background image

19

WARNING NOTE:

Properly installed, operated and maintained this
stove will not emit fumes into the dwelling.
Occasional fumes from the de-ashing and re-
fuelling may occur. However, persistent fume emis-
sion is potentially dangerous and must not be toler-
ated. If fume emission does persist, then the follow-
ing immediate action should be taken:

(a) Open doors and windows to ventilate room.

(b) Let the fire out or eject and safely dispose of 

fuel from the stove.

(c)  Check for flue or chimney blockage and clean if

required.

(d)  Do not attempt to relight the fire until the cause

of the fume emission has been identified and 
corrected.  If necessary seek expert advice.

The most common cause of fume emission is flue-
way or chimney blockage.  For your own safety
these must be kept clean at all times.

FIRE SAFETY

To provide reasonable fire safety, the following
should be given serious consideration.

1. Do not over fire the stove.
2. Over-firing will also damage painted or enamel

finish.

3. Install a smoke detector in the room.
4. A conveniently located class A fire extinguisher to

contend with small fires resulting from burning 
embers.

5. A practical evacuation plan.
6. A plan to deal with a chimney fire as follows:-

(a) Notify the fire department.

(b) Prepare occupants for immediate evacua-

tion.

(c) Close all openings into the stove.

GLASS REPLACEMENT

(a) Open the firedoor fully.
(b) Remove the four corner screws and clips and 

carefully remove the broken glass.

(c) Clean the glass recess in the door.
(d) Replace the sealing rope in the door if 

necessary

(e) Tighten screws.
(f) Replace glass only with ceramic glass 5mm 

thick. (See Fig 24).

(d) While awaiting the fire department watch for

ignition to adjacent combustibles from over- 

heated flue pipe or from embers or sparks 

from the chimney.

Fig. 24

CO ALARM

The fitting of CO Alarms in the same room as the
appliance is a compulsory requirement under cur-
rent Building Regulations. For ROI an additional CO
Alarm must be fitted either inside each bedroom or
within 5 metres of the bedroom door, refer to
Building Regulations Part J. Further guidance on the
installation of a carbon monoxide alarm is available
in BS EN 50292:2002 and from the alarm manufac-
turers instructions.

Provision of an alarm must not be considered a
substitute for either installing the appliance 
correctly or ensuring regular servicing and
maintenance of the appliance and chimney 
system.

WARNING:-

If the CO Alarm sounds unexpectedly:-

1. Open Doors and windows to ventilate the 

room and then leave the premises.

2. Let the fire go out.

PROLONGED PERIODS OF NON USE

If the stove is to be left unused for a prolonged peri-
od of time then it should be given a thorough clean
to remove ash and unburned fuel residues.  To
enable a good flow of air through the appliance to
reduce condensation and subsequent damage,
leave the air controls fully open.

It is important that the flue connection, any appliance
baffles or throat plates and the chimney are swept
prior to lighting up after a prolonged shutdown 
period.

Summary of Contents for Lismore

Page 1: ...should be supervised at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thoroughly cooled When using the boiler stove in situations where...

Page 2: ...bles 11 16 Floor Protection 11 17 Plumbing 11 18 Pipe Thermostat 11 19 Regulations 11 20 Gravity Circuit 11 21 Injector Tee 12 22 Water Circuit Temperature 12 23 Flue Water Pipe Locations 13 24 Stove...

Page 3: ...TABLE OF CONTENTS PAGE NO 43 Cleaning a Matt Black Senotherm Stove 18 44 Frozen System 18 45 Prolonged Periods of Non Use 19 46 Fire Safety 19 47 Glass Replacement 19 48 CO Alarm 19 49 Exploded View 2...

Page 4: ...ed as per the requirements of the manual Failure to comply with the Installation requirements or Building Regulations will void your warranty Waterford Stanley reserve the right to replace any part du...

Page 5: ...egulations to have a carbon monoxide alarm fitted to any room with a solid fuel appliance Location 10 Clearance to combustible materials must be adhered to as described in the Clearance to Combustible...

Page 6: ...llow a build up of ashes in the ash pan as this will cause the grate to burn out prematurely Empty the ashpan when refuelling 7 Avoid slow burning of damp or unseasoned fuel as this will result in tar...

Page 7: ...be done in accor dance with current Standards and Local Codes It should be noted that the requirements and these publications may be superseded during the life of this manual Please refer to the curr...

Page 8: ...uld be at be at least 2300mm when measured horizontally and at least 1000mm when measured vertically see Fig 1 In circumstances where there are adjoining buildings structures roof openings there are a...

Page 9: ...550mm per each kw of rated output above 5kw should be provided where a flue draught stabiliser is used the total free area shall be increased by 300mm for each kw of rated output 9 All materials used...

Page 10: ...duct approval covers this appliance when installed in accordance with the manufactur er s instructions and relevant standards As there is currently no standard for Ducted Combustion Air Supply this do...

Page 11: ...oking on refu elling See Fig 7 REGULATIONS The plumbing must be in accordance with all relevant regulations and practices It must include a gravity circuit with expansion pipe open to the atmosphere T...

Page 12: ...id condensation on the boiler and return piping Fitting a pipe thermo stat to the flow pipe of the gravity circuit and wiring it into the pump control will ensure rapid circulation of the hot water In...

Page 13: ...ly to be used on the stove and warn them to use only the recommended fuels for the stove Advise the user what to do should smoke or fumes be emitted from the stove The customer should be warned to use...

Page 14: ...e a stove provides 2kW to the room and 8kW to the boiler and if the thermostatic damper shuts down the air supply to provide 4kW to the boiler then the heat to room will decrease pro portionally to 1k...

Page 15: ...gs 1 BSP Max Water Pressure 2 Bar Efficiency 76 3 76 8 Model Energy Efficiency Class Heat Output to Room Heat Output to Water Energy Efficiency Index Preferred Fuel Nominal Heat Output Net Efficiency...

Page 16: ...18 The hex head bolt should now be re inserted in the alternative position which will lock the grate in the wood burning position See Fig 16 USER INSTRUCTIONS Riddling Rod Wood Setting Fig 16 Fig 17 C...

Page 17: ...the boiler cleaning plate The boiler cleaning plate can also be removed when cleaning the chimney if the flue pipe is fitted to the back outlet Fig 21 PERIODIC MAINTENANCE Adjusting the Door Catch Ove...

Page 18: ...possibility that the water system may be frozen do not attempt to light the stove until you are certain there is no ice in the system possibly causing a blockage VITREOUS ENAMEL CLEANING General clean...

Page 19: ...s and carefully remove the broken glass c Clean the glass recess in the door d Replace the sealing rope in the door if necessary e Tighten screws f Replace glass only with ceramic glass 5mm thick See...

Page 20: ...THERMOSTAT G00479AXX 22 BADGE GASKET P00107AXX 23 GLASS CLIP GASKET P00117AXX 24 GLASS T00101AXX 25 PULL ROD KNOB U00001AXX 26 AIR CONTROL KNOB U00006AXX 27 SECONDARY AIR CONTROL U00018AXX 28 DOOR HAN...

Page 21: ...NOTES 21...

Page 22: ...NOTES 22...

Page 23: ...NOTES 23...

Page 24: ...24 Manufactured by Waterford Stanley Ltd Unit 401 403 IDA Industrial Estate Cork Road Waterford Ireland Tel 051 302300 Fax 051 302315 Item No N00524AXX Rev 005 YS280717...

Reviews: