Mounting and installation
16
259910 / L40260300020
2017-09-18·BA00·III·en·00
Linear Luminaire with LED
Series EXLUX L402/2
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
7.3.2 Electrical connections
Electrical connection
Observe the maximum clamping possibility of the connecting terminals (see chapter
"Technical data").
For optional screw-type terminals, two conductors per clamping unit can be clamped
(ingoing and outgoing wiring).
Note:
• Clamping must be carried out precisely!
• Do not clamp any part of the conductor insulation!
• Do not interchange the conductors!
• Observe the technical regulations when connecting the conductor!
• Clamp the conductor firmly.
• The terminal cover of optional screw-type terminals does not have to be removed to
clamp the conductor!
• Optional screw-type terminals: Firmly tighten screws (tightening torque 2 Nm, for
unused clamping units 0.7 Nm)!
Connection terminals
Through wiring of the mains supply connection
Standard:
Spring clamp terminals
up to 4 mm
2
Optional:
Screw-type terminals
up to 4 mm
2
finely and
extra finely stranded,
and 6 mm
2
solid
Stripping length:
10 ... 11 mm
Stripping length:
10 ... 11 mm
15516E00
15438E00
NOTICE
Through wiring with 2.5 mm
2
cross section for max. 16 A.
N
L1
L2
L3
L3
L2
L1
N
L1, L2, L3 = Phase
N
= Neutral conductor
PE
= Protective conductor