THE LISMORE SOLID FUEL CENTRAL HEATING STOVE

INSTALLATION & OPERATING INSTRUCTIONS

GENERAL

When installing, operating and maintaining your
Lismore Stove respect basic standards of fire safety.
Read these instructions carefully before commenc-
ing the installation.  Failure to do so may result in
damage to persons and property.  Consult your local
Municipal office and your insurance representative
to determine what regulations are in force.  Save
these instructions for future reference.

Please note that it is a legal requirement under
England & Wales Building Regulations that the
installation of the stove is either carried out under
Local Authority Building Control approval or is
installed by a Competent Person registered with a
Government approved Competent Persons
Scheme.  HETAS Ltd operate such a scheme and a
listing of their Registered Competent Persons can
be found on their website at www.hetas.co.uk.

Special care must be taken when installing the stove
such that the requirements of the Health & Safety at
Work Act are met.

Handling

Adequate facilities must be available for loading,
unloading and site handling.  

Fire Cement

Some types of fire cement are caustic and should
not be allowed to come into contact with the skin.  In
case of contact with the skin wash immediately with
plenty of water.

Asbestos

This stove contains no asbestos.  If there is a possi-
bility of disturbing any asbestos in the course of
installation then please seek specialist guidance and
use appropriate protective equipment.

Metal Parts

When installing or servicing this stove care should
be taken to avoid the possibility of personal injury.

“IMPORTANT WARNING”

This stove must not be installed into a chimney that
serves any other heating appliance.

7

The complete installation must be done in accor-
dance with current Standards and Local Codes.  It
should be noted that the requirements and these
publications may be superseded during the life of
this manual.

Please refer to the current standards, BS EN 15287-
1:2007 Design, Installation and Commissioning of
chimneys.  BS EN 14336:2004: Heating Systems in
Buildings.  Installation & Commissioning of Water
Based Heating Systems.  BS EN 12828: 2003;
Heating Systems in Buildings.  Design of Water
Based Heating Systems.  BS EN 12831: 2003;
Heating Systems in Buildings.  method for 
calculation of the design heat load.

ELECTRICAL CONNECTIONS

The installation of any electrical services during the
installation of this stove must be carried out by a 
registered competent electrician and in accordance
with the requirements of the latest issue of BS 7671.

FLUES

Flues should be vertical wherever possible and
where a bend is necessary, it should not make an
angle of more than 45

o

with the vertical.  Horizontal

flue runs should be avoided except in the case of a
back outlet from the appliance, when the length of
the horizontal section should not exceed 150mm.

CHIMNEY

Do not connect to a chimney serving another
appliance.

The stove is a radiant room heater and must be con-
nected to a chimney of the proper size and type.

The chimney must have a cross-sectional area of at
least 30 square inches 19350sq. mm or a diameter
of at least 6” (150mm).  It is best to connect to a
chimney of the same size, as connection to a larger
size may result in a somewhat less draught.  

A flue that has proved to be unsatisfactory, particu-
larly with regard to down draught should not be used
for venting this appliance until it has been examined
and any faults corrected.  An existing masonry chim-
ney should be inspected and if necessary repaired
by a competent mason or relined using an approved
lining system.

Your Lismore stove is supplied with the following
items:

Ashpan  

Operating Tool 

Touch-Up Paint (Enamel Only) 

Glove

Thermostat Knob 

Summary of Contents for Lismore

Page 1: ...should be supervised at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thoroughly cooled When using the boiler stove in situations where...

Page 2: ...bles 11 16 Floor Protection 11 17 Plumbing 11 18 Pipe Thermostat 11 19 Regulations 11 20 Gravity Circuit 11 21 Injector Tee 12 22 Water Circuit Temperature 12 23 Flue Water Pipe Locations 13 24 Stove...

Page 3: ...TABLE OF CONTENTS PAGE NO 43 Cleaning a Matt Black Senotherm Stove 18 44 Frozen System 18 45 Prolonged Periods of Non Use 19 46 Fire Safety 19 47 Glass Replacement 19 48 CO Alarm 19 49 Exploded View 2...

Page 4: ...ed as per the requirements of the manual Failure to comply with the Installation requirements or Building Regulations will void your warranty Waterford Stanley reserve the right to replace any part du...

Page 5: ...egulations to have a carbon monoxide alarm fitted to any room with a solid fuel appliance Location 10 Clearance to combustible materials must be adhered to as described in the Clearance to Combustible...

Page 6: ...llow a build up of ashes in the ash pan as this will cause the grate to burn out prematurely Empty the ashpan when refuelling 7 Avoid slow burning of damp or unseasoned fuel as this will result in tar...

Page 7: ...be done in accor dance with current Standards and Local Codes It should be noted that the requirements and these publications may be superseded during the life of this manual Please refer to the curr...

Page 8: ...uld be at be at least 2300mm when measured horizontally and at least 1000mm when measured vertically see Fig 1 In circumstances where there are adjoining buildings structures roof openings there are a...

Page 9: ...550mm per each kw of rated output above 5kw should be provided where a flue draught stabiliser is used the total free area shall be increased by 300mm for each kw of rated output 9 All materials used...

Page 10: ...duct approval covers this appliance when installed in accordance with the manufactur er s instructions and relevant standards As there is currently no standard for Ducted Combustion Air Supply this do...

Page 11: ...oking on refu elling See Fig 7 REGULATIONS The plumbing must be in accordance with all relevant regulations and practices It must include a gravity circuit with expansion pipe open to the atmosphere T...

Page 12: ...id condensation on the boiler and return piping Fitting a pipe thermo stat to the flow pipe of the gravity circuit and wiring it into the pump control will ensure rapid circulation of the hot water In...

Page 13: ...ly to be used on the stove and warn them to use only the recommended fuels for the stove Advise the user what to do should smoke or fumes be emitted from the stove The customer should be warned to use...

Page 14: ...e a stove provides 2kW to the room and 8kW to the boiler and if the thermostatic damper shuts down the air supply to provide 4kW to the boiler then the heat to room will decrease pro portionally to 1k...

Page 15: ...gs 1 BSP Max Water Pressure 2 Bar Efficiency 76 3 76 8 Model Energy Efficiency Class Heat Output to Room Heat Output to Water Energy Efficiency Index Preferred Fuel Nominal Heat Output Net Efficiency...

Page 16: ...18 The hex head bolt should now be re inserted in the alternative position which will lock the grate in the wood burning position See Fig 16 USER INSTRUCTIONS Riddling Rod Wood Setting Fig 16 Fig 17 C...

Page 17: ...the boiler cleaning plate The boiler cleaning plate can also be removed when cleaning the chimney if the flue pipe is fitted to the back outlet Fig 21 PERIODIC MAINTENANCE Adjusting the Door Catch Ove...

Page 18: ...possibility that the water system may be frozen do not attempt to light the stove until you are certain there is no ice in the system possibly causing a blockage VITREOUS ENAMEL CLEANING General clean...

Page 19: ...s and carefully remove the broken glass c Clean the glass recess in the door d Replace the sealing rope in the door if necessary e Tighten screws f Replace glass only with ceramic glass 5mm thick See...

Page 20: ...THERMOSTAT G00479AXX 22 BADGE GASKET P00107AXX 23 GLASS CLIP GASKET P00117AXX 24 GLASS T00101AXX 25 PULL ROD KNOB U00001AXX 26 AIR CONTROL KNOB U00006AXX 27 SECONDARY AIR CONTROL U00018AXX 28 DOOR HAN...

Page 21: ...NOTES 21...

Page 22: ...NOTES 22...

Page 23: ...NOTES 23...

Page 24: ...24 Manufactured by Waterford Stanley Ltd Unit 401 403 IDA Industrial Estate Cork Road Waterford Ireland Tel 051 302300 Fax 051 302315 Item No N00524AXX Rev 005 YS280717...

Reviews: