Technical Data
10
218149 / 948260310010
2018-07-03·BA00·III·en·02
Temperature Input Module Zone 1
Series 9482/32
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Technical Data
connectable
resistance
temperature
detectors /
resistance
transmitters
Reaction time
Type
Reference
Measuring range
(ITS-90)
Medium
resolution
Pt100
IEC 60751
-200 to +850 °C
0.1 K
Pt500
IEC 60751
-200 to +850 °C
0.1 K
Pt1000
IEC 60751
-200 to +850 °C
0.1 K
Ni100
DIN 43760
-60 to +180 °C
0.1 K
Ni500
DIN 43760
-60 to +180 °C
0.1 K
Ni1000
DIN 43760
-60 to +180 °C
0.1 K
Pt46
2)
GOST 6651-94
-200 to +1100 °C
0.15 K
Pt50
2)
GOST 6651-94
-200 to +1100 °C
0.15 K
Pt100
1)
GOST 6651-94
-200 to +1100 °C
0.1 K
Cu53
2)
GOST 6651-94
-50 to +180 °C
0.1 K
M50
1)
GOST 6651-94
-200 to +200 °C
0.15 K
M100
1)
GOST 6651-94
-200 to +200 °C
0.1 K
Resistance
transmitter (3-wire)
–
0 to 500
O
0.02
O
Resistance
transmitter (3-wire)
–
0 to 2.5 k
O
0.10
O
Resistance
transmitter (3-wire)
–
0 to 5 k
O
0.20
O
Resistance
transmitter (3-wire)
–
0 to 10 k
O
0.4
O
Resistance
transmitter (3-wire)
–
-200 to +850 °C
0.1 K
Joystick (4-wire)
–
500 to 10 k
O
Type
Type of
connection
Operating mode
4 channel fast
Error control
Operating mode
8 channel accurate
Error control
Activated
Deactivated Activated
Deactivated
RTD
2-wire
400 ms
400 ms
750 ms
720 ms
RTD
3-wire
400 ms
400 ms
750 ms
720 ms
RTD
4-wire
400 ms
400 ms
750 ms
720 ms
R
2-wire in R
400 ms
400 ms
750 ms
720 ms
R
3-wire in %
90 ms
70 ms
750 ms
720 ms
R
4-wire in R
400 ms
400 ms
750 ms
720 ms
R
4-wire in %
90 ms
70 ms
750 ms
720 ms
To achieve the times with "error control deactivated", the error control must be
"OFF" for all channels! As soon as the error control is "ON" for just one
channel, the times for "error control activated" apply.