14 PROsine 2.5/3.0 Advanced Control System (ACS) Owner’s Manual
Error
Code
Description of Fault
Cause
Solution
205
Internal fault
Various
Record the error code and
contact Statpower.
206
AC Output voltage too high
1. Some loads, like motors,
can feed power back into
the output of the PROsine.
This may result in a
temporary over-voltage
which may trigger a fault
condition.
2. There is an internal
hardware or software fault
1. Contact Statpower if you
find incompatibility with
certain type of loads.
2. Record the error code and
contact Statpower.
207
Internal DC Bus voltage low.
1. Temporary condition
caused by low battery
voltage in conjunction with
an overload condition.
2. Internal Fault.
1. Check if battery is OK (see
error code 002).
Disconnect AC and DC
power to the PROsine.
Reconnect DC and AC
power after 15 minutes. If
the problem persists,
contact Statpower
Customer Service.
2. Contact Statpower.
Summary of Contents for Prosine 2.5
Page 2: ......