background image

22

The condensate trap may be primed by filling the CONDENSATE 

U-ASSEMBLY with tap water while the water heater is not operating. 

The system is fully primed when the water level reaches the adaptor 

connected into the Tee. In most installations the water heater will 

self-prime the condensate trap during the first full heat-up cycle. If 

a sound of air bubbling through water (gurgling) is heard while the 

blower is operating after the first heat-up cycle, then turn the unit off 

and contact your plumber or service representative.
If these instructions are not followed, the condensate build-up will 

block the exhaust outlet, which will cause improper operation.

Do 

NOT

block or

plug any

hole in this

hex plug.

DRAIN LINE

CONDENSATE 

U-ASSEMBLY, 

AKA. VENT PIPE 

ASSEMBLY #1

*NO PORTION OF THE FIELD SUPPLIED DRAIN LINE BEYOND 

 THE 1/2" ADAPTOR MAY BE ELEVATED HIGHER THAN THE 

 ADAPTOR.  THIS MUST BE  TRUE  FOR  THE  ENTIRE LENGTH 

 OF DRAIN LINE INCLUDING EXIT INTO AN APPROPRIATE DRAIN.

APPROXIMATELY

0.25" (6.35 mm)

fIGure 16.

Condensate is likely to form in the venting system attached to this 

water heater. The vent pipe should be sloped downward away from 

the blower assembly (not less than 1/8” (3.2 mm) nor greater than 1/2” 

(12.7 mm) per foot (30 cm) maximum). If the vent piping is vented level 

or sloped upwards away from the blower assembly, then adequate 

means for draining and disposing of the condensate needs to be made 

by the installer. Two 3/8” condensate hoses should be connected to 

the built in drain ports of blower outlet adaptor. If a VAA is installed, 

a 3/8” condensate hose should be connected to the barb fitting on it; 

otherwise the unused barb fitting on vent pipe assembly #2 should be 

plugged with one of the break-away plugs. See Figure 17.

Condensate neutralizer kits are available. Contact your distributor 

or Service Agency.

Blower asseMBlY InstallatIon

1.  This power vented water heater comes with blower assembly installed.
2.  After unit is set in place, make sure blower assembly is still mounted 

securely. Also make sure both drain ports of  rubber boot vent adapter 

are capped off. Lastly, make sure there is no damage to blower.

3.  Condensate drains from three locations on blower assembly. See 

Figure 17. One flexible hose runs from bottom of blower housing; 

two run from the ports of rubber connector at the outlet of blower. 

All these three condensate hoses are connected to barb fittings at  

vent pipe assembly #2. The hose from bottom of blower housing is 

clamped by two clamps and the two hoses from rubber connector are 

harnessed by another clamp. Make sure there is no kink or twist.

fIGure 17.

4.  Make sure there is no packing material in the inlet or discharge 

of the blower.

5.  Make sure that the plastic tubing is still attached from the air 

pressure switch to the port on the blower housing. Make sure 

the plastic tubing is not folded anywhere between the pressure 

switch and the blower housing.

6.  Make sure the ON/OFF switch is in the OFF position and that 

the outer harness is connected from the blower control box to 

the connector on the bottom side of the gas valve.

7.  If the outer harness is not factory installed, make sure the ON/

OFF switch is in the OFF position and then connect the outer 

harness from the blower control box to the connector on the 

bottom side of the gas valve.

8.  Do not plug in power cord until vent system is completely installed.  

The Power Vent operates on 110-120 Vac. therefore a grounded 

outlet must be within reach of the 6 foot (1.8 m) flexible power cord 

supplied with the vent (See Figure 1). The power cord supplied 

may be used on a unit only where local codes permit.  If local 

codes do not permit use of flexible power supply cord:

 

A.   Make sure the unit is unplugged  from the wall outlet. Remove 

the plastic top cap. Remove screws and open panel on the 

front of the control box on the blower.

  B.  Cut the flexible power cord, leaving enough to be able to make 

connections. Remove the strain relief fitting from the box.

  C.  Install a suitable conduit fitting inside the enclosure.

  D.  Splice field wiring into existing wiring using code authorized 

method (wire nuts, etc).

