STATUS SCIENTIFIC CONTROLS
Installation, Commissioning & Routine Gas Testing
FGD10A-M Gas Detector
TD18/032
Issue:
10
Change Note:
1869
Page 71
LOGICAL
ADDRESS
(R/W)
DATA
TYPE
DESCRIPTION
40235
R/W
MSFP16
Hysteresis Value Float
Most significant 16 bits of IEEE574
floating point value.
40236
R/W
LSFP16
Hysteresis Value Float
Least significant 16 bits of IEEE574
floating point value.
40237
R/W
uINT16
Warm up Timer
: e.g. 0x002d=45s
40238
R/W
uINT16
Screen On Time
e.g. 0x0001= 1 min
40239
R/W
uINT16
Screen Off Time
e.g. 0x000A= 10 min
40251
R/W
uINT16
RTC Seconds
e.g. 0x002F= 47
40252
R/W
uINT16
RTC Minutes
e.g. 0x001C= 28
40253
R/W
uINT16
RTC Hours
e.g. 0x000D =1 pm
40254
R
uINT16
RTC Weekday
not yet implemented
40255
R/W
uINT16
RTC Day
e.g. 0x0013 =19th
40256
R/W
uINT16
RTC Month
e.g. 0x0006= June
40257
R/W
uINT16
RTC Year
e.g. 0x000D= 2013
40301
R
uINT16
Alarm1 Year
The year the most recent alarm1
occurred e.g. 0x000D= 2013
40302
R
uINT16
Alarm1 Month
The month the most recent alarm1
occurred e.g. 0x0006= June
40303
R
uINT16
Alarm1 Day
The day the most recent alarm1
occurred e.g. 0x0013 =19th
40304
R
uINT16
Alarm1 Hours
The hour the most recent alarm1
occurred e.g. 0x000D =1 pm
40305
R
uINT16
Alarm1 Minutes
The minute the most recent alarm1
occurred e.g. 0x001C= 28