background image

12

in an alcove or closet, the entire floor must be covered by the panel. 

Failure to heed this warning may result in a fire hazard.

Minimum clearances between water heater and combustible 

construction are 0 inch at the sides and rear, 5.5” (14.0 cm) from the 

front and 12” (30.5 cm) from  top. (Standard clearance.) If clearances 

stated on the heater differ from standard clearances, install water 

heater according to clearances stated on the heater.
Adequate clearance 24” (61.0 cm) for servicing this appliance should 

be considered before installation, such as changing the anodes, etc.
A minimum clearance of 5.5” (14.0 cm) must be allowed for access 

to replaceable parts such as thermostats, drain valve, relief valve 

and condensate drain.
When installing the heater, consideration must be given to proper 

location. Location selected should be as close to the wall as practicable 

and as centralized with the water piping system as possible.

FIGURE 4.

A gas water heater cannot operate properly without the correct amount 

of air for combustion. Do not install in a confined area such as a closet, 

unless you provide air as shown in the “Locating The New Water 

Heater” section. Never obstruct the flow of ventilation air. If you have 

any doubts or questions at all, call your gas supplier.  Failure to provide 

the proper amount of combustion air can result in a fire or explosion 

and cause death, serious bodily injury, or property damage.

fIGure 5.

If this water heater will be used in beauty shops, barber shops, 

cleaning establishments, or self-service laundries with dry cleaning 

equipment, it is imperative that the water heater or water heaters 

be installed so that combustion and ventilation air be taken from 

outside these areas.  
Propellants of  aerosol sprays and  volatile  compounds,  (cleaners, 

chlorine based chemicals, refrigerants, etc.) in addition to being highly 

flammable in many cases, will also react to form corrosive hydrochloric 

acid when exposed to the combustion products of the water heater.  

The results can be hazardous, and also cause product failure.

InsulatIon BlanKets

Insulation blankets are available to the general public for external 

use on gas water heaters but are not necessary with these products. 

The purpose of an insulation blanket is to reduce standby heat loss 

encountered with storage tank heaters. Your water heater meets or 

exceeds the Energy Policy Act standards with respect to insulation and 

standby loss requirements, making an insulation blanket unnecessary.
Should you choose to apply an insulation blanket to this heater, you 

should  follow  these  instructions (For  identification of  components 

mentioned below, see Figure 1). Failure to follow these instructions can 

restrict the air flow required for proper combustion, potentially resulting 

in fire, asphyxiation, serious personal injury or death.

•  Do not apply insulation to the top of the water heater, as this will  

interfere with safe operation of the blower assembly.

•  Do not cover the outer door, thermostat or temperature & pressure  

relief valve.

•  Do not allow insulation to come within 2” (5.1 cm) of the floor to  

prevent blockage of combustion air flow to the burner.

•  Do not cover the instruction manual.  Keep it on the side of the  

water heater or nearby for future reference.

•  Do obtain new warning and instruction labels from the manufacturer  

for placement on the blanket directly over the existing labels.

•  Do inspect the insulation blanket frequently to make certain it  

does not sag, thereby obstructing combustion air flow.

aIr requIreMents

For safe operation an adequate supply of fresh uncontaminated 

air for combustion and ventilation must be provided.
An insufficient supply of air can cause recirculation of combustion 

products resulting in contamination that may be hazardous to life. 

Summary of Contents for SHE 50 76N

Page 1: ...L AND WARRANTY QUESTIONS SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEA...

Page 2: ...alert symbol indicates a potentially hazardous situation which if not avoided could result in property damage WARNING CAUTION CAUTION DANGER All safety messages will generally tell you about the type...

Page 3: ...3 GENERAL SAFETY INFORMATION...

Page 4: ...4 GENERAL SAFETY INFORMATION at least 18 45 7cm above the floor This will reduce but not eliminate the risk...

Page 5: ...ilablefromNational Fire Protection Association 1 Batterymarch Park Quincy MA 02269 3 The water heater when installed must be grounded in accordance with the local codes or in the absence of local code...

Page 6: ...feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch...

Page 7: ...Exhaust Tee GG Elbow GET TO KNOW YOUR WATER HEATER GAS MODELS A Vent Pipe B Anode C Hot Water Outlet D Outlet 120 VAC F Gas Supply G Main Manual Gas Shut Off Valve H Ground Joint Union J Dirt Leg K O...

Page 8: ...8 TYPICAL INSTALLATION CONDENSATE HOSE AND DRAIN PAN FIGURE 1 continued...

Page 9: ...ship for normal adult skin If anyone using hot water provided by the water heater being installed fits into one of these groups or if there is a local code or state law requiring a certain water tempe...

Page 10: ...cs All models Maximum Supply Pressure 14 inches W C 3 48kPa Minimum Supply Pressure Natural Gas 5 0 inches W C 1 24kPa Minimum Pressure must be maintained under both load and no load static and dynami...

Page 11: ...talled in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detector or water s...

Page 12: ...rine based chemicals refrigerants etc in addition to being highly flammable in many cases will also react to form corrosive hydrochloric acid when exposed to the combustion products of the water heate...

