Operating and service manual
Air exchange Sensor table Voltage - m3/h
There is an offset of 0.2 V due to mechanical design. The air exchange must be properly calibrated
before measuring.
Voltage
[V]
Air exchange
[m3/h]
Voltage
[V]
Air exchange
[m3/h]
Voltage
[V]
Air exchange
[m3/h]
Voltage
[V]
Air exchange
[m3/h]
0.20
0
1.45
60
2.25
120
3.35
180
0.30
5
1.50
65
2.35
125
3.40
185
0.50
10
1.55
70
2.40
130
3.50
190
0.65
15
1.65
75
2.50
135
3.60
195
0.80
20
1.70
80
2.55
140
3.65
200
0.85
25
1.75
85
2.65
145
3.80
205
0.95
30
1.90
90
2.70
150
3.85
210
1.05
35
1.95
95
2.80
155
3.95
215
1.15
40
2.00
100
2.90
160
4.00
220
1.20
45
2.05
105
3.00
165
1.30
50
2.10
110
3.10
170
1.35
55
2.20
115
3.20
175
Relative Humidity Sensor table %RH - Voltage
Relative humidity [%]
Voltage [V]
0
0
10
1
20
2
30
3
40
4
50
5
60
6
70
7
80
8
90
9
100
10