STATUS SCIENTIFIC CONTROLS
Installation, Commissioning & Routine Gas Testing
FGD10A-M Gas Detector
TD18/032
Issue:
10
Change Note:
1869
Page 23
Where a weather guard is not fitted, the use of a sampling adaptor (Stock
No. SS336) is required in order to present the gas to the FGD10A-M sensor.
8.2.2. Sampling time
Apply the test gas and allow a sufficient time for the sample to reach the gas
detector. The response time will vary according to the length of the sampling
tube.
8.2.3. Suggested calibration gas levels.
Hydrocarbon sensor:
Zero
gas free air.
Span
50% of the measuring range.