c. Alarm Test Module PN 830002
The Field Test Alarm Module provides the ability to field load test actuation circuits using
a resettable device. The Alarm Module is installed in the actuation circuitry and provides
a simulated Stat-X generator without the danger of false discharge. The Alarm Module
gives the system installer the ability to place a resettable simulator in place while
installing and commissioning a system. The Alarm Module also provides the field service
technician the ability to “live test” the SDRP panel and detection circuitry. When a
detection circuit “closes” in Alarm, the Alarm Module senses the electrical load and
simulates a system actuation. A red LED in the Alarm Module verifies an actuation signal
was sent by the SDRP panel. When the Alarm condition (detection circuit closure) is
repaired or reset, the push to reset button on the front of the Alarm Module is used to
clear the alarm condition. Multiple Alarm Modules may be used to verify the operation of
separate actuation circuits
Figure 7 - PN. 830002 Alarm Test
Module
Figure 8 - Alarm Test Module dimensions
The Alarm Module is polarized as positive #2, negative #1. The connector is a Deutsch
DTM06-2S connector which mates to a Deutsch DTM04-2P at the SDRP Actuation
Cable.