background image

11

Fig.10

WARM AIR DUCTING SYSTEM

This appliance can be fitted to a Warm Air Ducting
System that will allow to distribute warm air to ele-
vated positions within the room or other parts of the
building.

All duct runs must always rise from the appliance
and be as straight as possible, with the minimum of
bends to ensure a good airflow. All ducts should be
suitably supported along the full length. 

If the appliance is installed in a property with a gas
appliance fitted consideration should be given to the
ventilation air requirements of the gas appliance,
and an assessment made by a suitably trained and
appropriately qualified gas engineer.

Ducts must not be connected to areas designated as
a protected stairway as defined by the Local Building
Regulations.

Where ducts pass through walls or ceilings they
must be adequately supported and the space
around them filled with suitable non-combustible
filler.

It is recommended to fit a CO alarm in the area
where the ducts exit in addition to the one required
to be placed in the room with the appliance.

POSITIONING OF THE WARM AIR DUCT

The following must be adhered to when locating the
warm air duct system:
*

The air duct must not touch any combustible
materials within 550mm of the back of the
appliance.

*

Take care when routing the duct to ensure it
is not deformed and restricting the airflow.

*

Due to the possible high temperature of the
ducts, combustible material must be placed 
no closer than 100mm to the surface. The 
duct exits and grills must only be placed in a 
non-combustible wall panel.

*

Protect or place the exit ducts at a high level, 
as the grill surfaces can become very hot
when in use.

*

Use a suitable guard if the exit is at low level
to prevent touching or obstruction. 

*

Do not place combustible items near the 
operating duct exit.

FITTING THE WARM AIR DUCTS TO STOVE

1.

Remove the cover plates on the top of the 
firebox.

2.

Fit the warm air duct spigots to the top of the 
firebox using self tapping screws (see Fig
11).

3.

Position the vents as advised in the previous 
section.

4.

Fit the flexible pipe to the spigots & vents and
secure with the clamp bands.

Fig.11

WARM AIR DUCT SPIGOTS

600

600

Summary of Contents for Solis 80cm Single Sided Insert I80SS

Page 1: ...should be supervised at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thoroughly cooled When using the stove in situations where childr...

Page 2: ...arm Air Ducting System 11 18 Position of Warm Air Duct 11 19 Fitting the Warm Air Duct to the Stove 11 20 Stove Dimensions 12 21 Commissioning and Handover 12 22 Operation 12 23 Air Controls 13 24 Fan...

Page 3: ...requirements of the manual Failure to comply with the Installation Requirements or Building Regulations will void your warranty Waterford Stanley reserve the right to replace any part due to manufactu...

Page 4: ...d be provided to the chimney serving the appliance to allow for cleaning This can be done through the stove 9 It is a requirement by Building Regulations to have a carbon monoxide alarm fitted to any...

Page 5: ...ensure that there are no blockages Check flue ways before lighting especially after a shut down period Please see chimney cleaning section 5 Never allow a build up of ashes in the ash pan as this wil...

Page 6: ...cations may be superseded during the life of this manual Please refer to the current standards BS EN 15287 1 2007 Design Installation and Commissioning of chimneys BS EN 14336 2004 Heating Systems in...

Page 7: ...wind effects a basic guide is that the distance from the termination to the roof should be at least 2300mm when measured horizontally and at least 1000mm when measured vertically see Fig 1 In circumst...

Page 8: ...ver the terminal A suitable terminal or cowl will usually effectively combat direct down blow but no cowl is likely to pre vent down draught due to a low pressure zone See Fig 7 Fig 7 Direction of win...

Page 9: ...ld be of the correct size and unob structed for the appliance in use If there is an extraction fan fitted in adjacent rooms where this appliance is fitted additional air vents may be required to allev...

Page 10: ...e adhere to Clearance to Combustible Section Fig 8 3 ID ALUMINIUM FLEXIBLE DUCT PIPE ENDS TO BE COVERED WITH MESH 3 OD CONNECTOR SADDLE Fig 9 600mm 600mm HEAT RECOVERY VENTILATION Where a stove is to...

Page 11: ...xit in addition to the one required to be placed in the room with the appliance POSITIONING OF THE WARM AIR DUCT The following must be adhered to when locating the warm air duct system The air duct mu...

Page 12: ...t with the customer Ensure to advise the cus tomer on the correct use of the appliance and warn them to use only Wood Advise the user what to do should smoke or fumes be emitted from the stove The cus...

Page 13: ...n the lower casing of the stove has reached 50 degrees C in order to protect the electric components When the warm air ducting system is connected the air vents above the firedoor can be closed off us...

Page 14: ...ndover the installer should demonstrate how to operate the stove correctly LIGHTING THE STOVE 1 Open the fire door and open the primary secondary air inlets by pushing the two air control levers to th...

Page 15: ...ould be placed on a non combustible material pending final disposal If ashes are buried in soil or otherwise dumped they should be retained in the closed container until they are thoroughly cooled Ope...

Page 16: ...r a prolonged peri od of time then it should be given a thorough clean to remove ash and unburned fuel residues To enable a good flow of air through the appliance to reduce condensation and subsequent...

Page 17: ...pulsory requirement under cur rent Building Regulations For ROI an additional CO Alarm must be fitted either inside each bedroom or within 5 metres of the bedroom door refer to Building Regulations Pa...

Page 18: ...18 ELECTRICAL DIAGRAM...

Page 19: ...SPIGOT E2026 10 WARM AIR DUCT SPIGOT E2025 11 GLASS FIXING BRACKET JUN100 JUN80 12 GLASS 20CRC100DEK 20CRC80DEK 13 FIRE DOOR PTAKR100 PTAKR80 NO DESCRIPTION PART CODE I100DS I80DS 14 DOOR ROPE SEAL CO...

Page 20: ...20 Manufactured by Waterford Stanley Ltd Unit 401 403 IDA Industrial Estate Cork Road Waterford Ireland Tel 051 302300 Fax 051 302315 N00777AXX Rev 001 SG 210518...

Reviews: