background image

INSTALLATION & OPERATING INSTRUCTIONS

GENERAL

When installing, operating and maintaining your
Solis stove, respect basic standards of fire safety.
Read these instructions carefully before commenc-
ing the installation.  Failure to do so may result in
damage to persons and property.  Consult your local
Municipal office and your insurance representative
to determine what regulations are in force.  Save
these instructions for future reference.

Please note that it is a legal requirement under
England & Wales Building Regulations that the
installation of the stove is either carried out under
Local Authority Building Control approval or is
installed by a Competent Person registered with a
Government approved Competent Persons
Scheme.  HETAS Ltd operate such a scheme and a
listing of their Registered Competent Persons can
be found on their website at www.hetas.co.uk.

Special care must be taken when installing the stove
such that the requirements of the Health & Safety at
Work Act are met.

Handling

Adequate facilities must be available for loading,
unloading and site handling.  

Fire Cement

Some types of fire cement are caustic and should
not be allowed to come into contact with the skin. In
case of contact with the skin wash immediately with
plenty of water.

Asbestos

This stove contains no asbestos.  If there is a possi-
bility of disturbing any asbestos in the course of
installation then please seek specialist guidance and
use appropriate protective equipment.

Metal Parts

When installing or servicing this stove care should
be taken to avoid the possibility of personal injury.

“IMPORTANT WARNING”

This stove must not be installed into a chimney that
serves any other heating appliance.

6

The complete installation must be done in accor-
dance with current Standards and Local Codes.  It
should be noted that the requirements and these
publications may be superseded during the life of
this manual.

Please refer to the current standards, BS EN 15287-
1:2007 Design, Installation and Commissioning of
chimneys.  BS EN 14336:2004: Heating Systems in
Buildings.  Installation & Commissioning of Water
Based Heating Systems.  BS EN 12828: 2003;
Heating Systems in Buildings.  Design of Water
Based Heating Systems.  BS EN 12831: 2003;
Heating Systems in Buildings.  method for 
calculation of the design heat load.

Your Solis stove is supplied with the following items:

Ashpan  

Glove

Operating Tool

External Air Connection

Warm Air Duct Spigot x 2

Glass Frames x 2

Flue Adaptor

Fan Switch Cut-Out Blank

FLUES

Flues should be vertical wherever possible and
where a bend is necessary, it should not make an
angle of more than 45

o

with the vertical.  Horizontal

flue runs should be avoided in order to minimise flue
resistance and to make sweeping easier it is recom-
mended to use 2 x 45

o

bends rather than a 90

o

bend.

ELECTRICAL SUPPLY 

All wiring external to the appliance must conform to
the current BS 7671 (UK) BS 7462 Safety Document
635: ETC Part 1, Section 5.4.6 and The Electricity at
Work Regulations.
This unit requires a 220V-240V 50L/2 supply con-
nection of the appliance and any system controls to
the mains supply must be through a fused double
pole switch having contact seperation of at least
3mm with a fuse rated at 3 amp and located in a
readily accessible position close to the appliance.
Connection should be made through the cable sup-
plied and if required the cable must only be extend-
ed/ replaced with a similar sized cable that is silicon-
coated and heat resistant to 180

o

C (365

o

F).

CHIMNEY

Do not connect to a chimney serving another
appliance.

The stove is a radiant room heater and must be con-
nected to a chimney of the proper size and type.
The chimney must have a cross-sectional area of at
least 28 square inches 17660sq. mm or a diameter
of at least 6” (150mm). It is best to connect to a
chimney of the same size, as connection to a larger
size may result in a somewhat less draught.  

Summary of Contents for Solis 80cm Single Sided Insert I80SS

Page 1: ...should be supervised at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thoroughly cooled When using the stove in situations where childr...

Page 2: ...arm Air Ducting System 11 18 Position of Warm Air Duct 11 19 Fitting the Warm Air Duct to the Stove 11 20 Stove Dimensions 12 21 Commissioning and Handover 12 22 Operation 12 23 Air Controls 13 24 Fan...

Page 3: ...requirements of the manual Failure to comply with the Installation Requirements or Building Regulations will void your warranty Waterford Stanley reserve the right to replace any part due to manufactu...

Page 4: ...d be provided to the chimney serving the appliance to allow for cleaning This can be done through the stove 9 It is a requirement by Building Regulations to have a carbon monoxide alarm fitted to any...

Page 5: ...ensure that there are no blockages Check flue ways before lighting especially after a shut down period Please see chimney cleaning section 5 Never allow a build up of ashes in the ash pan as this wil...

Page 6: ...cations may be superseded during the life of this manual Please refer to the current standards BS EN 15287 1 2007 Design Installation and Commissioning of chimneys BS EN 14336 2004 Heating Systems in...

Page 7: ...wind effects a basic guide is that the distance from the termination to the roof should be at least 2300mm when measured horizontally and at least 1000mm when measured vertically see Fig 1 In circumst...

Page 8: ...ver the terminal A suitable terminal or cowl will usually effectively combat direct down blow but no cowl is likely to pre vent down draught due to a low pressure zone See Fig 7 Fig 7 Direction of win...

Page 9: ...ld be of the correct size and unob structed for the appliance in use If there is an extraction fan fitted in adjacent rooms where this appliance is fitted additional air vents may be required to allev...

Page 10: ...e adhere to Clearance to Combustible Section Fig 8 3 ID ALUMINIUM FLEXIBLE DUCT PIPE ENDS TO BE COVERED WITH MESH 3 OD CONNECTOR SADDLE Fig 9 600mm 600mm HEAT RECOVERY VENTILATION Where a stove is to...

Page 11: ...xit in addition to the one required to be placed in the room with the appliance POSITIONING OF THE WARM AIR DUCT The following must be adhered to when locating the warm air duct system The air duct mu...

Page 12: ...t with the customer Ensure to advise the cus tomer on the correct use of the appliance and warn them to use only Wood Advise the user what to do should smoke or fumes be emitted from the stove The cus...

Page 13: ...n the lower casing of the stove has reached 50 degrees C in order to protect the electric components When the warm air ducting system is connected the air vents above the firedoor can be closed off us...

Page 14: ...ndover the installer should demonstrate how to operate the stove correctly LIGHTING THE STOVE 1 Open the fire door and open the primary secondary air inlets by pushing the two air control levers to th...

Page 15: ...ould be placed on a non combustible material pending final disposal If ashes are buried in soil or otherwise dumped they should be retained in the closed container until they are thoroughly cooled Ope...

Page 16: ...r a prolonged peri od of time then it should be given a thorough clean to remove ash and unburned fuel residues To enable a good flow of air through the appliance to reduce condensation and subsequent...

Page 17: ...pulsory requirement under cur rent Building Regulations For ROI an additional CO Alarm must be fitted either inside each bedroom or within 5 metres of the bedroom door refer to Building Regulations Pa...

Page 18: ...18 ELECTRICAL DIAGRAM...

Page 19: ...SPIGOT E2026 10 WARM AIR DUCT SPIGOT E2025 11 GLASS FIXING BRACKET JUN100 JUN80 12 GLASS 20CRC100DEK 20CRC80DEK 13 FIRE DOOR PTAKR100 PTAKR80 NO DESCRIPTION PART CODE I100DS I80DS 14 DOOR ROPE SEAL CO...

Page 20: ...20 Manufactured by Waterford Stanley Ltd Unit 401 403 IDA Industrial Estate Cork Road Waterford Ireland Tel 051 302300 Fax 051 302315 N00777AXX Rev 001 SG 210518...

Reviews: