background image

LOCATION

There are several conditions to be considered in
selecting a location for your Solis stove.

a.

Position in the area to be heated, central 
locations are usually best.

b.

Allowances for proper clearances to 
combustibles.

c.

Allowances for proper clearances for mainte-
nance work.

CLEARANCES TO COMBUSTIBLES

This appliance must be installed in a recess and the
recess should not contain any combustible material.
Wood battens and plaster board should not be used
within the clearance to combustibles. The minimum
clearance to combustibles required is as follows:

From the Top

400mm

From the Sides

600mm

From the Front/Back

1400mm

Combustible Front - Floor Level

225mm

Combustible Side

600mm

10

Note:  When Installing
outside air pipe adhere
to ‘Clearance to
Combustible’ Section.

Fig.8

3” ID ALUMINIUM 
FLEXIBLE DUCT

PIPE ENDS TO BE 
COVERED WITH MESH

3” OD CONNECTOR SADDLE 

Fig.9

600mm

600mm

HEAT RECOVERY VENTILATION

Where a stove is to be installed in a dwelling with

Heat Recovery Ventilation

(HRV) a number of pre-

cautionary measures must be undertaken:

Where the product is to be installed with a
Mechanical Ventilation, the stove must be connect-
ed to an external air supply, The ductwork for the
external air supply must be no longer than 6 metres
and the air inlet terminal to the ductwork must have
a cross sectional area of at least 80cm

2

.

FLOOR PROTECTION

It is recommended that the appliance is installed on
a solid, level, concrete base of non combustible
hearth conforming to the current Building
Regulations and must extend 225mm in front of the
appliance. This will provide protection from sparks
and embers which may fall out when stoking on refu-
elling.

Summary of Contents for Solis 80cm Single Sided Insert I80SS

Page 1: ...should be supervised at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thoroughly cooled When using the stove in situations where childr...

Page 2: ...arm Air Ducting System 11 18 Position of Warm Air Duct 11 19 Fitting the Warm Air Duct to the Stove 11 20 Stove Dimensions 12 21 Commissioning and Handover 12 22 Operation 12 23 Air Controls 13 24 Fan...

Page 3: ...requirements of the manual Failure to comply with the Installation Requirements or Building Regulations will void your warranty Waterford Stanley reserve the right to replace any part due to manufactu...

Page 4: ...d be provided to the chimney serving the appliance to allow for cleaning This can be done through the stove 9 It is a requirement by Building Regulations to have a carbon monoxide alarm fitted to any...

Page 5: ...ensure that there are no blockages Check flue ways before lighting especially after a shut down period Please see chimney cleaning section 5 Never allow a build up of ashes in the ash pan as this wil...

Page 6: ...cations may be superseded during the life of this manual Please refer to the current standards BS EN 15287 1 2007 Design Installation and Commissioning of chimneys BS EN 14336 2004 Heating Systems in...

Page 7: ...wind effects a basic guide is that the distance from the termination to the roof should be at least 2300mm when measured horizontally and at least 1000mm when measured vertically see Fig 1 In circumst...

Page 8: ...ver the terminal A suitable terminal or cowl will usually effectively combat direct down blow but no cowl is likely to pre vent down draught due to a low pressure zone See Fig 7 Fig 7 Direction of win...

Page 9: ...ld be of the correct size and unob structed for the appliance in use If there is an extraction fan fitted in adjacent rooms where this appliance is fitted additional air vents may be required to allev...

Page 10: ...e adhere to Clearance to Combustible Section Fig 8 3 ID ALUMINIUM FLEXIBLE DUCT PIPE ENDS TO BE COVERED WITH MESH 3 OD CONNECTOR SADDLE Fig 9 600mm 600mm HEAT RECOVERY VENTILATION Where a stove is to...

Page 11: ...xit in addition to the one required to be placed in the room with the appliance POSITIONING OF THE WARM AIR DUCT The following must be adhered to when locating the warm air duct system The air duct mu...

Page 12: ...t with the customer Ensure to advise the cus tomer on the correct use of the appliance and warn them to use only Wood Advise the user what to do should smoke or fumes be emitted from the stove The cus...

Page 13: ...n the lower casing of the stove has reached 50 degrees C in order to protect the electric components When the warm air ducting system is connected the air vents above the firedoor can be closed off us...

Page 14: ...ndover the installer should demonstrate how to operate the stove correctly LIGHTING THE STOVE 1 Open the fire door and open the primary secondary air inlets by pushing the two air control levers to th...

Page 15: ...ould be placed on a non combustible material pending final disposal If ashes are buried in soil or otherwise dumped they should be retained in the closed container until they are thoroughly cooled Ope...

Page 16: ...r a prolonged peri od of time then it should be given a thorough clean to remove ash and unburned fuel residues To enable a good flow of air through the appliance to reduce condensation and subsequent...

Page 17: ...pulsory requirement under cur rent Building Regulations For ROI an additional CO Alarm must be fitted either inside each bedroom or within 5 metres of the bedroom door refer to Building Regulations Pa...

Page 18: ...18 ELECTRICAL DIAGRAM...

Page 19: ...SPIGOT E2026 10 WARM AIR DUCT SPIGOT E2025 11 GLASS FIXING BRACKET JUN100 JUN80 12 GLASS 20CRC100DEK 20CRC80DEK 13 FIRE DOOR PTAKR100 PTAKR80 NO DESCRIPTION PART CODE I100DS I80DS 14 DOOR ROPE SEAL CO...

Page 20: ...20 Manufactured by Waterford Stanley Ltd Unit 401 403 IDA Industrial Estate Cork Road Waterford Ireland Tel 051 302300 Fax 051 302315 N00777AXX Rev 001 SG 210518...

Reviews: