background image

10

HEAT RECOVERY VENTILATION

Where a stove is to be installed in a dwelling with

Heat Recovery Ventilation

(HRV) a number of

precautionary measures must be undertaken:

Should for example the delivery fan in the HRV unit
fail and the extraction fan in HRV fan continue to
run the HRV may create a pressure less than
atmospheric, this low pressure will effect the flue
pressure which is required to safely evacuate the
products of combustion from the stove.

1.

Fit an adequately sized vent in the room to pre-
vent pressure less than atmospheric occurring.
The size should be established by closing all 
windows and doors and then creating the 
possible failure situation.  Then open a window
in the room where the stove is fitted, slowly 
until the pressure reaches atmospheric.  The 
size of the window opening should be
measured and a vent of the corresponding size
installed.

2.

Fit a CO Alarm which has been approved to 
EN 50291.

EXTERNAL DUCTED AIR

Where required the primary air supply can be 
ducted from outside.  An aluminium flexible duct is
available to order for connection to the stove.

It is recommended to bring the air supply for the
stove into the house using a 4” plastic pipe.  Where
the pipe meets the outside wall make sure a vent
cover is fitted properly to ensure no rodents can
enter via the vent pipe.  

The vent pipe should be located to prevent the
ingress of moisture and in a location where it will not
get blocked with leaves or any other debris.  

Fig.6

Note:  When Installing
outside air pipe adhere
to ‘Clearance to
Combustible’ Section.

‘HETAS product approval covers this appliance
when installed in accordance with the manufactur-
er’s instructions and relevant standards. As there is
currently no standard for Ducted Combustion Air
Supply this does not fall within the remit for HETAS
product approval. Responsibility for the specification
of this and for appropriate manufacturer’s instruc-
tions is carried by the appliance manufacturer, as
allowed for under the Building Regulations.’

Where such an installation exists, a test for spillage
should be made with the fan or fans and other appli-
ances using air in operation at full rate, (i.e.extraction
fans, tumble dryers) with all external doors and win-
dows closed. 

If spillage occurs following the above operation, an
additional air vent of sufficient size to prevent this
occurrence should be installed.

Especially Airtight Properties:-

If the stove is being fitted in a property where the
design air permeability is less than 5m

3

/ (h.m

2

) (nor-

mally newer properties built from 2006), then a per-
manent ventilation must be fitted to provide 550mm

2

of ventilation for each kW of rated output.  If a
draught stabiliser is also fitted then the requirement
is 850mm

2

per kW of rated output.  

If there is an extraction fan fitted in adjacent rooms
where this appliance is fitted, additional air vents
may be required to alleviate the possibility of
spillage of products of combustion from the appli-
ance/flue while the fan is in operation.  Refer to B.S.
8303 Part 1. 

As wind effects can create suction and pressure
zones on 

opposite sides of the dwelling it is

recommended to run the air vent from opposite
poles (North, South,  East & West) of the dwelling
and tee off for the air supply to the stove.  This
should negate the effect of suction and pressure
zones.  See Fig.6.

Summary of Contents for Lismore

Page 1: ...should be supervised at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thoroughly cooled When using the boiler stove in situations where...

Page 2: ...bles 11 16 Floor Protection 11 17 Plumbing 11 18 Pipe Thermostat 11 19 Regulations 11 20 Gravity Circuit 11 21 Injector Tee 12 22 Water Circuit Temperature 12 23 Flue Water Pipe Locations 13 24 Stove...

Page 3: ...TABLE OF CONTENTS PAGE NO 43 Cleaning a Matt Black Senotherm Stove 18 44 Frozen System 18 45 Prolonged Periods of Non Use 19 46 Fire Safety 19 47 Glass Replacement 19 48 CO Alarm 19 49 Exploded View 2...

Page 4: ...ed as per the requirements of the manual Failure to comply with the Installation requirements or Building Regulations will void your warranty Waterford Stanley reserve the right to replace any part du...

Page 5: ...egulations to have a carbon monoxide alarm fitted to any room with a solid fuel appliance Location 10 Clearance to combustible materials must be adhered to as described in the Clearance to Combustible...

Page 6: ...llow a build up of ashes in the ash pan as this will cause the grate to burn out prematurely Empty the ashpan when refuelling 7 Avoid slow burning of damp or unseasoned fuel as this will result in tar...

Page 7: ...be done in accor dance with current Standards and Local Codes It should be noted that the requirements and these publications may be superseded during the life of this manual Please refer to the curr...

Page 8: ...uld be at be at least 2300mm when measured horizontally and at least 1000mm when measured vertically see Fig 1 In circumstances where there are adjoining buildings structures roof openings there are a...

Page 9: ...550mm per each kw of rated output above 5kw should be provided where a flue draught stabiliser is used the total free area shall be increased by 300mm for each kw of rated output 9 All materials used...

Page 10: ...duct approval covers this appliance when installed in accordance with the manufactur er s instructions and relevant standards As there is currently no standard for Ducted Combustion Air Supply this do...

Page 11: ...oking on refu elling See Fig 7 REGULATIONS The plumbing must be in accordance with all relevant regulations and practices It must include a gravity circuit with expansion pipe open to the atmosphere T...

Page 12: ...id condensation on the boiler and return piping Fitting a pipe thermo stat to the flow pipe of the gravity circuit and wiring it into the pump control will ensure rapid circulation of the hot water In...

Page 13: ...ly to be used on the stove and warn them to use only the recommended fuels for the stove Advise the user what to do should smoke or fumes be emitted from the stove The customer should be warned to use...

Page 14: ...e a stove provides 2kW to the room and 8kW to the boiler and if the thermostatic damper shuts down the air supply to provide 4kW to the boiler then the heat to room will decrease pro portionally to 1k...

Page 15: ...gs 1 BSP Max Water Pressure 2 Bar Efficiency 76 3 76 8 Model Energy Efficiency Class Heat Output to Room Heat Output to Water Energy Efficiency Index Preferred Fuel Nominal Heat Output Net Efficiency...

Page 16: ...18 The hex head bolt should now be re inserted in the alternative position which will lock the grate in the wood burning position See Fig 16 USER INSTRUCTIONS Riddling Rod Wood Setting Fig 16 Fig 17 C...

Page 17: ...the boiler cleaning plate The boiler cleaning plate can also be removed when cleaning the chimney if the flue pipe is fitted to the back outlet Fig 21 PERIODIC MAINTENANCE Adjusting the Door Catch Ove...

Page 18: ...possibility that the water system may be frozen do not attempt to light the stove until you are certain there is no ice in the system possibly causing a blockage VITREOUS ENAMEL CLEANING General clean...

Page 19: ...s and carefully remove the broken glass c Clean the glass recess in the door d Replace the sealing rope in the door if necessary e Tighten screws f Replace glass only with ceramic glass 5mm thick See...

Page 20: ...THERMOSTAT G00479AXX 22 BADGE GASKET P00107AXX 23 GLASS CLIP GASKET P00117AXX 24 GLASS T00101AXX 25 PULL ROD KNOB U00001AXX 26 AIR CONTROL KNOB U00006AXX 27 SECONDARY AIR CONTROL U00018AXX 28 DOOR HAN...

Page 21: ...NOTES 21...

Page 22: ...NOTES 22...

Page 23: ...NOTES 23...

Page 24: ...24 Manufactured by Waterford Stanley Ltd Unit 401 403 IDA Industrial Estate Cork Road Waterford Ireland Tel 051 302300 Fax 051 302315 Item No N00524AXX Rev 005 YS280717...

Reviews: