Engineering
Mechanical data
Degree of protection (IEC 60529)
IP20
Module enclosure
polyamide 6GF
Fire resistance (UL 94)
V2
Pollutant class
corresponds to G3
Dimensions
L = 128 mm, W = 96.5 mm, H = 67 mm
Indication
LED indication
Module requires maintenance
"M/S" LED, blue
Operating state
"RUN" LED, green
Group error
"ERR" LED, red
Channel error
LED red for each channel
Function indication
Retrievable parameters
Manufacturer, Type, hardware revision, software revision,
serial number
Error indication
Module status and alarms
• Internal bus error primer / redundant
• No response from IOM
• Configuration does not correspond to the module
• Hardware error
• Excess temperature
• Slot error
• Module requires maintenance
Signal errors for each channel
Signal status bit
"0" = signal interference present; "1" = signal valid
Wire breakage input
Resistance temperature detector / resistance transmitter:
> 100 Ω; thermocouples / mV-sensors: > 1000 Ω
Short circuit input
Resistance temperature detector / resistance transmitter: < 15 Ω
Measuring range
Exceeding / shortfall
Mounting / Installation
Installation conditions
Mounting type
On 35 mm DIN rail NS 35/15 (DIN EN 60715)
Mounting orientation
horizontal or vertical (observe operating instructions)
NOTICE
Failure of the devices installed in the cabinet caused by too high ambient
temperature!
Non-compliance can result in material damage.
• Install and adjust the cabinet in such a way that it is always operated within
the permissible temperature range.
• Carefully observe the "Cabinet installation guide".
You can find detailed information about project engineering in the
"Cabinet installation guide" (download from www.r-stahl.com,
Product documentation, subitem "Engineering").