MOUNT PUMP
Select a dry location (to avoid water intrusion and pump damage) above the
solution tank. Best recommended location is above the solution tank in a vertical
position with the pump head pointed downward and the spill recovery
(see page
20)
in place to reduce the risk and severity of damage.
To prevent pump damage in the event of a pump tube leak, never mount the pump
vertically with the pump head up.
To avoid chemical damage from fumes, DO NOT mount pump directly over an open
solution tank. Keep tank covered.
Avoid flooded suction or pump mounted lower than the solution container. Draw
solution from the top of the tank. Pump can run dry without damage. If pump is
installed with a flooded suction, a shut-off valve or other device must be provided
to stop flow to pump during service.
1.
Use the mounting bracket as a template
to drill pilot holes in mounting location.
2.
Secure bracket with fasteners or wall
anchors. Slide pump into bracket.
Provide 8" clearance to allow pump
orientation to be reversed during tube
replacement. DO NOT allow water
intrusion into the motor or corrosion
and damage will occur.
To prevent motor damage, verify
with a volt meter that the receptacle
voltage corresponds with the
pump voltage.
3.
Plug cord into receptacle and turn the
motor power switch on. If the pump is
adjustable, turn the dial ring to 10.
4.
Activate the pump by the pump control (flow switch, pressure switch, etc.) and verify
rotation of the roller assembly within the clear pump head. Turn pump switch off.
USA and Canada 800.683.2378, International 904.641.1666
17
INSTALLATION
continued
Rain Roof
(optional)
slips into
wall bracket.
Wall Bracket
Pump Head