![Stephill SSDP30 Handbook Download Page 19](http://html1.mh-extra.com/html/stephill/ssdp30/ssdp30_handbook_1372631019.webp)
Issue 4
17
Press and hold either of the
Menu Navigation
buttons to cycle to the section which is
required to be edited.
Press the
Menu Navigation
buttons to cycle to the parameter within the section chosen to
be edited.
Press the
Tick
button to edit the parameter. The parameter begins to flash to indicate that the
parameter is being edited.
Press the
Previous ─ & Next +
buttons to adjust the parameter to the required value.
Press the
Tick
button to stop editing the parameter. The parameter ceases flashing to indicate
that it the parameter is no longer being edited.
9.1.4 EXITING THE FRONT PANEL CONFIGURATION EDITOR
Press and hold the
Stop/Reset Mode
button to exit the editor without saving changes.
Press and hold the
Tick
button to exit the editor and save the changes.
10 Fault finding 6110
Sympton
Possible Remedy
Unit is inoperative
Read/Write configuration
does not operate
Check the battery and wiring to the unit. Check the DC supply.
Check the DC fuse.
Unit shuts down
Check DC supply voltage is not above 35 Volts or below 9 Volts
Check the operating temperature is not above 70°C. Check the DC fuse.
Fail to Start is activated
after pre-set number of
attempts to start
Check wiring of fuel solenoid. Check fuel. Check battery supply.
Check battery supply is present on the Fuel output of the module.
Check the speed-
sensing signal is present on the module’s inputs.
Refer to engine manual.
Continuous starting of
generator when in the
Auto Mode
Check that there is no signal present on the “Remote Start” input.
Check configured polarity is correct.
Check the mains supply is available and within configured limits
Generator fails to start on
receipt of Remote Start
signal.
Check Start Delay timer has timed out.
Check signal is on “Remote Start” input.
Confirm correct
configuration of input is configured to be used as “Remote Start”.
Check that the oil pressure switch or sensor is indicating low oil pressure to the
controller.
Depending upon configuration, the set does not start if oil pressure is not low.
Pre-heat inoperative
Check wiring to engine heater plugs.
Check battery supply.
Check battery supply is present on the Pre-heat output of module. Check pre-
heat configuration is correct.
Starter motor inoperative
Check wiring to starter solenoid. Check battery supply.
Check battery supply is present on the Starter output of module. Ensure oil
pressure switch or sensor is indicating the “low oil pressure” state to the
controller.
10.1 ALARMS
Low oil Pressure fault
operates after engine has fired
Check engine oil pressure. Check oil pressure switch/sensor and wiring.
Check switch is Normally Closed at rest and opens when running.
High engine temperature fault
operates after engine has fired.
Check engine temperature. Check switch/sensor and wiring.
Check switch is Normally Open and closes to fault.
Shutdown fault operates
Check relevant switch and wiring of fault indicated on LCD display.
Electrical Trip fault operates
Check relevant switch and wiring of fault indicated on LCD display.
Warning fault operates
Check relevant switch and wiring of fault indicated on LCD display.
Incorrect reading on Engine
gauges
Check engine is operating correctly. Check sensor and wiring paying
particular attention to the wiring to terminal 10 (refer to appendix).
Fail to stop alarm when engine
is at rest
Check that Oil sender wiring is correct and correctly earthed.