background image

15

This water heater should not be connected to any heating systems or 

component(s) used with a non-potable water heating appliance.

All piping components connected to this unit for space heating 

applications should be suitable for use with potable water.

Toxic chemicals, such as those used for boiler treatment should not 

be introduced into this system.
When the system requires water for space heating at temperatures 

higher than required for domestic water purposes, a tempering 

valve must be installed. Please refer to Figure 2 for suggested 

piping arrangement.

space heatInG and potaBle water sYsteM

This  appliance  has  been  design  certified  as  complying  with 

American National Standard/CSA Standard for water heaters  

and  is  considered  suitable  for  Water  (Potable)  Heating  and  

Space Heating.
Your water heater is equipped with inlet/outlet connections 

for  use  in  space  heating  applications  (see  Figure  2).  If  this 

water heater is to be used to supply both space heating and 

potable  (drinking)  water,  the  instructions  listed  below  must 

be followed:
•  Be sure to follow the manual(s) shipped with the air handler or other 

type heating system.

•  This water heater is not to be used as a replacement for an existing 

boiler installation.

•  Do not use with piping that has been treated with chromates, boiler 

seal or other chemicals and do not add any chemicals to the water 

heater piping

•  If the space heating system requires water temperatures in excess 

of  120°F  (49°C),  a  tempering  valve  must  be  installed  per  the 

manufacturer’s instructions in the potable hot water supply to limit 

the risk of scald injury.

•  Pumps, valves, piping and fi ttings must be compatible with potable 

water.

•  A  properly  installed  flow  control  valve  is  required  to  prevent 

thermosiphoning. Thermosiphoning is the result of a continuous 

flow  of  water  through  the  air  handler  circuit  during  the  off  cycle. 

Weeping  (blow  off)  of  the  temperature  and  pressure  relief  valve  

(T & P) or higher than normal water temperatures are the first signs 

of thermosiphoning.

•  The hot water line from the water heater should be vertical past any 

tempering valve or supply line to the heating system to remove air 

bubbles from the system.

•  Do  not  connect  the  water  heater  to  any  system  or  components 

previously used with non-potable water heating appliances when 

used to supply potable water.

closed water sYsteMs

Water supply systems may, because of code requirements or such 

conditions as high line pressure, among others, have installed 

devices such as pressure reducing valves, check valves, and back 

flow preventers. Devices such as these cause the water system to 

be a closed system.

cheMIcal vapor corrosIon

CORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY 

OCCUR IF AIR FOR COMBUSTION CONTAINS CERTAIN CHEMICAL 

VAPORS. SUCH CORROSION MAY RESULT IN FAILURE AND 

RISK OF ASPHYXIATION.
Spray can propellants, cleaning solvents, refrigerator and air 

conditioning refrigerants, swimming pool chemicals, calcium and 

sodium chloride (water softener salt), waxes, and process chemicals 

are typical compounds which are potentially corrosive.
Do not store products of this sort near the heater. Also, air which is 

brought in contact with the heater should not contain any of these 

chemicals. If necessary, uncontaminated air should be obtained from 

remote or outside sources. The limited warranty is voided when failure 

of water heater is due to a corrosive atmosphere. (See limited warranty 

for complete terms and conditions).

water pIpInG

DANGER

Water temperature over 125°F (52°C)

can cause severe burns instantly

resulting in severe injury or death.
Children, the elderly and the physically 

or mentally disabled are at highest 

risk for scald injury.
Feel water before bathing or showering.
Temperature limiting valves are 

available.
Read instruction manual for safe

temperature setting.

HOTTER  WATER  CAN  SCALD: 

Water heaters are intended to produce hot water. Water heated to 

a temperature which will satisfy space heating, clothes washing, 

dish washing, cleaning and other sanitizing needs can scald and 

permanently injure you upon contact. Some people are more likely 

to be permanently injured by hot water than others. These include 

the elderly, children, the infirm, or physically/mentally handicapped. 

If anyone using hot water fits into one of these groups or if there is 

a local code or state law requiring a certain temperature water at the 

hot water tap, then you must take special precautions. In addition to 

using lowest possible temperature setting that satisfies your hot water 

needs, a means such as a mixing valve, should be used at hot water 

taps used by these people or at the water heater, see Figure 2. Valves 

for reducing point of use temperature by mixing cold and hot water are 

also available:

 

Consult a Qualified Installer or Service Agency. Follow  manufacturer’s 

instructions for installation of valves. Before changing the factory setting 

on thermostat, read “Temperature Regulation” section in this manual.

InstallInG the new water heater

Summary of Contents for SHE 50 76N

Page 1: ...L AND WARRANTY QUESTIONS SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEA...

Page 2: ...alert symbol indicates a potentially hazardous situation which if not avoided could result in property damage WARNING CAUTION CAUTION DANGER All safety messages will generally tell you about the type...

Page 3: ...3 GENERAL SAFETY INFORMATION...

Page 4: ...4 GENERAL SAFETY INFORMATION at least 18 45 7cm above the floor This will reduce but not eliminate the risk...

Page 5: ...ilablefromNational Fire Protection Association 1 Batterymarch Park Quincy MA 02269 3 The water heater when installed must be grounded in accordance with the local codes or in the absence of local code...

Page 6: ...feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch...

Page 7: ...Exhaust Tee GG Elbow GET TO KNOW YOUR WATER HEATER GAS MODELS A Vent Pipe B Anode C Hot Water Outlet D Outlet 120 VAC F Gas Supply G Main Manual Gas Shut Off Valve H Ground Joint Union J Dirt Leg K O...

Page 8: ...8 TYPICAL INSTALLATION CONDENSATE HOSE AND DRAIN PAN FIGURE 1 continued...

