Stephill SSDP30 Handbook Download Page 18

 

 

Issue 4                                                                                                                      

16 

These settings provide for normal running of the generator up to 100% full load. If full load is surpassed, the 

Immediate Warning 

alarm is triggered, the set continues to run. 

The effect of an overload on the generator is that the alternator windings begin to overheat; the aim of the 

IDMT alarm 

is to prevent the windings being overload (heated) too much. The amount of time that the set can 

be safely overloaded is governed by how high the overload condition is. 
 
With typical settings as above, this allows for overload of the set to the limits of the 

Typical Brushless 

Alternator  

whereby 110% overload is permitted for 1 hour. 

 

8.6 MAINTENANCE ALARM 

Maintenance alarms are configured as follows: 

 

Maintenance alarm 1: Service required 500 Hour intervals 

 

Maintenance alarm 2: Not used 

 

Maintenance alarm 3: Not used 

 
When activated, the maintenance alarm is a 

Warning 

and set continues to run. 

Resetting the maintenance alarm is actioned by the site service engineer after performing the required 
maintenance. The method of reset is by breaking the connection between wires 43 & 1 which are located at 
the side of the MCCB. Panel must be powered up for re-set to operate. 
 

9.0 FRONT PANEL CONFIGURATION EDTIOR 
9.1.1 ACCESSING THE FRONT PANEL CONFIGURATION EDITOR 

 

Ensure the engine is at rest and the module by pressing the 

Stop/Reset Mode 

 

button. 

 

Press the 

Stop/Reset Mode 

and 

Tick 

buttons together to enter the front panel configuration 

editor. 

 
9.1.2 ENTERING PIN 

 

 

 

 

Pin number 1234. 

 

If a module security PIN has been set, the PIN request is then shown. 

 

Press the 

Tick 

 

button, the first ‘#’ changes to ‘0’. Press the 

Previous - & Next + 

buttons to adjust 

it to the correct value. 

 

Press the 

Next + 

button when the first digit is correctly entered. The digit you have just entered now 

shows as ‘#’ for security. 

 

Press the 

Scroll Down 

 

button to move back to adjust one of the previous digits. 

 

After editing the final PIN digit, press the 

Tick 

 button. The PIN is then checked for validity. If the 

number is not correct, the PIN must be re-entered. 

 

If the PIN has been successfully entered the editor is displayed. 

 

9.1.3 EDITING A PARAMETER 

 

 

Summary of Contents for SSDP30

Page 1: ...stephill generators co uk Web Web www stephill generators co uk Northants NN8 6AG DO NOT OPERATE THE GENERATOR BEFORE READING THIS MANUAL AND ENGINE MANUFACTURER S OWNER S MANUAL AND WARNINGS THIS ST...

Page 2: ...PERATION 10 7 1 Starting the engine 10 7 2 Stopping the engine 10 7 3 Stop Reset mode 10 11 7 4 Manual mode 11 7 4 1 Starting sequence 11 7 4 2 Stopping sequence 11 7 5 Automatic mode 11 7 5 1 Waiting...

Page 3: ...run are based on these figures 2 GENERAL SAFETY 2 1 Warning signs Warnings shown on the machine should be observed at all times The warning signs should be checked for legibility and any that have be...

Page 4: ...orms of contact are irritant and therefore should also be avoided If skin contact is made wash with soap and water 4 3 Bunded tank This generator is fitted with a secondary containment system Bunded t...

Page 5: ...generator unless all guards are in place There is a risk of burns or serious mechanical injury 5 OPERATING INSTRUCTIONS 5 1 Pre start checks Before starting the generator please read the engine owners...

Page 6: ...e possibility of an automatic or manual reset selectable by a microswitch and to protect the settings by its sealable transparent front cover 1 Current tripping setting potentiometer 2 Tripping time s...

Page 7: ...es and hoses should be checked to ensure that they are un perished following extended periods of storage The generator should be stored in a clean dry area ideally having a reasonable constant ambient...

Page 8: ...e responds to the Start button to start the generator and run it off load Auto Mode This button places the module into its Auto Mode This mode allows the module to control the function of the generato...

Page 9: ...strumentation page the instruments displayed are automatically subject to the setting of the LCD Scroll Timer The screenshot below shows the factory settings for the timers taken from the DSE Configur...

