Technical data
8
259910 / L40260300020
2017-09-18·BA00·III·en·00
Linear Luminaire with LED
Series EXLUX L402/2
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
5
Technical data
Technical Data
Electrical data
Control gear
AC: 220 ... 240 V ±10 %; 50 ... 60 Hz
DC: 200 ... 250 V ±10 %
Inrush current
I
peak
= 53,5 A; Δt = 124,8
m
s
maximale Anzahl der Leuchten pro Leitungsschutzschalter:
Power factor
)
0.93
Degree of protection IP66 / IP67 (IEC 60598)
Protection class
I (with internal PE connection)
Impact strength
(IK code)
IK10 (IEC 62262)
Disconnection of the
light
When opening the luminaire
Switch with safety lock (optional); when opening the central lock all poles of the
voltage supply to the ballast are disconnected; contacts of the switching
element are positive opening, they can only be switched on again when the
luminaire trough and the central locking system are closed.
Luminous characteristics
Luminous flux
Values apply to T
a
= +25 °C.
Luminous flux decrease at T
a
= +55 °C to 85% of the nominal value.
Typ
10 A
16 A
20 A
25 A
B
8
12
16
20
C
13
21
27
33
K
27
43
54
67
L4
02/21.2
-.5..-..0
L4
02/22.4
-.5..-..0
L4
02/21.2
-.5..-..1
L4
02/22.4
-.5..-..1
Power consumption [W]
28
52
28
52
Colour rendering [Ra]
)
80
)
80
)
70
)
70
Colour temperature [K]
5000
5000
5700
5700
without diffuser
Luminous flux [lm]
3100
6200
3400
6800
Luminaire efficiency [lm/W]
111
119
121
131
with diffuser
Luminous flux [lm]
2550
5100
2800
5600
Luminaire efficiency [lm/W]
91
98
100
108
Summary of Contents for EXLUX L402/2 Series
Page 20: ......