Temperature Input Module Zone 1
Series 9482/32
8.1
Dimensions / Fastening Dimensions
8.2
Mounting / Dismounting, Operating Position
8.2.1 Mounting / Dismounting on BusRail
Mounting on BusRail
Dimensional drawings (All dimensions in mm [inches]) – Subject to change
15254E00
9482/32
NOTICE
Malfunction or device damage caused by improper mounting.
Non-compliance may lead to material damage!
• Only install and operate the device in a vertical or horizontal position!
(Horizontal orientation: Reading direction from below)
05683E00
• Position the module vertically at the
intended slot of the BusRail and press
slightly to snap it into place.
• The module may no longer be
loosened without actuating the handle.
• Plug the pluggable terminals X1 and
X2 into the module and secure it
against loosening using safety screws
(tightening torque 0.5 to 0.6 Nm).
• If necessary, mount a partition to
ensure a distance of at least 50 mm
between the intrinsically safe and
non-intrinsically safe electric circuits o
r release the adjacent slot on the
BusRail.
64
[2,52]
128,5 [5,06]
68
[2,68]
70
[2,76]
96,5
[3,8]
98 [3,86]
BusRail
BusRail