background image

Comfort Control Relay Panel (CCRP)

Page 5

N

OTES

 C

ONTINUED

...

NOTE 4:  Overrides (Optional, Power Company
Permitting) / Multiple Control Strategies

With the addition of the 3-zone override module to the
CCRP, peak override of 6 of the 9 circuits is possible.  If
enabled, relays 1, 2, 3, 7, 8, or 9 can be used in 60-minute
intervals during a peak control period, if desired.  Devices
controlled by relays 4, 5, and 6 can never be overridden.
Installation instructions for this feature are provided with
the override module. (Order item #1302060.)

For power companies desiring to control loads separately using multiple signals, the override ports in the termi-
nal block can also be used to recognize these signals and trigger the peak control.

OV1 = allows relay 1 circuit to be overridden or controlled on a separate rate/control strategy
OV2 = allows relay 2 circuit to be overridden or controlled on a separate rate/control strategy
OV3 = allows relay 3 circuit to be overridden or controlled on a separate rate/control strategy
OV4 = allows relay circuits 7, 8, and 9 to be overridden (cannot override these circuits separately) or

controlled on a separate rate/control strategy

* The 4-pole CCRP is configured to utilize relays 1, 2, 3, and 7.

NOTE 5:  Room Temperature Set Back or Independent Relay Input

If using the CCRP with the 1000, 2000 and/or 2100 series room heating units and utilizing the automatic room
temperature set back feature, the addition of a signaling device is required to initiate the set back time.  This
signaling device attaches to the “E” and "R" positions of the terminal strip in the CCRP.  The transmitter in the
CCRP receives the set back signal, and, in turn, sends the signal (wireless) to the heater(s).

If the power company uses multiple signals for peak control of devices on different rate strategies, the “E”
terminal position can be used as the input port to trigger peak control of those devices on the separate strategy
rather than for room temperature set back.

NOTE 6:  Jumpers 8 and 9 (Isolated Relay Switching - Multiple Control Strategy Applications)

These jumpers couple the relays to different input signals and enable separate control of the circuits connected
to them.  If these jumpers are set to the “ON” position, the relays are controlled by the microprocessor on the
circuit board through either the “P” or “E” input terminals depending on dip switch 6 setting in the CCRP.  If
Jumper 8 (J8) is in the “OFF” position, relays 7, 8, and 9 respond only to the OV4 input terminal.  If Jumper 9
(J9) is in the “OFF” position, relay 1 responds only to the OV1 input terminal; relay 2 responds only to the OV2
input terminal; and relay 3 responds only to the OV3 input terminal.

Depending upon how the controllable devices are field wired into the circuit board, the positions of J8 and J9
jumpers, and dip switch 6 setting, it is possible to have the CCRP provide individual load control for up to 6
separate control strategies.  If utilizing multiple control strategies, refer to Dip Switch Settings description, the
Relay Triggering Schematic, and the Example System Wiring Diagram for Multiple Strategies in this manual.

NOTE 7:  Anticipated Peak

Typically, power companies are capable of sending one signal for peak control of selected devices.  There are
some instances; however, where power companies are capable of sending multiple signals for control pur-
poses.  In these situations, it is possible to have on-peak hours, off-peak hours, and anticipated peak (pre-peak)
hours.

On-peak 

hours are those times during which a controllable load is disabled.  

Off-peak 

hours are those times

during which a controllable load is allowed to operate.  

Anticipated (pre-peak) 

hours are those times during

which ETS equipment can be prepared for an upcoming on-peak (control) period, or a time when power
companies can apply customized control of the ETS equipment. If uncertain as to whether this option is being
used in your area, contact your local power company representative.

Š

Devices controlled by relays 4, 5, and 6 can never
be overridden.

Š

If the CCRP is being used to do both peak control
and automatic charge control of fluid regulated
ETS room heating systems, then peak override of
the fluid regulated ETS heater(s) is not possible.

IMPORTANT

Summary of Contents for CCRP

Page 1: ...ommitment to Innovation Manufactured in North America OPERATION INSTALLATION GUIDE FOR Applicable to Software Version 14 0 14 9 Comfort Control Relay Panel CCRP 9 Pole CCRP 4 Pole CCRP Off Peak System Control ...

Page 2: ...shall Steffes Corporation be liable for any indirect special or consequential damages or lost profits In compiling this manual Steffes Corporation has used its best judgement based upon information available but disclaims any responsibility or liability for any errors or miscalculations contained herein or any revisions hereof or which result in whole or in part from the use of this manual or any ...

Page 3: ...RP Circuit Board Configuration Diagram 3 Notes 4 5 DipSwitchSettings 6 7 TestingPLCCommunication 7 TypicalSystemWiringDiagram NinePole 8 TypicalSystemWiringDiagram FourPole 9 RelayTriggeringSchematic 10 Example SystemWiringDiagramforMultipleControlStrategyApplications 11 Table of Contents TC ...

Page 4: ...ceive this signal and respond accordingly The PLC control feature allows for peak control of devices without having to do direct wiring This feature can reduce installation costs significantly especially in multiple unit installations and projects such as housing subdivisions hotels motels apartments condo s etc PLC Communication is very reliable in most applications but can be affected and hinder...