 

E.  Be certain that neutral and line connections are not reversed 

when making these connections.

 

F.  Ground heater properly.  This water heater must be grounded 

in accordance with the National Electrical Code NFPA 70 or the 

Canadian Electrical Code C22.1 and/or local codes. These 

must be followed in all cases.

   

The water heater must be connected to a grounded metal, 

permanent wiring system; or an equipment grounding 

conductor must be run with the circuit conductors and 

connected to the equipment grounding terminal or lead on 

the water heater, see Figure 19.

  G.  Close the panel on the control box. Make sure that the access 

panel is secured shut.

 

9.  The blower discharge boot is made to accept only straight sections of 

2” pipe. To start off with an elbow, a short section of the furnished 

pipe, a minimum of 2 inches (5.1 cm), must be cut and glued into 

the end of the elbow that will mount on the discharge boot.

InstallatIon of vent sYsteM

Before beginning installation of piping system thoroughly read the 

section of this manual VENT PIPE PREPARATION.

If you are installing your system so that it vents through roof, please refer 

to section  titled INSTALLATION OF VERTICAL VENT SYSTEM.

vent terMInal InstallatIon, sIdewall

1.  Install the vent terminal by using the cover plate as a template to 

mark the hole for the vent pipe to pass through the wall.  BEWARE 

OF CONCEALED WIRING AND PIPING INSIDE THE WALL.

2.  If the Vent Terminal is being installed on outside of a finished wall, it 

Summary of Contents for SHE 50 76N

Page 1: ...L AND WARRANTY QUESTIONS SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEA...

Page 2: ...alert symbol indicates a potentially hazardous situation which if not avoided could result in property damage WARNING CAUTION CAUTION DANGER All safety messages will generally tell you about the type...

Page 3: ...3 GENERAL SAFETY INFORMATION...

Page 4: ...4 GENERAL SAFETY INFORMATION at least 18 45 7cm above the floor This will reduce but not eliminate the risk...

Page 5: ...ilablefromNational Fire Protection Association 1 Batterymarch Park Quincy MA 02269 3 The water heater when installed must be grounded in accordance with the local codes or in the absence of local code...

Page 6: ...feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch...

Page 7: ...Exhaust Tee GG Elbow GET TO KNOW YOUR WATER HEATER GAS MODELS A Vent Pipe B Anode C Hot Water Outlet D Outlet 120 VAC F Gas Supply G Main Manual Gas Shut Off Valve H Ground Joint Union J Dirt Leg K O...

Page 8: ...8 TYPICAL INSTALLATION CONDENSATE HOSE AND DRAIN PAN FIGURE 1 continued...

Page 9: ...ship for normal adult skin If anyone using hot water provided by the water heater being installed fits into one of these groups or if there is a local code or state law requiring a certain water tempe...

Page 10: ...cs All models Maximum Supply Pressure 14 inches W C 3 48kPa Minimum Supply Pressure Natural Gas 5 0 inches W C 1 24kPa Minimum Pressure must be maintained under both load and no load static and dynami...

Page 11: ...talled in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detector or water s...

Page 12: ...rine based chemicals refrigerants etc in addition to being highly flammable in many cases will also react to form corrosive hydrochloric acid when exposed to the combustion products of the water heate...

Page 13: ...e the size of openings providing fresh air into confined spaces EXHAUST FANS Where exhaust fans are installed additional air shall be provided to replace the exhausted air When an exhaust fan is insta...

Page 14: ...a reference for the openings that provide fresh air into confined spaces only Do not refer to these illustrations for the purpose of vent installation See Installation of Vent System on pages 20 21 fo...

Page 15: ...f code requirements or such conditions as high line pressure among others have installed devices such as pressure reducing valves check valves and back flow preventers Devices such as these cause the...

Page 16: ...the T P valve Secure all insulation using tape Temperature Pressure Relief Valve Explosion Hazard Temperature Pressure Relief Valve must comply with ANSI Z21 22 CSA 4 4 and ASME code Properly sized T...

Page 17: ...T P valve is not intended for the constant relief of thermal expansion Aproperly sized thermal expansion tank must be installed on all closed systems to control thermal expansion see Closed Water Syst...

