Permitted maximum values
Operating Instructions MT-xx6-A
R. STAHL HMI Systems GmbH / OI_MT_xx6_A_en_V_03_00_26.docx / 03.11.2020
Page 21 of 60
Reader WCR1 (X8) (connection voltage supply, X8.1-2):
U
i
=
11.4
V
I
i
=
200
mA
P
i
=
2.28
W
C
i
=
25
nF
L
i
=
0
mH
Reader WCR1 (power supply reader, X8.3-4):
U
o
=
5,88
V
l
o
=
200
mA
P
o
=
1.18
W
a)
The maximum values for zone 1 group IIC are:
C
i
=
5.3
µF
C
o
=
27.7
37.7
µF
L
i
=
0
mH
L
o
=
2
1
µH
C
o
and L
o
pairs directly above/underneath each other may be used.
The maximum values for zone 1 group IIB are:
C
i
=
5.3
µF
C
o
=
55.7
94.7
µF
L
i
=
0
mH
L
o
=
20
10
µH
C
o
and L
o
pairs directly above/underneath each other may be used.
b)
The maximum values for zone 2 group IIC are:
C
i
=
5.3
µF
C
o
=
80.7
664.7
µF
L
i
=
0
mH
L
o
=
2
1
µH
C
o
and L
o
pairs directly above/underneath each other may be used.
The maximum values for zone 2 group IIB are:
C
i
=
5.3
µF
C
o
= 114.7 234.7
µF
L
i
=
0
mH
L
o
=
20
10
µH
C
o
and L
o
pairs directly above/underneath each other may be used.
Reader WCR1 and WCR2 (signal input / output, X8.5-8):
U
i
=
15
V
U
o
=
5.88
V
I
i
=
500
mA
I
o
=
51
mA
P
i
=
2.5
W
P
o
=
75
mW
a)
The maximum values for zone 1 group IIC are:
C
i
=
0
µF
C
o
=
34
µF
L
i
=
0
mH
L
o
=
2
µH
C
o
and L
o
pairs directly above/underneath each other may be used.
The maximum values for zone 1 group IIB are:
C
i
=
0
µF
C
o
=
63
µF
L
i
=
0
mH
L
o
=
20
µH
C
o
and L
o
pairs directly above/underneath each other may be used.
b)
The maximum values for zone 2 group IIC are:
C
i
=
0
µF
C
o
=
87
µF
L
i
=
0
mH
L
o
=
2
µH
C
o
and L
o
pairs directly above/underneath each other may be used.
The maximum values for zone 2 group IIB are:
C
i
=
0
µF
C
o
=
130
µF
L
i
=
0
mH
L
o
=
20
µH
C
o
and L
o
pairs directly above/underneath each other may be used.