i. Actuation Zone Field Wiring
Figure 14 - Sample Actuation Circuit Wiring
•
Field wiring used to connect between the SDRP and each Stat-X generator must be at a
minimum UL Listed Plenum wire, 18 awg. series field wiring is used between generators
which is easily supervised by the SDRP. Parallel field wiring is acceptable but must be
protected in emt/conduit as individual Stat-X generators are not supervised by the
SDRP.
•
Wiring connections must be secure to deliver electrical energy to each Stat-X generator.
The ideal connection is a soldered connection using a no clean, non-corrosive solder,
and flux. Wire surfaces must be clean prior to soldering.
•
A terminal strip connection may be used if the connection is made inside of a
watertight/mechanically protected housing or enclosure.