Page 18: ...system by closing itsindividualmanualShut offvalveduringanypressuretestingofthegas supply piping system at test pressures equal to or less than 1 2 pound per square inch 3 5 kPa Connecting gas piping...

Page 19: ...uctions Assemble Vent Pipe Assemblies 1 2 and 3 See Figure 1 prior to cementing The preferred orientation of Vent Pipe Assembly 1 Condensate U Assembly is shown in Figure 16 However this assembly may...

Page 20: ...0 cm 12 inches 30 cm K Clearance to a mechanical air supply inlet 6 feet 1 83 m 3 feet 91 cm above if within 10 feet 3 m horizontally E Clearance to unventilated soffit 12 inches 30 cm 12 inches 30 cm...

Page 21: ...ectmaterialasdetailedabovehasbeenused andthatminimum ormaximumventlengthsandterminallocationasdetailedinthismanual have been met Carefully inspect entire venting system for any signs of cracks or frac...

Page 22: ...that the plastic tubing is still attached from the air pressure switch to the port on the blower housing Make sure the plastic tubing is not folded anywhere between the pressure switch and the blower...

Page 23: ...ine This will allow the vent to easily slide through the opening The resulting gap will be covered up by the Vent Terminal cover plate Repeat this step on inside wall if necessary SEQUENCE OF INSTALLA...

Page 24: ...ighest anticipated snow level install a snorkel as shown in bottom portion of Figure 20 NOTE With the installation of a snorkel it is necessary to use two 90 elbows that shall be considered along with...

Page 25: ...cement not included with kit and glue the two inch PVC pipe coming from the blower into the VAA 3 Perform the same sequence on the PVC pipe coming from the exhaust side vent terminal side of the VAA...

Page 26: ...and the vent pipe system Air leaks will allow flue gas by products to disseminate into the room creating an unsafe environment and could cause illness asphyxiation and or even death FIGURE 24 Typical...

Page 27: ...and above PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitutes for cleanin...

Page 28: ...make a second mark as the primer and cement will most likely destroy your first one Apply primer to the surface of the pipe and fitting socket with a natural bristle brush This process softens and pr...

Page 29: ...R buttons together and holding for 1 second Then press the COOLER button until the WARM indicator light appears 2 Set the ON OFF switch on the blower control box to the OFF position 3 Turn off all ele...

Page 30: ...c does not have access If a suitable area is not available a cover should be installed over the thermostat to prevent tampering Thewatertemperaturesettingwasfactorysetatthelowesttemperature Pressing t...

Page 31: ...cal water heater supplier or service agency for further information concerning an Anode Replacement Kit and this chlorination treatment If the smelly water persists after the anode replacement and chl...

Page 32: ...uld be made of the main burner and the hot surface igniter assembly for proper flame characteristics and ignition sequences This can be done by removing the Outer Door and viewing the main burner oper...

Page 33: ...ve a thermal expansion tank installed is not covered under the limited warranty Thermal expansion tanks must be installed on all closed water systems DO NOT PLUG THE TEMPERATURE PRESSURE RELIEF VALVE...

Page 34: ...ose connections or the relief valve DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken Leakage from other appliances wat...

Page 35: ...control does not energize the blower replace the Intelli Vent control If the blower fails to Blower may run continuously in start when energized replace the blower assembly this condition 2 Ensure the...

Page 36: ...ff for 10 20 seconds then on again to clear this error code 4 Ensure the flame sensor is clean use ultra fine steel wool or Scotch Brite pad to clean flame sensor 5 Ensure the hot surface ignitor is p...

Page 37: ...in tolerance 1 Ensure air pressure switch hose is not kinked or clogged ensure the blower housing is clear of any condensation 2 Check vent temperature limit switch if it is determined that the vent t...

Page 38: ...38 These guidelines should be utilized by a qualified service agent TROUBLESHOOTING GUIDELINES TROUBLESHOOTING GUIDELINES...

Page 39: ...installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited warranty the warrantor will...

Page 40: ...www statewaterheaters com 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 365 0024 Parts 800 821 2017...

Reviews: