18
Pro700
Installation and Programming Manual
A100K10226 v.4.1 Jul. 2006
External loudspeaker
;
Set jumpers to pos
1 – 2
,
EXT LS.
;
Connect a 20 ohm loudspeaker to terminals
1
and
8
.
-
Remote Output function can then not be used.
Remote Output
Door opening
(activated by "5" from a priority station during
conversation).
These stations have a 30mA transistor output.
;
Set jumpers to pos
2 – 3, REM CON.
-
External loudspeaker can then not be connected.
;
Connect 12 VDC relay to the screw terminal
3
and
8.
;
Connect the door lock magnet via the relay contact.
-
External power for the door lock magnet is needed.
5.3 AA703, AA704, AA705, BC735
The 3-pair installation cable is connected to terminals 1/2, 3/4 and 7/8
on screw terminal block
TB1
on the printed circuit board NFE1830.
Extra equipment is connected to terminals 5/6 and 9/10 on terminal
block
TB1
and to
TB2
and
TB3
on the same printed circuit board.
The stations have to be opened to get access to the terminal blocks.
External loudspeaker
;
Connect a 20 – 50 ohm loudspeaker to terminals
TB1 - 5
and
6.
-
The loudspeaker can be connected independent of jumper
settings and other equipment.
Remote Output
The built-in relay can carry max. 5 A.
Door opening:
(activated by "5" from a priority station during
conversation).
;
Set jumper
1
to
pos
2 - 3
.
;
Connect the door magnet in series with its power supply to
terminals
TB1 - 9
and
10
.
Optional Warning:
(active when station is called, cancelled by "2").
;
Set jumper
1 to
pos
1 - 2
.
;
Connect the warning device in series with its power supply to
terminals
TB1 - 9
and
10.
Remote Input, Emergency Call
External switch in parallel with the keyboard switch "9".
;
Connect a closing contact switch to
TB2
terminals
1
and
2
.
Local Reset
Reset a CAS call-in station by pushing an external switch “X”.
;
Connect a closing contact switch to
TB2
terminals
3
and
4
.
Local Output
A lamp will light when a CAS call-in or doorbell call is made.
;
Connect a 5W lamp to
TB2
terminals
5
and
6
.
-
The lamp voltage must correspond to the available power!
EXT LS
REM CON
30 m A
EXT LS
REM CON
1
2
3
1
2
3
1
2
3
4
5
6
7
8
EX
T
+ 24 V
1
2
3
4
5
6
7
8
9
10
5A
TB1
OPT WARN
OPT WARN
REM OUT
REM OUT
1
2
3
1
2
3
1
2
3
4
5
6
7
8
9
10
TB1
24V
+
-
Signal
Signal
Power +
Power -
Program
Program
1
2
3
4
5
6
TB2
12-24V
5W
ALARM
RESET CAS
“X”
“9”