Operating and service manual
48 of 222 pages
Configuration:
F01 Container ID viewing (Container)
Function:
Viewing of container ID.
Value:
Shown in the lower display line. E.g. MCID 000 001 2
F02 Software version viewing (Software version)
Function:
Viewing of software version and revision
Value:
-
F03 Compressor FC type setting (FC type)
Function:
Setting of actual FC type.
Value:
Setting as DANFOSS for Danfoss VLT
and NONE for no FC mounted (see
“Emergency Opera-
tion” p. 50
, for specific information).
F04 Compressor frequency converter ID (FC ID)
Function:
Viewing of ID for FC for compressor.
Value:
-
F05 Setting of phase direction (Phase direction)
Function:
Setting of phase direction.
Value:
Is only possible when AL423 is active.
Default setting is Auto for automatic phase detection – automatically selected when the unit has
been switched off for more than 30 min. before switching it on again.
Can be used for manual phase setting: Setting as CW for clockwise rotation or CCW for counter-
clockwise rotation.
If manual phase direction is set, heat is reduced to 60% of max.
F06 Calibration of AirExchange sensor (AirEx calibration)
Function:
Zero adjust of AirExchange sensor when the air inlet is closed
Value:
Actual value of sensor is set to zero when enter key,
, is pressed.
F07 Type of low pressure transmitter (Low pres type)
Function:
Set the pressure transmitter that is physically mounted for low pressure measurement. Press En-
ter for 3 sec. to make the selection.
Value:
AKS for Danfoss pressure transmitter, NSK for SAGInoMIYA pressure transmitter.
F08 Type of high pressure transmitter (High pres type)
Function:
Set the pressure transmitter that is physically mounted for high pressure measurement. Press
Enter for 3 sec. to make the selection.
Value:
AKS for Danfoss pressure transmitter, NSK for SAGInoMIYA pressure transmitter.