Permitted maximum values
Operating Instructions MT-xx6-A
R. STAHL HMI Systems GmbH / OI_MT_xx6_A_en_V_03_00_26.docx / 03.11.2020
Page 19 of 60
8.3
External intrinsically safe circuits
USB-0 (X4) and USB-2 (X6):
U
o
=
5.9
V
I
o
=
2.18
A
P
o
=
1.24
W
a)
The maximum values for zone 1 group IIC are:
C
i
=
0
µF
C
o
=
5.1
11
28
43
µF
L
i
=
0
mH
L
o
=
10
5
2
1
µH
C
o
and L
o
pairs directly above/underneath each other may be used.
The maximum values for zone 1 group IIB are:
C
i
=
0
µF
C
o
=
14
40
79
200
µF
L
i
=
0
mH
L
o
=
50
20
10
5
µH
C
o
and L
o
pairs directly above/underneath each other may be used.
b)
The maximum values for zone 2 group IIC are:
C
i
=
0
µF
C
o
=
12
24
74
670
µF
L
i
=
0
mH
L
o
=
10
5
2
1
µH
C
o
and L
o
pairs directly above/underneath each other may be used.
The maximum values for zone 2 group IIB are:
C
i
=
0
µF
C
o
=
37
92
200
790
µF
L
i
=
0
mH
L
o
=
50
20
10
5
µH
C
o
and L
o
pairs directly above/underneath each other may be used.
Reader RSi1 and RSi2 (X8) +Uint 1 (power supply circuit, X8.0, bridge to X8.2):
U
o
=
10.4
V
l
o
=
220
mA
P
o
=
2.29
W
a)
The maximum values for zone 1 group IIC are:
C
i
=
1.72
µF
C
o
=
0.8
µF
L
i
=
0
mH
L
o
=
10
µH
C
o
and L
o
pairs directly above/underneath each other may be used.
b)
The maximum values for zone 2 group IIC are:
C
i
=
1.72
µF
C
o
=
4.68
µF
L
i
=
0
mH
L
o
=
10
µH
C
o
and L
o
pairs directly above/underneath each other may be used.
Reader RSi1 (X8) +U_ex1 (power supply circuit, X8.2, bridge from X8.0):
U
i
=
12.4
V
I
i
=
220
mA
P
i
=
2.29
mW
C
i
=
25
nF
L
i
=
0
mH