the i...

Page 23: ...use of parts not supplied by STEPHILL GENERATORS LTD Lack of or incorrect maintenance Fair wear and tear misuse negligence accidental damage improper storage incorrect starting warm up run in or shut...

Page 24: ...wn 4mm Black 4mm Grey 6mm Grey 6mm Brown 6mm Black 6mm Grey 6mm Black 6mm Brown 6mm Blue 6mm Green Yellow Hard wire terminals 50A MCB W 27 V 26 U 25 N 28 1 5mm Grey 1 5mm Black 1 5mm Brown 37 34 33 37...

Page 25: ...L1 N E L2 L3 32A MCB 4mm Blue 1 5mm Blue 4mm Brown 4mm Black 1 5mm Grey 4mm Grey 4mm Black 4mm Brown 10mm Grey 10mm Blue 10mm Black 10mm Brown 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 4 3 2 1 28...

Page 26: ...53 38 REMOTE START VE 1 BATTERY VE 2 5mm 1 COOLANT SWITCH 51 1 41 9 41 1 41 B D C 2 BATTERY VE CLOSE TO START REMOTE START VE 1 HARD WIRE DOOR 42 1 VE 2 FUEL A 4 START B 5 EMERGENCY STOP 3 C 7 D 8 CHA...

Page 27: ...3 10 11 27 6 25 22 21 30 17 7 39 40 42 36 41 5 43 14 15 R Golding A 30 06 14 New drawing Date Revision Issue THIRD ANGLE PROJECTION Description Fax Phone Drawing Number Drawn SSDP33 70 Mk2 Exploded vi...

Page 28: ...SSD30 Silencer bracket 21 016 0121 SSD30 Silencer bracket 22 016 0272 SSD30 MK2 Air outlet deflector plate 22 016 0272 SSD30 MK2 Air outlet deflector plate 23 016 0119 SSD30 Radiator plate 23 016 0119...

Reviews: