Instruction Manual of
-S3 Inverter for Elevator
Refer to Figure 6.2 Adjustable Sequence.
Note 9: brake delay B16
B16 needs configuration only when the Inverter is to directly control the brake contactor.
B16 defines the delay from zero speed to the sending of brake contactor cutoff command
to release the brake when stop. The zero speed takes B04 setting as its threshold, i.e., the
speed shall be regarded as zero when it goes below that set by B04.
Refer to Figure 6.2 Adjustable Sequence.
IMPORTANT
Note that the above delays shall meet the following requirement: B08 (contactor opening
delay) > B03 (zero speed time) > B16 (brake delay). Or elevator slipping may occur or
damages may even be caused to the Inverter.
Function Parameter List
Figure 6.2 Adjustable sequence
6-