15
USA and Canada 800.683.2378, International 904.641.1666
Econ T
INSTALLATION
continued
MOUNT PUMP
Select a dry location (to avoid water intrusion and pump damage) above the
solution tank.
To prevent pump damage in the event of a pump tube leak, never mount the
pump vertically with the pump head up.
DO NOT mount pump directly over an open solution tank. Keep tank covered.
Avoid flooded suction or pump mounted lower than the solution container. Draw
solution from the top of the tank. Pump can run dry without damage. If pump is
installed with a flooded suction, a shut-off valve or other device must be provided
to stop flow to pump during service.
To prevent motor damage, verify with a volt meter that the receptacle voltage
corresponds with the pump voltage.
1.
Plug the power supply into the receptacle.
2.
Press the
MANUAL
button to set the pump to ON and verify the rotation of the roller
assembly. Disconnect the power.