Page 9: ...ship for normal adult skin If anyone using hot water provided by the water heater being installed fits into one of these groups or if there is a local code or state law requiring a certain water tempe...

Page 10: ...cs All models Maximum Supply Pressure 14 inches W C 3 48kPa Minimum Supply Pressure Natural Gas 5 0 inches W C 1 24kPa Minimum Pressure must be maintained under both load and no load static and dynami...

Page 11: ...talled in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detector or water s...

Page 12: ...rine based chemicals refrigerants etc in addition to being highly flammable in many cases will also react to form corrosive hydrochloric acid when exposed to the combustion products of the water heate...

Page 13: ...e the size of openings providing fresh air into confined spaces EXHAUST FANS Where exhaust fans are installed additional air shall be provided to replace the exhausted air When an exhaust fan is insta...

Page 14: ...a reference for the openings that provide fresh air into confined spaces only Do not refer to these illustrations for the purpose of vent installation See Installation of Vent System on pages 20 21 fo...

Page 15: ...f code requirements or such conditions as high line pressure among others have installed devices such as pressure reducing valves check valves and back flow preventers Devices such as these cause the...

Page 16: ...the T P valve Secure all insulation using tape Temperature Pressure Relief Valve Explosion Hazard Temperature Pressure Relief Valve must comply with ANSI Z21 22 CSA 4 4 and ASME code Properly sized T...

Page 17: ...T P valve is not intended for the constant relief of thermal expansion Aproperly sized thermal expansion tank must be installed on all closed systems to control thermal expansion see Closed Water Syst...

Page 18: ...system by closing itsindividualmanualShut offvalveduringanypressuretestingofthegas supply piping system at test pressures equal to or less than 1 2 pound per square inch 3 5 kPa Connecting gas piping...

Page 19: ...uctions Assemble Vent Pipe Assemblies 1 2 and 3 See Figure 1 prior to cementing The preferred orientation of Vent Pipe Assembly 1 Condensate U Assembly is shown in Figure 16 However this assembly may...

Page 20: ...0 cm 12 inches 30 cm K Clearance to a mechanical air supply inlet 6 feet 1 83 m 3 feet 91 cm above if within 10 feet 3 m horizontally E Clearance to unventilated soffit 12 inches 30 cm 12 inches 30 cm...

Page 21: ...ectmaterialasdetailedabovehasbeenused andthatminimum ormaximumventlengthsandterminallocationasdetailedinthismanual have been met Carefully inspect entire venting system for any signs of cracks or frac...

Page 22: ...that the plastic tubing is still attached from the air pressure switch to the port on the blower housing Make sure the plastic tubing is not folded anywhere between the pressure switch and the blower...

Page 23: ...ine This will allow the vent to easily slide through the opening The resulting gap will be covered up by the Vent Terminal cover plate Repeat this step on inside wall if necessary SEQUENCE OF INSTALLA...

Page 24: ...ighest anticipated snow level install a snorkel as shown in bottom portion of Figure 20 NOTE With the installation of a snorkel it is necessary to use two 90 elbows that shall be considered along with...

Page 25: ...cement not included with kit and glue the two inch PVC pipe coming from the blower into the VAA 3 Perform the same sequence on the PVC pipe coming from the exhaust side vent terminal side of the VAA...

Page 26: ...and the vent pipe system Air leaks will allow flue gas by products to disseminate into the room creating an unsafe environment and could cause illness asphyxiation and or even death FIGURE 24 Typical...

Page 27: ...and above PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitutes for cleanin...

Page 28: ...make a second mark as the primer and cement will most likely destroy your first one Apply primer to the surface of the pipe and fitting socket with a natural bristle brush This process softens and pr...

Page 29: ...R buttons together and holding for 1 second Then press the COOLER button until the WARM indicator light appears 2 Set the ON OFF switch on the blower control box to the OFF position 3 Turn off all ele...

Page 30: ...c does not have access If a suitable area is not available a cover should be installed over the thermostat to prevent tampering Thewatertemperaturesettingwasfactorysetatthelowesttemperature Pressing t...

Page 31: ...cal water heater supplier or service agency for further information concerning an Anode Replacement Kit and this chlorination treatment If the smelly water persists after the anode replacement and chl...

Page 32: ...uld be made of the main burner and the hot surface igniter assembly for proper flame characteristics and ignition sequences This can be done by removing the Outer Door and viewing the main burner oper...

Page 33: ...ve a thermal expansion tank installed is not covered under the limited warranty Thermal expansion tanks must be installed on all closed water systems DO NOT PLUG THE TEMPERATURE PRESSURE RELIEF VALVE...

Page 34: ...ose connections or the relief valve DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken Leakage from other appliances wat...

Page 35: ...control does not energize the blower replace the Intelli Vent control If the blower fails to Blower may run continuously in start when energized replace the blower assembly this condition 2 Ensure the...

Page 36: ...ff for 10 20 seconds then on again to clear this error code 4 Ensure the flame sensor is clean use ultra fine steel wool or Scotch Brite pad to clean flame sensor 5 Ensure the hot surface ignitor is p...

Page 37: ...in tolerance 1 Ensure air pressure switch hose is not kinked or clogged ensure the blower housing is clear of any condensation 2 Check vent temperature limit switch if it is determined that the vent t...

Page 38: ...38 These guidelines should be utilized by a qualified service agent TROUBLESHOOTING GUIDELINES TROUBLESHOOTING GUIDELINES...

Page 39: ...installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited warranty the warrantor will...

Page 40: ...www statewaterheaters com 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 365 0024 Parts 800 821 2017...

Reviews: