Temperatures Menu
Description/Action
Display
•
Differential
- Adjustable user setting that changes the tank
temperature differential with a range of 2° to 20°F. The factory
setting is 8°F.
•
Tank Temperature
- Non adjustable. Control system sensed
temperature (averaged from upper & lower temperature probes).
•
Tank Probe Offset
- adjustable user setting, range -5° to +5°
(factory setting 0°).
Note:
These settings should only be used if hot water supply
temperature varies greatly from the Operating Set Point
setting.
•
The Tank Probe Offset is used to calibrate control system
temperature sensing. This can improve the precision of
temperature control in the storage tank and at points of use.
This feature can also be used to compensate for building
recirculation loops (hot water returning to the storage tank) that
may cause the heating cycles to terminate prematurely.
•
Example: If the current temperature from a temperature probe is
120°F (49°C) and the Offset setting is adjusted to a value other
than 0°, the control system would calibrate or “offset” the sensed
temperature from the probe and the averaged tank temperature.
Heating cycles would be activated and deactivated based on
the calibrated (offset) temperature. A -5° setting results in +5°
hotter water.
•
These settings are adjusted as described in
Temperatures
HELP
BACK
Operating Setpoint
120°F >
Differential
8°F >
Tank Temperature
120°F
Tank Probe Offset
0°F >
HEATER STATUS MENU
Description/Action
Display
Press Heater Status from the Main Menu to enter this menu. This menu
contains non adjustable operational information. Use the slidebar to navigate
the menu.
•
Status
- displays the current Operating State, see
•
ECO Contact
,
Low Gas PS
,
Blocked Inlet PS
,
Blocked Outlet
PS
,
Blower Prover PS
- displays the current state of the switch
contacts; open or closed.
•
Igniter On
,
Gas Valve On
- displays whether or not the control
system is currently energizing these water heater components; yes
= energized, no = de-energized.
•
Flame Detected
- displays whether or not the control system has
detected Main Burner flame during ignition from the flame sensor.
•
Blower RPM CMD –
displays the controls commanded blower
rpms.
•
Blower RPM –
displays the actual blower rpms.
•
Anode Current, Anode Tank Voltage, Anode Drive Voltage –
displays the powered anodes current and voltage levels.
Note:
Menu displays shown are for informational purposes only. The
actual heater display will vary dependent upon the operational
state of the water heater.
Top of Menu
Heater Status
HELP
BACK
Status:
Standby
ECO Contact
Closed
Low Gas PS
Closed
Blocked Inlet PS
Closed
Blocked Outlet PS
Closed
Igniter On
No
Middle of Menu
Heater Status
HELP
BACK
Gas Valve On
No
Flame Detected
No
Blower RPM CMD
0
Blower RPM
0
Anode Current
51.500mA
Anode Tank Voltage
2.641V
Bottom of Menu
Heater Status
HELP
BACK
Flame Detected
No
Blower RPM CMD
0
Blower RPM
0
Anode Current
51.500mA
Anode Tank Voltage
2.641V
Anode Drive Voltage
3.539V