Issue 4
14
Example:
Electrical trips are latching alarms and to remove the fault, press the
Stop/Reset Mode
button on the
module.
Fault
Description
Analogue Input A to D
The module detects that an input configured to create a fault
condition has become active and the appropriate LCD message is
displayed.
Digital Inputs A to F
The module detects that a digital input which has been user configured to
create a fault condition has become active and the appropriate LCD message is
displayed.
Expansion Unit Failure
The module detects the DSE Net link to the expansion module has failed or
communications to the expansion module has been lost.
Low Fuel Level
The level detected by the fuel level sensor is below the low fuel
level pre-set pre-alarm setting.
8.4 SHUTDOWN ALARMS
Shutdown alarms are latching and immediately stop the Generator. On initiation of the shutdown condition the
module de-energises all the Delayed Load Output and the Close Gen Output outputs to remove the load from
the generator. Once this has occurred, the module shuts the generator set down immediately to prevent
further damage. The alarm must be accepted and cleared, and the fault removed to reset the module.
Example:
Shutdowns are latching alarms and to remove the fault, press the
Stop/Reset Mode
button on the module.
Fault
Description
Analogue Input A to D
The module detects that an input configured to create a fault condition has
become active and the appropriate LCD message is displayed.
Charge Alternator Failure
The auxiliary charge alternator voltage is low as measured from the W/L
terminal.
Coolant Temperature
Sensor Fault
The module detects that the circuit to the coolant temperature sensor has been
broken.
Emergency Stop
The emergency stop button is pressed. This failsafe (normally closed to
emergency stop) input and immediately stops the set when the signal is
removed.
Delayed Over Current
The measured current has risen above the configured trip level for a configured
duration.
Digital Inputs A to F
The module detects that a digital input which has been user configured to
create a fault condition has become active and the appropriate LCD message is
displayed.