Hazardous voltage. Can
shock, burn, or cause
death.
BEFORE WORKING
ON PUMP OR
MOTOR:
Unplug pump motor.
ELECTRICAL
All wiring must be done by a licensed electrician and must conform to all local and
national codes and regulations.
Ground and bond motor before connecting to electrical power supply. Failure to ground
and bond pump motor can cause serious or fatal electrical shock hazard.
Do NOT ground to a gas supply line.
To avoid dangerous or fatal electrical shock, turn OFF power to motor before working on
electrical connections.
Ground Fault Circuit Interrupter (GFCI) tripping indicates electrical problem. If GFCI trips
and won’t reset, consult electrician to inspect and repair electrical system.
Fire Hazard. Match supply voltage to motor nameplate voltage.
Ensure that the electrical supply available agrees with the motor’s voltage, phase, and cycle, and that the wire
size is adequate for the HP (kW) rating and distance from the power source.
NOTE - All electrical wiring
MUST be performed by a licensed electrician, and MUST conform to local codes and NEC regulations.
Use copper conductors only.
ELECTRICAL GUIDE - 60 CYCLE - SINGLE PHASE
MOTOR
VOLTS
CIRCUIT
BREAKER
RATINGS-AMPS
BRANCH
FUSETRON
RATINGS-AMPS
RECOMMENDED
WIRE SIZE 0-50’
KW
HP
.37
1/2
115
15
15
No. 14
.55
3/4
115
230
15
10
15
6.25
No. 14
.75
1
115
230
20
10
20
9
No. 12
No. 14
1.1
1 1/2
115
230
30
15
30
15
No. 10
No. 14
1.55
2
115
230
30
15
30
12
No. 10
No. 14
1.88
2 1/2
230
20
20
No. 12