Page 10: ...Alarm on the module Press and hold either of the Menu Navigation buttons to scroll to the alarms page to investigate Press the Stop Reset Mode button to clear the alarm if the alarm does not clear the...

Page 11: ...the Alarm Page The LCD displays multiple alarms such as Coolant Temperature High Emergency Stop and Low Coolant Warning These automatically scroll in the order that they occurred In the event of an a...

Page 12: ...Reset Mode is activated by pressing the Stop Reset Mode button In Stop Reset Mode the module removes the generator from load if necessary before stopping the engine if it is already running If the en...

Page 13: ...either The Stop Reset Mode button is pressed The delayed load outputs are de activated immediately and the set immediately stops The Auto Mode button is pressed The set observes all Auto Mode start re...

Page 14: ...The Cooling Down timer allows the set to run off load and cool sufficiently before being stopped This is particularly important where turbo chargers are fitted to the engine After the Cooling Down tim...

Page 15: ...the expansion module has failed or communications to the expansion module has been lost Fail To Stop The module has detected a condition that indicates that the engine is running when it has been ins...

Page 16: ...load from the generator Once this has occurred the module shuts the generator set down immediately to prevent further damage The alarm must be accepted and cleared and the fault removed to reset the m...

Page 17: ...below the under speed trip alarm setting 8 5 HIGH CURRENT SHUTDOWN The overcurrent alarm combines a simple warning trip level with a fully functioning IDMT curve for thermal protection Alarm is set at...

Page 18: ...ervice engineer after performing the required maintenance The method of reset is by breaking the connection between wires 43 1 which are located at the side of the MCCB Panel must be powered up for re...

Page 19: ...ilable and within configured limits Generator fails to start on receipt of Remote Start signal Check Start Delay timer has timed out Check signal is on Remote Start input Confirm correct configuration...

Page 20: ...n the DC connector plug and socket Check continuity on VE and VE wires to battery Battery not Note you may experience low charge if fan belt is loose charging Check for loose wires on the DC connector...

Page 21: ...59 018 0059 018 0059 Reactive silencer MK1 1 st Silencer 016 0133 016 0133 016 0175 016 0175 016 0175 Absorption Silencer MK1 With tail pipe 016 0135 016 0135 016 0176 016 0176 016 0176 U Pipe with ab...

Page 22: ...nning Ensure battery isolator switch is in the off position when working on generator this will prevent generator from starting 13 1 Engine service Service the engine strictly in accordance with the i...

Page 23: ...use of parts not supplied by STEPHILL GENERATORS LTD Lack of or incorrect maintenance Fair wear and tear misuse negligence accidental damage improper storage incorrect starting warm up run in or shut...

Page 24: ...wn 4mm Black 4mm Grey 6mm Grey 6mm Brown 6mm Black 6mm Grey 6mm Black 6mm Brown 6mm Blue 6mm Green Yellow Hard wire terminals 50A MCB W 27 V 26 U 25 N 28 1 5mm Grey 1 5mm Black 1 5mm Brown 37 34 33 37...

Page 25: ...L1 N E L2 L3 32A MCB 4mm Blue 1 5mm Blue 4mm Brown 4mm Black 1 5mm Grey 4mm Grey 4mm Black 4mm Brown 10mm Grey 10mm Blue 10mm Black 10mm Brown 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 4 3 2 1 28...

Page 26: ...53 38 REMOTE START VE 1 BATTERY VE 2 5mm 1 COOLANT SWITCH 51 1 41 9 41 1 41 B D C 2 BATTERY VE CLOSE TO START REMOTE START VE 1 HARD WIRE DOOR 42 1 VE 2 FUEL A 4 START B 5 EMERGENCY STOP 3 C 7 D 8 CHA...

Page 27: ...3 10 11 27 6 25 22 21 30 17 7 39 40 42 36 41 5 43 14 15 R Golding A 30 06 14 New drawing Date Revision Issue THIRD ANGLE PROJECTION Description Fax Phone Drawing Number Drawn SSDP33 70 Mk2 Exploded vi...

Page 28: ...SSD30 Silencer bracket 21 016 0121 SSD30 Silencer bracket 22 016 0272 SSD30 MK2 Air outlet deflector plate 22 016 0272 SSD30 MK2 Air outlet deflector plate 23 016 0119 SSD30 Radiator plate 23 016 0119...

Reviews: