background image

16

CHIMNEY CLEANING

The chimney should be cleaned twice annually or if
the stove is not used for a prolonged period during
the summer period, it should be cleaned prior to
commencement of usage. The chimney can be
cleaned through the stove depending on the flue
configuration and the flue liner should be cleaned in
accordance with manufacturer's instructions. Always
use a brush with plastic bristles that is the correct
size to reach all areas of the flue.

GLASS CLEANING

The stove glass will self-clean when there is suffi-
cient heat generated by the burning fuel i.e. when
the unit is operated at the maximum air settings. If a
build-up of creosote occurs on the glass it may be
due to low draft conditions, poor quality fuel or oper-
ating the stove at the minimum air settings for long
periods of time. The glass should be cleaned when
cool and cleaned with a non-abrasive cloth using
warm soapy water. For stubborn deposits, a grade 0
steel wool can be used whilst taking care not to
scratch the glass with any coal/ash deposits.

CLEANING A MATT BLACK/SENOTHERM
STOVE

Cleaning should be done when the stove is cold by
removing any dust or dirt using a dry cloth. Do not
use any water on the matt black/senotherm finish as
this will cause it to rust.

PROLONGED PERIODS OF NON USE

If the stove is to be left unused for a prolonged peri-
od of time then it should be given a thorough clean
to remove ash and unburned fuel residues. To
enable a good flow of air through the appliance to
reduce condensation and subsequent damage,
leave the air controls fully open.

It is important that the flue connection, any appliance
baffles or throat plates and the chimney are swept
prior to lighting up after a prolonged shutdown peri-
od.

WARNING NOTE:

Properly installed, operated and maintained this
stove will not emit fumes into the dwelling.
Occasional fumes from the de-ashing and re-
fuelling may occur. However, persistent fume emis-
sion is potentially dangerous and must not be toler-
ated. If fume emission does persist, then the follow-
ing immediate action should be taken:

(a) Open doors and windows to ventilate room.

(b) Let the fire out or eject and safely dispose of 

fuel from the stove.

(c)  Check for flue or chimney blockage and clean if

required.

(d)  Do not attempt to relight the fire until the cause

of the fume emission has been identified and 
corrected.  If necessary seek expert advice.

The most common cause of fume emission is flue-
way or chimney blockage. For you own safety these
must be kept clean at all times.

PERIODIC MAINTENANCE

Rope Seal Replacement

Over time, the fire door latch can loosen due to the
continued compression and hardening of the seal
between the door and the front frame.
It is recommended that the rope seals are changed
at least every two years or sooner if the seal looses
its integrity. 

Fig.18

Fig.19

TOP BAFFLE

CLIPS

Summary of Contents for Solis 80cm Single Sided Insert I80SS

Page 1: ...should be supervised at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thoroughly cooled When using the stove in situations where childr...

Page 2: ...arm Air Ducting System 11 18 Position of Warm Air Duct 11 19 Fitting the Warm Air Duct to the Stove 11 20 Stove Dimensions 12 21 Commissioning and Handover 12 22 Operation 12 23 Air Controls 13 24 Fan...

Page 3: ...requirements of the manual Failure to comply with the Installation Requirements or Building Regulations will void your warranty Waterford Stanley reserve the right to replace any part due to manufactu...

Page 4: ...d be provided to the chimney serving the appliance to allow for cleaning This can be done through the stove 9 It is a requirement by Building Regulations to have a carbon monoxide alarm fitted to any...

Page 5: ...ensure that there are no blockages Check flue ways before lighting especially after a shut down period Please see chimney cleaning section 5 Never allow a build up of ashes in the ash pan as this wil...

Page 6: ...cations may be superseded during the life of this manual Please refer to the current standards BS EN 15287 1 2007 Design Installation and Commissioning of chimneys BS EN 14336 2004 Heating Systems in...

Page 7: ...wind effects a basic guide is that the distance from the termination to the roof should be at least 2300mm when measured horizontally and at least 1000mm when measured vertically see Fig 1 In circumst...

Page 8: ...ver the terminal A suitable terminal or cowl will usually effectively combat direct down blow but no cowl is likely to pre vent down draught due to a low pressure zone See Fig 7 Fig 7 Direction of win...

Page 9: ...ld be of the correct size and unob structed for the appliance in use If there is an extraction fan fitted in adjacent rooms where this appliance is fitted additional air vents may be required to allev...

Page 10: ...e adhere to Clearance to Combustible Section Fig 8 3 ID ALUMINIUM FLEXIBLE DUCT PIPE ENDS TO BE COVERED WITH MESH 3 OD CONNECTOR SADDLE Fig 9 600mm 600mm HEAT RECOVERY VENTILATION Where a stove is to...

Page 11: ...xit in addition to the one required to be placed in the room with the appliance POSITIONING OF THE WARM AIR DUCT The following must be adhered to when locating the warm air duct system The air duct mu...

Page 12: ...t with the customer Ensure to advise the cus tomer on the correct use of the appliance and warn them to use only Wood Advise the user what to do should smoke or fumes be emitted from the stove The cus...

Page 13: ...n the lower casing of the stove has reached 50 degrees C in order to protect the electric components When the warm air ducting system is connected the air vents above the firedoor can be closed off us...

Page 14: ...ndover the installer should demonstrate how to operate the stove correctly LIGHTING THE STOVE 1 Open the fire door and open the primary secondary air inlets by pushing the two air control levers to th...

Page 15: ...ould be placed on a non combustible material pending final disposal If ashes are buried in soil or otherwise dumped they should be retained in the closed container until they are thoroughly cooled Ope...

Page 16: ...r a prolonged peri od of time then it should be given a thorough clean to remove ash and unburned fuel residues To enable a good flow of air through the appliance to reduce condensation and subsequent...

Page 17: ...pulsory requirement under cur rent Building Regulations For ROI an additional CO Alarm must be fitted either inside each bedroom or within 5 metres of the bedroom door refer to Building Regulations Pa...

Page 18: ...18 ELECTRICAL DIAGRAM...

Page 19: ...SPIGOT E2026 10 WARM AIR DUCT SPIGOT E2025 11 GLASS FIXING BRACKET JUN100 JUN80 12 GLASS 20CRC100DEK 20CRC80DEK 13 FIRE DOOR PTAKR100 PTAKR80 NO DESCRIPTION PART CODE I100DS I80DS 14 DOOR ROPE SEAL CO...

Page 20: ...20 Manufactured by Waterford Stanley Ltd Unit 401 403 IDA Industrial Estate Cork Road Waterford Ireland Tel 051 302300 Fax 051 302315 N00777AXX Rev 001 SG 210518...

Reviews: