h. Detection Zone Field Wiring
Field wiring used to connect between the SDRP and each spot thermal detector must be at
a minimum UL Listed Plenum wire, 18 awg. Parallel field wiring is used between detectors.
Detection field wiring must be protected in emt/conduit between each detector.
A terminal strip connection may be used if the connection is made inside of a
watertight/mechanically protected housing or enclosure.