Page 5: ...e existing power lines wireless communication to an unlimited number of 1000 2000 and 2100 series room heaters Comfort Plus systems and the Steffes Mini Receivers provided all systems are operating at 240V or less and are on the same power company distribution transformer Peak and anticipated peak pre peak control signals Outdoor temperature information for automatic brick core charging of ETS roo...

Page 6: ...witch 2 and 3 are ON in this diagram Transformer Microprocessor Software Relay 6 Relay 5 On LED 3 See Note 6 LED 4 Relay 8 LED 2 Relay 9 See Note 6 Override Jumper J8 LED 5 1 2 3 1 2 3 Relay 7 LED 6 Override Jumper J9 Off 1 2 3 N L2 L1 A1 P2 See Note 3 A Anticipated Peak See Note 7 OV1 Relay 1 Override Multiple Control Input OV2 Relay 2 Override Multiple Control Input OV3 Relay 3 Override Multiple...

Page 7: ...r is unable to process information Check system wiring Continuous Illumination Will occur any time a peak control signal is being received Slow Flash 4 second duration Will occur during off peak times The illumination time of the light is in direct relation to the temperature information the CCRP is receiving from the outdoor temperature sensor A long illumination time indicates warmer temperature...

Page 8: ...tching Multiple Control Strategy Applications These jumpers couple the relays to different input signals and enable separate control of the circuits connected to them If these jumpers are set to the ON position the relays are controlled by the microprocessor on the circuit board through either the P or E input terminals depending on dip switch 6 setting in the CCRP If Jumper 8 J8 is in the OFF pos...

Page 9: ... will be overridden DIP SWITCH 2 3 4 AND 5 TRANSMIT CHANNEL The transmitter built into the Steffes CCRP is capable of transmitting on one of fifteen channels The dip switch settings in the CCRP must be set to match the channel setting of the receiving device s To select the power line carrier communication channel desired use the chart below and set dip switches 2 3 4 and 5 to the appropriate posi...

Page 10: ...e outdoor temperature sensor information upward if it is reading lower than the actual outdoor temperature In most situations this procedure does not need to be performed FACTORY DEFAULT SETTING OFF Off Standard operating position On A positive 5o F 5o F outdoor temperature calibration is applied TESTINGPLC COMMUNICATION If using the built in PLCTransmitter Feature forControl The PLC system is a h...

Page 11: ...YSTEM GROUND CIRCUIT 3 CIRCUIT 7 CIRCUIT 9 CIRCUIT 8 CIRCUIT 6 CIRCUIT 4 CIRCUIT 5 20 AMP MAX CIRCUIT ONE CIRCUIT 2 CIRCUIT 1 See Note 3 ANTICIPATED TEMPERATURE PEAK CONTROL UTILITY SWITCH SET BACK ROOM Field Installed Wiring TYPICAL SYSTEM WIRING DIAGRAM NINE POLE Utilizing PLC Control with the Steffes 1000 2000 2100 Series Room Units A panel label is provided in the package of screws used to mou...

Page 12: ...ed Peak CIRCUIT ONE 20 AMP MAX OPTION A RED CIRCUIT Red Circuit 2 TYPICAL SUPPLY Red Circuit 1 Black Circuit 1 Black Circuit 2 CIRCUITS 5 4 3 2 1 10 9 8 7 240VAC SOURCE 6 BLUE BLUE BLACK GREEN DUAL OPTION FEED BLACK RED RED GREEN BLUE BLACK BLUE BLACK RED RED SYSTEM GROUND SEE NOTE 2 NOTE MODELS 2002 AND 2003 DO NOT HAVE SINGLE FEED CIRCUIT 2 CIRCUIT 3 CIRCUIT 1 CIRCUIT 4 A panel label is provided...

Page 13: ...trip connections E Room Temperature Set Back or Independent Relay Control OV4 Relays 7 8 and 9 Override or Multiple Control Input ON OFF Relay Relay Relay Jumper 8 ON Jumper 9 OFF Relay Relay SWITCH DIP 6 OVC Override Common OVR Override Hot OVS Override Switch A Anticipated Peak R Low Voltage Hot OS Outdoor Sensor OS Outdoor Sensor C Low Voltage Common Relay Relay Relay Relay Input Voltage P2 L2 ...

Page 14: ... Switch Connect to P Connect to R Switch Switch Relay 1 OPTIONAL SENSOR OUTDOOR Jumper J8 1 2 3 Override Microprocessor Transformer OS OS P R E A EXAMPLE SYSTEM WIRING DIAGRAM FOR MULTIPLE CONTROL STRATEGYAPPLICATIONS 1 Dip switch 6 must be ON to enable independent relay control Refer to dip switch 6 setting description in this manual 2 Override Jumper J8 must be OFF in this application Refer to N...

Page 15: ...edeviceismovedfromthepremisesinwhichitwasoriginallyinstalled This Warranty shall not apply to the device or its part which have been altered in any respect or improperly installed serviced or used or have been subject to accident negligence abuse or misuse THEABOVE WARRANTYBYSTEFFES IS EXCLUSIVEAND IN LIEU OFALLOTHER WARRANTIES WHETHER WRITTEN OR ORAL EXPRESS OR IMPLIED INCLUDING ANYIMPLIED WARRAN...

Reviews: