STATUS SCIENTIFIC CONTROLS
Installation, Commissioning & Routine Gas Testing
FGD10A-M Gas Detector
TD18/032
Issue:
10
Change Note:
1869
Page 31
For gases on the
“Flammable” menu other than methane
, the
Span operation must be carried out with propane.
•
Apply a known concentration of Propane e.g. 55% LEL at a
flow rate of between 500 and 1000cc/min. Allow time for the
sensor to respond.
•
From the menu system select menu option:
Sensor Span
and
press ENTER.
Gas Level
Edit
.
+
•
For calibration gas 1.1% this corresponds to a gas level of 55%
at the default LEL of 2.0%v/v. Change the gas level to 55% and
press ENTER.
Calibration
Span Sensor
•
To accept the calibration value, press ENTER.
Calibration
Updated