background image

Installation Instructions for 83KM/93KM–85KM/95KM IDH Max Cylindrical Locks

BEST ACCESS SYSTEMS

a Product Group of Stanley Security Solutions, Inc

23

Installation Instructions for 83KM/93KM–85KM/95KM IDH Max Cylindrical Locks

Testing the installation

Perform the following steps to test the installation. Also, 
perform any standard testing recommended by the 
manufacturer of the access control panel. If you encounter 
problems, see 

Troubleshooting the installation,

 on 

page 24.

1  Check the control electronics’ green status LED and the 

panel interface module’s green status LED.
Both LEDs should be blinking, indicating that the 
communication connection between the panel 
interface circuit board and the lock’s control 
electronics circuit board is OK.

2 After performing any necessary programming for the 

lock and putting the door in a locked mode, use a valid 
token to access the lock.
Confirm that the red reader LED, green reader LED, and 
sounder respond as expected.
The lock should allow access, verifying that the 
solenoid is working.
To check that the reader is working, view the lock’s 
event history and verify that the information recorded 
for the token is correct.

3 Use an invalid token to attempt to access the lock.

Confirm that the red reader LED, green reader LED, and 
sounder respond as expected.
The lock should deny access.

4 With the door armed, attempt to exit through the 

door.
The request-to-exit (RQE) feature should let you exit 
without triggering an alarm by the access control 
panel.

5 Remove power from the lock and check whether the 

door remains locked or is unlocked.
Verify that the lock fails safe or secure, according to its 
function.

6 With the door armed, hold the door open. Hold a 

magnet against the edge of the door, over the door 
status sensor, until the access control panel sees the 
door as closed. Then remove the magnet.
Verify that the appropriate alarm response is triggered 
by the access control panel, indicating that the door 
status sensor is working.

Summary of Contents for 83KM-93KM

Page 1: ...sentative A panel interface module is provided with the lock The panel interface module receives token data and lock sensor data from the lock through an RS 485 connection It translates this data into...

Page 2: ...requirements for ANSI BHMA 156 25 Side of door Range Inside 66 F to 74 F 19 C to 23 C Outside 31 F to 151 F 35 C to 66 C Side of door Range Inside and outside 32 F to 120 F 0 C to 49 C Use the follow...

Page 3: ...distance from the power supply to the first door If powering more than one door daisy chained to the same power supply add the total distance of the power runs between the doors Refer to the table bel...

Page 4: ...rk the vertical centerline of the door edge Note The recommended height from the floor to the centerline of the lock is 38 2 Fold the W16 Template Installation Template for 83KM 93KM IDH Max Cylindric...

Page 5: ...HRB reader wire hole solenoid wire hole 3 8 diameter through door before drilling chassis hole chassis hole 2 1 8 diameter through door after drilling solenoid wire hole latch hole 1 diameter meets ch...

Page 6: ...Drill a wire access hole through the frame side of the hinge mortise 2 Drill holes or pockets for the splice connectors in the frame and door Refer to the hinge manufacturer s specifications for the...

Page 7: ...drill through bolt holes 9KW only 1 Press the drill jig KD303 onto the door engaging it with the latch tube prongs Make sure the front edge of the jig is parallel with the door edge 2 Drill the throu...

Page 8: ...hole in the fire plate and into the hole drilled through the door to the hinge mortise 2 From the latch edge of the door fish the field wire harness through the door to the hinge mortise 3 Make sure t...

Page 9: ...s out the wire hole to the inside of the door as shown in Figure 8 9 Install strike box and strike plate 1 In alignment with the center of the latchbolt mortise the door jamb to fit the strike box and...

Page 10: ...r past the keeper 4 Slide the knob lever off of the sleeve Caution Be careful that you do not disconnect the lever keeper spring 11 Adjust for door thickness 1 Determine the door s thickness 2 Pull th...

Page 11: ...chassis hole routing the solenoid wire through the notch Caution Make sure that the latch tube prongs engage the chassis frame and that the latch tailpiece engages the retractor 13 Install fire plate...

Page 12: ...the chassis aligning the holes in the rose liner with the holes prepared in the door Caution Make sure that there is clearance for the solenoid wire between the RQE rose liner and the door 2 Install t...

Page 13: ...chassis sleeve so it rests on the hub Note You do not need to change the positions of the DIP switches on the control electronics circuit board located in the inside escutcheon By default switches 1 t...

Page 14: ...holes at the top and bottom of the fire plate 3 Tighten the mounting screw to the outside escutcheon until the fire plate and escutcheon are securely mounted to the door 4 Connect the reader wire har...

Page 15: ...n making the sensor connections and solenoid connection make sure there are no loose wire connections where the wires are inserted into the connectors the connectors are firmly mated 18 Install bottom...

Page 16: ...top cover above the fire plate and slide it down over the guide notches on the fire plate Caution Make sure that the top cover does not pinch any wires as you slide it over the fire plate 2 Use two co...

Page 17: ...levers to check that they operate smoothly 21 Install core and throw member 1 Install the blocking plate onto the throw member Caution You must use the blocking plate to prevent unauthorized access F...

Page 18: ...wires Install the wire transfer hinge 23 Install lock power supply optional If you are providing a separate power supply for the lock instead of providing power via the panel interface module connect...

Page 19: ...l interface circuit board Note JP2 and JP3 shown in Figure 22a are used for manufacturing purposes only 3 Connect the RS 485 shield wire to one of the GND terminals on J1 26 Connect panel interface mo...

Page 20: ...put Switch like output to the access control panel reader interface that indicates the status of the lock s RQE switch By default the output is closed to indicate the RQE switch is closed Note The loc...

Page 21: ...ovided to the Reader LED input and the Sounder input must be greater than 3 5 volts DC to be interpreted as a 5 volts DC signal Signals with voltage less than 0 8 volts DC are interpreted as 0 volts D...

Page 22: ...cuit board both must be set to ON automatic baud rate detection 38400 bps Switch 2 OFF Switch 3 OFF 19200 bps Switch 2 ON Switch 3 OFF 9600 bps Switch 2 OFF Switch 3 ON 2400 bps Switch 2 ON Switch 3 O...

Page 23: ...that the red reader LED green reader LED and sounder respond as expected The lock should allow access verifying that the solenoid is working To check that the reader is working view the lock s event...

Page 24: ...ate detection or to the same positions as DIP switches 2 and 3 on the panel interface circuit board Check the connections for all communication field wiring Check the communication connections between...

Reviews: