763.134 Z02 1913 coolcept_fleX
4.7
Setting the feed-in management
Depending on the country, PV generators must be able to reduce the fed-in active power.
The following products are suitable for implementing this legal requirement:
•
StecaGrid SEM
•
WEB’log from Meteocontrol
•
Solar-Log from Solare Datensysteme
•
Energy-Manager from Kiwigrid
An energy meter can be connected to the inverter via the Modbus RTU interface (refer to
section 3.9.7).
The feed-in management is set in the "Energy management"
submenu (refer to section 7.1).
•
"Mode": switching the energy meter on or off
•
"Dyn. feed in control": limiting the value of feed-in
•
"Configuration": selecting an energy meter
4.7.1 Switching the energy meter on or off
•
"Off": switching the energy meter off
•
"Energymeter": switching the energy meter on
4.7.2 Limiting the dynamic feed-in value
1. Limit the power fed into the grid. You can enter values
starting from 0 W and incrementing by 10 W.
4.7.3 Selecting an energy meter
The inverter can only communicate with the energy meters that
have been preprogrammed.
1. Call the "Metertype" menu by pressing "SET".
2. Using "
", select a meter type from the list of preprogrammed energy meters.
3. Exit the menu with "ESC".