Do not route field wiring over objects which may damage the wiring due to vibration, high
temperature, or sharp edges or corners.
-
Add drip loops as needed
Figure 1 - Drip Loop Example (use for detectors and generators as needed)
Stat-X Generator Location and Operation
-
Stat-X generators must be securely mounted and aimed per the Hazard Analysis.
-
Field wiring from the SDRP to each generator may be wired in series or in parallel.
-
Only two generators may be wired to each actuation zone.
-
Ensure the wiring connection from the SDRP field wiring to each generator is tight, clean
and environmentally sealed. Corrosion and poor electrical connections will add electrical
resistance to the actuation circuit. Clean and tight electrical connections reduce the
opportunity for problems.