GB & IE version
5
1.1
Special Notice for LPG Fuel Type:
Important Notice –
Please read carefully for all LPG stove installations
This manual covers the fuel type Natural Gas and LPG versions
This is a Mandatary Requirement for Natural Gas & LPG
- the gas feed pipe to the rear/side
of this stove must be a minimum of 16mm in diameter this will ensure the correct pressure and
flow to the stove. Plus a ON/OFF tap with a test point must be fitted just before the 8mm stove
pipe is connected
LPG Specific – Please Read
If this stove is LPG it will only operate at 37.5 mb of supply pressure (+/- 5% tolerance)
If you have other LPG appliances in your home such as cooker or central heating boiler this
stove must be fed directly from the main feed pipe to the other LPG appliances. The other
appliances must be balanced so each appliance is supplied with sufficient gas pressure and
flow to operate
For this stove to work correctly you must maintain a constant supply pressure of 37.5 mbars (+/-
5% tolerance) to the ON/OFF tap and test point at the side of this stove
37.5 mbars of supply pressure must be maintained and tested at the stove test point when
other appliances in the property are running on full flame/full heat to ensure the stove has been
fed with sufficient flow and pressure of 37.5 mbar
If you
DO NOT
have any other LPG appliances in your property, again you would use a 16 mill
diameter pipe to feed the stove directly from the regulator
If you
’re not able to maintain 37.5 mbar of pressure at the inlet tap (with test point incorporated)
at the rear or side of this stove we recommend you do not fit this stove.
If supply pressure to this stove drops below the 37.5 mbar the flame will reduce in height and
will potentially cause black spotting on the glass & sooting on the Logs - this is not covered by
any warranty
Mandatory Requirement for Installing & Commissioning this stove:
·
Supply Pressure of 37.5 mbar to the stove (LPG Variant only)
·
16mm diameter minimum gas feed pipe to this stove
·
Fitting of an ON/OFF Tap with a Pressure Test Point fitted to the side of this stove
(this tap is not supplied with the stove)
·
Rear Chain kit is fitted – full instructions in this stove
·
Flue locking screws x2 fitted into the flue collar
·
The stove is installed, commissioned & operated as stated in this manual