Mount Pump
Select a dry location (to avoid water
intrusion and pump damage) above the
solution tank. Best recommended location
is above the solution tank in a vertical
position with the pump head pointed
downward and the spill recovery (see
next page) in place to reduce the risk and
severity of damage.
To prevent pump damage in the event of
a pump tube leak, never mount the pump
vertically with the pump head up.
To avoid chemical damage from fumes,
do not mount pump directly over an open
solution tank. Keep tank covered.
Avoid flooded suction or pump mounted
lower than the solution container.
Draw solution from the top of the tank.
If pump is installed with a flooded
suction, a shut-off valve or other device
must be provided to stop flow to pump
during service.
• Use the mounting bracket as a template
to drill pilot holes in mounting location.
• Secure bracket with fasteners or wall
anchors. Slide pump into bracket.
Provide 8" clearance to allow pump
orientation to be reversed during tube
replacement. Do not allow water intrusion
into the motor or corrosion and damage
will occur.
To prevent motor damage, verify with a
volt meter that the receptacle voltage
corresponds with the pump voltage.
• Plug cord into receptacle and turn the
motor power switch on. If the pump is
adjustable, turn the dial ring to 10.
• Activate the pump by the pump control
(flow switch, pressure switch, etc.) and
verify rotation of the roller assembly
within the clear pump head. Turn pump
switch off.
Installation
continued
– mount pump
Wall
bracket
Rain roof
(optional)
slips onto
wall bracket
Pump
head