Page 13: ...e the size of openings providing fresh air into confined spaces EXHAUST FANS Where exhaust fans are installed additional air shall be provided to replace the exhausted air When an exhaust fan is insta...

Page 14: ...a reference for the openings that provide fresh air into confined spaces only Do not refer to these illustrations for the purpose of vent installation See Installation of Vent System on pages 20 21 fo...

Page 15: ...f code requirements or such conditions as high line pressure among others have installed devices such as pressure reducing valves check valves and back flow preventers Devices such as these cause the...

Page 16: ...the T P valve Secure all insulation using tape Temperature Pressure Relief Valve Explosion Hazard Temperature Pressure Relief Valve must comply with ANSI Z21 22 CSA 4 4 and ASME code Properly sized T...

Page 17: ...T P valve is not intended for the constant relief of thermal expansion Aproperly sized thermal expansion tank must be installed on all closed systems to control thermal expansion see Closed Water Syst...

Page 18: ...system by closing itsindividualmanualShut offvalveduringanypressuretestingofthegas supply piping system at test pressures equal to or less than 1 2 pound per square inch 3 5 kPa Connecting gas piping...

Page 19: ...uctions Assemble Vent Pipe Assemblies 1 2 and 3 See Figure 1 prior to cementing The preferred orientation of Vent Pipe Assembly 1 Condensate U Assembly is shown in Figure 16 However this assembly may...

Page 20: ...0 cm 12 inches 30 cm K Clearance to a mechanical air supply inlet 6 feet 1 83 m 3 feet 91 cm above if within 10 feet 3 m horizontally E Clearance to unventilated soffit 12 inches 30 cm 12 inches 30 cm...

Page 21: ...ectmaterialasdetailedabovehasbeenused andthatminimum ormaximumventlengthsandterminallocationasdetailedinthismanual have been met Carefully inspect entire venting system for any signs of cracks or frac...

Page 22: ...that the plastic tubing is still attached from the air pressure switch to the port on the blower housing Make sure the plastic tubing is not folded anywhere between the pressure switch and the blower...

Page 23: ...ine This will allow the vent to easily slide through the opening The resulting gap will be covered up by the Vent Terminal cover plate Repeat this step on inside wall if necessary SEQUENCE OF INSTALLA...

Page 24: ...ighest anticipated snow level install a snorkel as shown in bottom portion of Figure 20 NOTE With the installation of a snorkel it is necessary to use two 90 elbows that shall be considered along with...

Page 25: ...cement not included with kit and glue the two inch PVC pipe coming from the blower into the VAA 3 Perform the same sequence on the PVC pipe coming from the exhaust side vent terminal side of the VAA...

Page 26: ...and the vent pipe system Air leaks will allow flue gas by products to disseminate into the room creating an unsafe environment and could cause illness asphyxiation and or even death FIGURE 24 Typical...

Page 27: ...and above PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitutes for cleanin...

Page 28: ...make a second mark as the primer and cement will most likely destroy your first one Apply primer to the surface of the pipe and fitting socket with a natural bristle brush This process softens and pr...

Page 29: ...R buttons together and holding for 1 second Then press the COOLER button until the WARM indicator light appears 2 Set the ON OFF switch on the blower control box to the OFF position 3 Turn off all ele...

Page 30: ...c does not have access If a suitable area is not available a cover should be installed over the thermostat to prevent tampering Thewatertemperaturesettingwasfactorysetatthelowesttemperature Pressing t...

Page 31: ...cal water heater supplier or service agency for further information concerning an Anode Replacement Kit and this chlorination treatment If the smelly water persists after the anode replacement and chl...

Page 32: ...uld be made of the main burner and the hot surface igniter assembly for proper flame characteristics and ignition sequences This can be done by removing the Outer Door and viewing the main burner oper...

Page 33: ...ve a thermal expansion tank installed is not covered under the limited warranty Thermal expansion tanks must be installed on all closed water systems DO NOT PLUG THE TEMPERATURE PRESSURE RELIEF VALVE...

Page 34: ...ose connections or the relief valve DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken Leakage from other appliances wat...

Page 35: ...control does not energize the blower replace the Intelli Vent control If the blower fails to Blower may run continuously in start when energized replace the blower assembly this condition 2 Ensure the...

Page 36: ...ff for 10 20 seconds then on again to clear this error code 4 Ensure the flame sensor is clean use ultra fine steel wool or Scotch Brite pad to clean flame sensor 5 Ensure the hot surface ignitor is p...

Page 37: ...in tolerance 1 Ensure air pressure switch hose is not kinked or clogged ensure the blower housing is clear of any condensation 2 Check vent temperature limit switch if it is determined that the vent t...

Page 38: ...38 These guidelines should be utilized by a qualified service agent TROUBLESHOOTING GUIDELINES TROUBLESHOOTING GUIDELINES...

Page 39: ...installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited warranty the warrantor will...

Page 40: ...www statewaterheaters com 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 365 0024 Parts 800 821 2017...

Reviews: