Stat-X SDRP Installation, Operation And Owner'S Manual Download Page 1

 

 

 

 

Stat-X

®

 Dual Release Panel  

(SDRP) 

 

 

Installation, Operation, 

and Owner’s Manual 

 
 
 

 

 

 

Summary of Contents for SDRP

Page 1: ...Stat X Dual Release Panel SDRP Installation Operation and Owner s Manual...

Page 2: ...erview 3 Component Description a Control Panel b Cable Harness c Alarm Test Module d Detection Wiring e Actuation Wiring 4 System Design and Installation 5 Inspection and Maintenance 6 System Alarms a...

Page 3: ...t aluminum enclosure surrounds the military qualified electronic components The SDRP provides electrical supervision of fire detection release manual activation as well as battery condition The SDRP i...

Page 4: ...rom the elements it s always good practice to keep electronics away from water oil and other conductive materials Ensure the SDRP is not located in the hazard area and is protected in some manner agai...

Page 5: ...ion and Operation Stat X generators must be securely mounted and aimed per the Hazard Analysis Field wiring from the SDRP to each generator may be wired in series or in parallel Only two generators ma...

Page 6: ...igure 2 SDRP Controls and Indications Figure 3 SDRP Labeling The SDRP panel includes two detection zones and two releasing zones The SDRP can be ordered in one of two programming configurations Serial...

Page 7: ...Input Switch will also actuate both actuation zones PN 830001 01 Dual Detection Zones and Dual Releasing Zones Each detection zone will actuate individual separate actuation zones A single dedicated...

Page 8: ...s use color coded ty wraps along with labels which indicate the cable wire function Note It s important to note that while the Stat X generators are not polarized the Alarm Test Module PN 830002 which...

Page 9: ...he ability to live test the SDRP panel and detection circuitry When a detection circuit closes in Alarm the Alarm Module senses the electrical load and simulates a system actuation A red LED in the Al...

Page 10: ...roven MIL 26482 metal shell connector to link the manual switch to the SDRP panel manual release input circuit The normally open toggle switch used with the Manual Release Switch is protected by a lab...

Page 11: ...n End of Line device completing a loop back to the SDRP If a Fire occurs the outer and inner insulating jackets of the linear thermal wire melt allowing the individual conductors of the linear thermal...

Page 12: ...gh an end of line device completing a loop back to the SDRP If a fire occurs the normally open contacts in the spot thermal close This change in electrical resistance is interpreted by the SDRP as a f...

Page 13: ...The end of line device EOL PN 830007 provides a series resistance of 470k ohms The EOL consists of a two position Deutsch connector with an over molded 470k ohm resistor The EOL provides a high resist...

Page 14: ...he SDRP and each spot thermal detector must be at a minimum UL Listed Plenum wire 18 awg Parallel field wiring is used between detectors Detection field wiring must be protected in emt conduit between...

Page 15: ...s easily supervised by the SDRP Parallel field wiring is acceptable but must be protected in emt conduit as individual Stat X generators are not supervised by the SDRP Wiring connections must be secur...

Page 16: ...k Manual Release Switch for any damage or other changes Annual Inspection 1 Before performing any detection circuit tests attach alarm module PN 830002 to both SDRP actuation circuits 2 Flip the test...

Page 17: ...ly use our PN 830009 as a replacement 1 See figures 10 11 below 2 Remove panel from mounting position 3 Remove pull pin and flip toggle switch to Disable System position 4 Replace pull pin 5 Disconnec...

Page 18: ...Fireaway Inc Version 1 5852 Baker Road 10 2017 Minnetonka MN 55345 P N 19112 18 Figure 16 SDRP battery replacement data to be completed annually when batteries are replaced...

Page 19: ...nt Panel Display System OK Green LED ON System Trouble Yellow LED OFF Indicates Status Detection Field Wiring Continuous circuit with correct resistance Actuation Field Wiring Continuous circuit with...

Page 20: ...generator to field wiring connection is intact Check for corrosion at Stat X generator to field wiring connection Check actuation circuit for any breaks or damage Verify Stat X generator has not disc...

Page 21: ...F Type XCR 830025 xxx Linear Thermal Wire 135o F Type XLT 8 Miscellaneous Notes a Battery Storage STORAGE Store in a cool regulated preferably below 21 C and in any case below 30 C dry and ventilated...

Page 22: ...t thereof which proves to be defective in workmanship or material for a period of eighteen 18 months from the date of first shipment from our factory Defective units should be returned shipment prepai...